| Date |
Text |
| 2006-08-19 00:00:00 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS DESIGNED BY THE REGISTERED ARCHITECT. THE |
| | ORIGINAL SIGNATURE IS |
| | REQUIRED ON THE SEAL, AND THE BUSINESS |
| | LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), IS REQUIRED IN THE TITLE |
| | BLOCK OF EACH SHEET. 61G1-16.004(1)(5) |
| | AND FS 481.219 481.2055. |
| | |
| | 2. SHT D1 DEMO REQUIREMENTS #'S 2 & 3 |
| | DEAD ENDS ARE NOT ALLOWED. SECTION |
| | 704.5. |
| | |
| | 3. SHT D1 GREASE INTERCEPTORS SHALL BE |
| | PUMPED OUT AND WASHED DOWN PRIOR TO |
| | REMOVING. |
| | |
| | 4. SHTS A1, A5.2 & A9 BREAK ROOM SINK |
| | SHALL BE ACCESSIBLE. PLEASE SUBMIT A |
| | DETAIL SHOWING THE FOLLOWING: |
| | A. 11-4.24.3 KNEE CLEARANCE |
| | B. 11-4.24.4 SINK DEPTH |
| | C. 11-4.24.5 CLEAR FLOOR SPACE (FORWARD |
| | APPROACH REQUIRED. NO CABINET DOORS |
| | ALLOWED IN CLEAR FLOOR SPACE). |
| | D. 11-4.24.7 FAUCETS |
| | |
| | 5. SHT A5.3 DRINKING FOUNTAIN TO BE |
| | ACCESSIBLE. SUBMIT A DETAIL SHOWING THE FOLLOWING: |
| | A. 11-4.15.2 SPOUT HEIGHT |
| | B. 11-4.15.5 CLEARANCES AND CLEAR FLOOR |
| | SPACE. (FORWARD APPROACH REQUIRED). |
| | |
| | 6. SHT A5.2 DETAIL 1 INDICATES A SINK |
| | WITH AN EYEWASH STATION. MORE |
| | INFORMATION REQUIRED. PLEASE SUBMIT A |
| | DETAIL AND MANUFACTURE SPECIFICATION & INSTALLATION |
| | SHEETS. |
| | |
| | 7. A5.3 FAMILY TOILET ROOM, (129), |
| | WOMENS TOILET ROOM, (130), MEN'S TOILET |
| | FOOM, (127). SHALL BE ACCESSIBLE. SUBMIT |
| | THE FOLLOWING: |
| | FOR W/C'S... |
| | A. 11-4.16.3 HEIGHT |
| | B. 11-4.16.4 GRAB BARS |
| | C. 11-4.16.5 FLUSH CONTROLS |
| | D. 11-4.16.6 DISPENSERS |
| | FOR STALLS.... |
| | A. 11-4.17.3 EXCEPTION 2 THE ACCESSIBLE |
| | W/C SHALL BE LOCATED IN THE CORNER, |
| | DIAGONAL TO THE DOOR. (SEE MENS TOILET |
| | ROOM). |
| | FOR URINALS... |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.4 FLUSH CONTROLS |
| | FOR LAVS.... |
| | A. 11-4.19.2 HEIGHT & CLEARANCES |
| | B. 11-4.19.4 EXPOSED PIPES & SURFACES |
| | C. 11-4.19.5 FAUCETS |
| | D. 11-4.19.6 MIRRORS |
| | |
| | 8. SHT A5.3 DETAIL 6 TOILET ELEVATION |
| | FOR THE ACCESSIBLE STALL DOES NOT SHOW |
| | THE LAV. SECTION 106.1.1. |
| | |
| | 9. SHT A5.3 FAMILY TOILET, W/C TO BE 18" |
| | OFF THE WALL TO CENTERLINE OF THE |
| | FIXTURE. SEE FIG. 28. |
| | |
| | 10. ALL PME & REFRIG. SHEETS. ENGINEERS |
| | SHALL LEGIBLY INDICATE THEIR NAME, AND |
| | LICENSE NUMBER, AS WELL AS, THE NAME, |
| | ADDRESS AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER OF THE ENGINEERING BUSINESS ON |
| | EACH SHEET. 61G15-23.002(2) & FS 471.025 |
| | |
| | 11. SHT P1 GREASE INTERCEPTORS SHALL BE |
| | SIZED BY THE UTILITY DEPT. ENVIRONMENTAL COMPLIANCE |
| | MGR. PLEASE CONTACT LYNN |
| | MASSON, (561) 822-2271, FAX (561) |
| | 822-2279, OR E-MAIL [email protected] FOR |
| | A DETERMINATION ON INTERCEPTOR SIZE. |
| | WASTE ORDINANCE #3434. |
| | |
| | 12. SHT P1 CLEANOUTS REQUIRED PER |
| | SECTIONS 708.3.1, 708.3.3, & 708.3.5 |
| | REQUIRED ON THE SANT., GREASE, AND |
| | CONDENSATE SYSTEMS. |
| | |
| | 13. SHT P1 INDICATES REMOVAL OF ALL |
| | FLOOR DRAINS. IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM |
| | DEAD ENDS SHALL BE PROHIBITED. SECTION |
| | 704.5. |
| | |
| | 14. SHT P1 MINIMUM FACILITIES REQUIRES |
| | TWO DRINKING FOUNTAINS. ONLY A HI/LOW |
| | DRINKING FOUNTAIN IS SHOWN. IF A FIXTURE |
| | HAS ONLY ONE DRAIN LINE AND ONE SUPPLY |
| | LINE IT IS CONSIDERED ONE FIXTURE. |
| | PLEASE INDICATE THE LOCATION OF EWC-1 AS |
| | SHOWN ON SHT P4 PLUMBING FIXTURE |
| | SCHEDULE. TABLE 403.1. |
| | |
| | 15. SHT P-3 WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT ALL QUICK CLOSING VALVES, |
| | SUCH AS DISH WASHERS, ICE MAKERS, ETC. |
| | PLEASE SHOW ONE AT THE ICE MAKER. ALL |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURES, IN AN "EFFECTIVE |
| | RANGE" NOT IN THE CEILING AS SHOWN AT |
| | THE LAVS IN MENS AND WOMENS TOILET ROOM. |
| | SECTION 604.9 AND PDI-WH 201. |
| | |
| | 16. SHT P3 2 WAY CLEANOUTS ARE REQUIRED |
| | AT THE INLET AND EXIT OF EACH GREASE |
| | INTERCEPTOR. |
| | |
| | 17. SHT P3 THE SANT. RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN BETWEEN |
| | FIXTURE AND 1ST FIXTURE. |
| | SHOW ALL PIPE SIZES ON THE RISER |
| | DIAGRAM. SECTION 106.1.1 AND TABLES |
| | 710.1(1) & 710.1(2). |
| | |
| | 18. SHT P4 COFFEE BAR PLUMBING EQUIPMENT CONNECTION |
| | SCHEDULE CO8. SUBMIT MANUF SPECIFICATION SHEETS FOR THE |
| | WATER |
| | FILTER. FILTER SHALL COMPLY WITH NSF 42. |
| | |
| | 19. SUBMIT A CONDENSATE RISER DIAGRAM |
| | ISOMETRIC SHOWING ALL PIPE SIZES. |
| | SECTION 106.3.5.1.3. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |