| Plan Review Notes For Permit 06070594 |
| Permit Number |
06070594 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-01-19 09:30:07 | *** DENIED *** | | | 1) COULD NOT FIND THE A/C SYSTEM LISTED ON PLANS IN THE | | | ARI DIRECTORY, PLEASE CORRECT MODEL NUMBERS OR SUBMIT | | | MANUFACTURER'S SPECIFICATION'S FOR A/C SYSTEM. | | | | | | 2) ENERGY CALCULATIONS ARE SHOWING A HEAT RECOVERY UNIT | | | FOR A CONSERVATION CREDIT, PLEASE SHOW THE HEAT | | | RECOVERY UNIT ON THE MECHANICAL PLANS ANDPLEASE | | | SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S FOR HEAT | | | RECOVERY UNIT. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729. |
|