Plan Review Notes
Plan Review Notes For Permit 06070674
Permit Number 06070674
Review Stop B
Sequence Number 2
Notes
Date Text
2006-09-21 00:00:00 
  
 DENIED
  
 1) TRUSS PACKAGE IS INCOMPLETE, MISSING
 THE INDIVIDUAL TRUSS SHEETS WITH THE
 SIGNED AND SEALED INDEX SHEET. PLEASE BE
 AWARE THIS CAN BE SUBMITTED TO ON SITE
 INSPECTOR PRIOR TO TRUSS INSTALLATION
  
 2) THE PRESSURES FOR COMPONENT AND
 CLADDING ARE FOR EXPOSURE B AND THE WIND
 DESIGN CRITERIA STATES EXPOSURE C PLEASE
 CORRECT ONE OF THESE ITEMS
  
 3) FLORIDA COVER SHEET FOR THE PROJECTED
 WINDOWS FL#2766-R4 DOES NOT COVER
 ATW-400 AWNING WINDOWS AND THEY ARE NOT
 IMPACT AS STATED ON THE DRAWING PLEASE
 SUBMITTHE CORRET PRODUCT OR IF THIS
 AWNING IS TO BE USED SHUTTER PRODUCT
 APPROVALS WILL BE REQUIRED
  
 4) PER R311.5.4 THERE SHALL BE A LANDING
 AT THE TOP AND BOTTOM OF EACH STAIRWAY.
 THE WIDTH SHALL NOT BE LESS THAN THE
 STAIRWAY BEING SERVED AND SHALL HAVE A
 MINIMUM DIMENSION OF 36" MEASURED IN THE
 DIRECTION OF TRAVEL
  
 BLDG PLAN REVIEW