| Plan Review Notes For Permit 06070674 |
| Permit Number |
06070674 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-09-21 00:00:00 | | | | | | | DENIED | | | | | | 1) TRUSS PACKAGE IS INCOMPLETE, MISSING | | | THE INDIVIDUAL TRUSS SHEETS WITH THE | | | SIGNED AND SEALED INDEX SHEET. PLEASE BE | | | AWARE THIS CAN BE SUBMITTED TO ON SITE | | | INSPECTOR PRIOR TO TRUSS INSTALLATION | | | | | | 2) THE PRESSURES FOR COMPONENT AND | | | CLADDING ARE FOR EXPOSURE B AND THE WIND | | | DESIGN CRITERIA STATES EXPOSURE C PLEASE | | | CORRECT ONE OF THESE ITEMS | | | | | | 3) FLORIDA COVER SHEET FOR THE PROJECTED | | | WINDOWS FL#2766-R4 DOES NOT COVER | | | ATW-400 AWNING WINDOWS AND THEY ARE NOT | | | IMPACT AS STATED ON THE DRAWING PLEASE | | | SUBMITTHE CORRET PRODUCT OR IF THIS | | | AWNING IS TO BE USED SHUTTER PRODUCT | | | APPROVALS WILL BE REQUIRED | | | | | | 4) PER R311.5.4 THERE SHALL BE A LANDING | | | AT THE TOP AND BOTTOM OF EACH STAIRWAY. | | | THE WIDTH SHALL NOT BE LESS THAN THE | | | STAIRWAY BEING SERVED AND SHALL HAVE A | | | MINIMUM DIMENSION OF 36" MEASURED IN THE | | | DIRECTION OF TRAVEL | | | | | | BLDG PLAN REVIEW | | | ADRIAN MORSE | | | 561-805-6716 | | | | | | | | | | | | |
|