Text |
| 2006-10-06 00:00:00 | PROVISO:PLAN CHECK ONLY | | | | | | 1.PLAN SHEET M1, THE ROOFTOP EQUIPMENT | | | PIPING RUNOUT INDICATES 3/4" FOR ALL | | | UNITS.PLEASE NOTE, CONDENSATE SHALL BE | | | INSTALLED PER MANUFACTURER'S | | | SPECIFICATIONS, FULL LINE SIZE FOR | | | PROPER DRAINAGE. | | | | | | 2.ADDITIONAL PERMITS REQUIRED FOR | | | HOOD, FIRE SUPPRESSION & WALK-IN | | | COOLERS.PLEASE PROVIDE MANUFACTURER'S | | | SUBMITTAL DATA WITH PERMIT APPLICATION. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561)805-6719 OR | | | E-MAIL [email protected]. |
|