Plan Review Notes
Plan Review Notes For Permit 06070594
Permit Number 06070594
Review Stop M
Sequence Number 2
Notes
Date Text
2007-01-19 09:30:07*** DENIED ***
 1) COULD NOT FIND THE A/C SYSTEM LISTED ON PLANS IN THE
 ARI DIRECTORY, PLEASE CORRECT MODEL NUMBERS OR SUBMIT
 MANUFACTURER'S SPECIFICATION'S FOR A/C SYSTEM.
  
 2) ENERGY CALCULATIONS ARE SHOWING A HEAT RECOVERY UNIT
 FOR A CONSERVATION CREDIT, PLEASE SHOW THE HEAT
 RECOVERY UNIT ON THE MECHANICAL PLANS ANDPLEASE
 SUBMIT DETAILED MANUFACTURER'S SPECIFICATION'S FOR HEAT
 RECOVERY UNIT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.