| Plan Review Notes For Permit 06070674 |
| Permit Number |
06070674 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-02 00:00:00 | *** DENIED *** | | | 1) SEE ENERGY CALCULATIONS #6 SHOWS | | | CONDITIONED FLOOR AREA AS 2176.8 SQ. | | | FT., NEED TO SHOW ADDITION SQ. FT. ONLY, | | | NOT WHOLE HOUSE. #11 SHOWS DUCT LOCATION | | | IN CONDITIONED AREA, DUCT WORK IS IN THE | | | ATTIC AND IN A NON-CONDITIONED SPACE, | | | AND DUCT R VALUE IS 4.2, DUCTS IN THE | | | ATTIC NEED TO BE R-6. PLEASE CORRECT THE | | | ABOVE. | | | | | | 2) ENERGY CALCULATIONS NEED TO BE SIGNED | | | BY OWNER/AGENT ALSO, PER 2004 FBC | | | 13-600.3.ABC.2 | | | | | | 3) SHOW SEER OF A/C SYSTEM ON MECHANICAL | | | PLANS EQUIPMENT SCHEDULE. | | | | | | 4) MECHANICAL PLANS SHOW FS (FIRE STAT) | | | AT AIR HANDLER, PLEASE EXPLAIN WHAT FIRE | | | STAT IS. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. | | | |
|