| 2006-08-03 00:00:00 | ********** UNSAT ************* |
| | |
| | **********WAL-MART NEW /REMODEL****** |
| | |
| | ** PLEASE SEE PLANS WERE ONLY SUBMITTED |
| | FOR "PLAN REVIEW" AND HAVE NOT BEEN |
| | SUBMITTED FOR PERMIT. |
| | |
| | |
| | 1) NOTE: PLEASE SEE ALL ARCHITECTURAL |
| | SHEETS CONTAIN A RAISED SEAL OVER A |
| | "PHOTO-COPIED" SIGNATURE OF THE |
| | ARCHITECT OF RECORD. PLEASE KNOW UNDER |
| | FS 481.221 AND FAC 61G1-16.004 THE |
| | SIGNATURE SHALL BE ORIGINAL. SEALED |
| | PHOTO-COPIED PLANS ARE NOT ACCEPTABLE. |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | TRADES AND FOR ALL SHEETS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 2) NOTE: PLEASE ALSO SEE "S-1, S-2, AND |
| | S-3, AS THESE ALSO CONTAIN A RAISED SEAL |
| | OVER A PHOTO-COPIED SIGNATURE> |
| | PLEASE SEE FS 472.025, FAC 61G17 |
| | REQUIRED FOR BOTH SETS AND WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER |
| | REVIEWER(S). |
| | |
| | 3) NOTE: PLEASE SEE MISSING REQUIRED |
| | INFORMATION ON TITLE BLOCKS FOR |
| | ARCHITECTURAL AND ENGINEERING FIRMS. |
| | PLEASE SEE FLORIDA ADMINISTRATIVE CODE |
| | 61G1-16.004 AND FLORIDA STATUES 481.219 |
| | FOR THE ARCHITECTURAL FIRM AND PLEASE |
| | SEE FAC61G15-23.002 AND FS 471.023 FOR |
| | ENGINEERING FIRM. |
| | PLEASE SEE MISSING PRINTED NAME AND |
| | LICENSE NUMBER'S FOR INDIVIDUAL |
| | DESIGNERS OF RECORD. |
| | PLEASE SEE MISSING CERTIFICATE OF |
| | AUTHORIZATION NUMBER REQUIRED FOR BOTH |
| | FIRMS REQUIRED ON TITLE BLOCKS ALSO. |
| | ** PLEASE KNOW THIS IS REQUIRED FOR ALL |
| | SHEETS AND FOR ALL TRADES WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER REVIEWER(S). |
| | |
| | 4) NOTE: PLEASE BE SURE PLANS REFLECT |
| | THE FOLLOWING CODES AT A MINIMUM. |
| | PLEASE SEE PLANS MENTIONS THE 2004 |
| | FLORIDA ELECTRICAL CODE, HOWEVER CHAPTER |
| | 27 OF THE 2004 FBC ADOPTED THE 2002 |
| | NFPA-70 (NEC). |
| | PLEASE ALSO LIST THE FOLLOWING. |
| | NFPA-72 2002, NFPA-101 2003. |
| | |
| | 5) NOTE: PLEASE SEE 2004 FBC CHAPTER 13. |
| | PLEASE SEE 13-413.1ABC.1, PROVIDE WORST |
| | CASE FOR FEEDERS AND BRANCH CIRCUITS. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, .1.3. |
| | PLEASE PROVIDE LIGHTING CONTROL/ ENERGY |
| | MANG SYSTEM DETAILS. |
| | PLEASE SEE 13-415.1.AB.1 , |
| | 13-415.2.ABC.1 FOR TABLES 415.2.C.1 AND 415.2.B.1. |
| | PLEASE ALSO BE SURE ALL ENERGY |
| | CALCULATIONS ARE SIGNED, DATED AND |
| | SEALED BY THE DESIGNER(S) OF RECORD. |
| | |
| | 6) NOTE: PLEASE SEE PANELS IN |
| | DELI/BAKERY ARE WHICH DO NOT SEEM TO |
| | MEET 110.26 FOR MIN CLEARANCES. |
| | |
| | 7) NOTE: PLEASE SEE MINIMUM DOOR/ EGRESS REQUIREMENTS |
| | SHALL BE REQUIRED FOR MAIN |
| | ELECTRICAL ROOM. PLEASE ALSO SEE PANIC |
| | HARDWARE AND DOORS CHANGES WILL BE |
| | REQUIRED FOR NEW EQUIPMENT. |
| | |
| | 8) NOTE: PLEASE SEE PANEL WHICH IS BEING |
| | SHOWN IN STORAGE ROOM SHALL BE A |
| | DEDICATED ELECTRICAL/EQUIPMENT ROOM OR |
| | PLEASE RELOCATE PANEL. |
| | PLEASE SEE 110.26,408.7, AND 240.24 AS |
| | STORAGE OF ANY TYPE FOR MIN CLEARANCES, COMBUSTIBLES OF |
| | EASILY IGNITABLE |
| | MATERIALS. |
| | |
| | 9) NOTE: PLEASE SUBMIT ACTUAL |
| | SPEC/MANUFACTURES CUT SHEETSFOR THE |
| | MAIN SW BD AND PROPOSED"KIRK KEY |
| | INTERLOCK". PLEASE KNOW, THIS OFFICE HAS |
| | SEEN SOME SYSTEMS WHICH DO NOT MEET THE |
| | CODE WITH RESPECT TO TRANSFER EQUIPMENT |
| | AND LISTED FOR THE INTENDED USE. |
| | 702.6, 110.3 |
| | |
| | 10) NOTE: PLEASE CLARIFY OF ALL |
| | CONTINUOUS LOADS AND LARGEST MOTOR LOADS |
| | ARE ALREADY SHOWN AT 125%. |
| | 215.3,230.42 ETC |
| | PLEASE PROVIDE DETAIL ON LOAD |
| | CALCULATIONS. |
| | 220. |
| | |
| | 11) NOTE: PLEASE CLARIFY RECEPTS IN |
| | BATH(S) AS GFI PROTECTED OR NOT. |
| | PLEASE SEE PANEL SCHEDULE DOES NOT SEEM |
| | TO INDICATE THE REQUIRED GFI PROTECTION. |
| | 210.8B1 |
| | |
| | ** PLEASE BE SURE TO SEE ANY POSISBLE |
| | COMMENTS FROM OTHER TRADES WHICH MAY |
| | AFFECT ELECTRICAL PLANS/DESIGN. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| 2006-08-02 00:00:00 | PLANS WILL BE GOING INTO A "F" STATUS, |
| | NOTES TO FOLLOW. |
| 2006-07-30 00:00:00 | IN ELECTRIC FOR REVIEW, |