2006-07-18 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE SEE PLANS SHALL CONTAIN
 A CLEAR AND VISABLE SEAL WITH ALL
 INFORMATION AS REQUIRED ON SAID SEAL.
 PLEASE SEE FAC 61G15-23.001,.002 AND FS
 471.025
 ** PLEASE KNOW, THIS IS REQUIRED FOR ALL
 SHEETS AND FOR ALL TRADES WHETHER OR NOT
 COMMENT IS MADE BY OTHER REVIEWER(S).
  
 2) NOTE: PLEASE SEE PLAN NOTES MENTIONS
 THE COMPLETE REMOVAL OF PANEL "J",
 WIRING , CONDUIT ETC AND TERMINATE
 FEEDERS INTO A J-BOX IN CEILING AREA
 WITH TAPS, LABELING ETC, HOWEVER PLEASE
 SEE NEW RECEPTS SHOWN INDICATE THE
 CIRCUITING TO THIS PANEL WHICH IS BEING
 REMOVED??
 HOW IS THIS POSSIBLE OR IS THERE ANOTHER
 PANEL "J"??
 PLEASE CORRELATE AND REVISE AS NEEDED.
  
 3) NOTE: PLEASE SEE THAT THE FOLLOWING
 CODES AT A MIN SHALL BE INDICATED ON
 PLANS.
 2004 FBC, NFPA-70 2002
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  