Date Text
2006-08-02 00:00:00*** DENIED ***
 1) SEE ENERGY CALCULATIONS #6 SHOWS
 CONDITIONED FLOOR AREA AS 2176.8 SQ.
 FT., NEED TO SHOW ADDITION SQ. FT. ONLY,
 NOT WHOLE HOUSE. #11 SHOWS DUCT LOCATION
 IN CONDITIONED AREA, DUCT WORK IS IN THE
 ATTIC AND IN A NON-CONDITIONED SPACE,
 AND DUCT R VALUE IS 4.2, DUCTS IN THE
 ATTIC NEED TO BE R-6. PLEASE CORRECT THE
 ABOVE.
  
 2) ENERGY CALCULATIONS NEED TO BE SIGNED
 BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2
  
 3) SHOW SEER OF A/C SYSTEM ON MECHANICAL
 PLANS EQUIPMENT SCHEDULE.
  
 4) MECHANICAL PLANS SHOW FS (FIRE STAT)
 AT AIR HANDLER, PLEASE EXPLAIN WHAT FIRE
 STAT IS.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  