| Plan Review Notes For Permit 06070608 |
| Permit Number |
06070608 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-07-13 00:00:00 | BUILDING REVIEW CHECKLIST: | | | 1- FLAT ROOF SYSTEM: A) DADE COUNTY NOA | | | 03-0430.13 PACKAGE SUBMITTED SHOWS | | | SELECTED APPROVED ASSEMBLY ON PAGE 27 | | | FOR CONCRETE DECK, NON INSULATED | | | ASSEMBLY. BUT, THERE IS ADDITIONAL | | | INFORMATION SUBMITTED FOR INSULATION. | | | NEED TO BE SPECIFIC ON WHICH ASSEMBLY IS | | | GOING TO BE INSTALLED. INSULATED OR | | | NON-INSULATED IN ORDER TO CHECK | | | COMPLIANCE WITH GENERAL LIMITATION #7 OR | | | #9 ON LAST PAGE OF NOA. SEE ATTACHED | | | COPY OF CITY POLICY FOR RE-ROOFS PERMITS | | | FOR REQUIRED INFORMATION TO BE | | | SUBMITTED. | | | B) PROVIDE COPY OF COVER PAGE OF | | | FLORIDA PRODUCT APPROVAL FL-617 WHICH IS | | | THE ONE THAT MATCHES THIS NOA. | | | C) IF SELECTING AN INSULATED ASSEMBLY, | | | THEN CLEARLY MARK WHICH INSULATION | | | ASSEMBLY IS GOING TO BE INSTALLED. | | | | | | 2- DADE COUNTY NOA 01-1226.03 FOR ELK | | | PRESTIQUE SHINGLES IS EXPIRED. PROVIDE | | | CURRENT NOA. | | | | | | JULIO GOMEZ | | | BUILDING PLANS EXAMINER | | | (561)805-6712 |
|