Plan Review Notes
Plan Review Notes For Permit 06070594
Permit Number 06070594
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-18 16:18:09** UNSAT2ND REVIEW **
  
 ** THIS IS THE FIRST SET OF ELECTRICAL PLANS BEING
 SUBMITTED FOR REVIEW. THE FIRST SET OF PLANS SUBMITTED
 DID NOT CONTAIN ELECTRICAL PLANS NEEDED.
  
 1) NOTE: PLEASE SEE MEP SHEETS WHICH CONTAIN A TITLE
 BLOCK FOR AN ENGINEERING FIRM WHICH DOES NOT CONTAIN A
 CERTIFICATE OF AUTHORIZATION NUMBER AS REQUIRED UNDER
 THE FLORIDA ADMINISTRATIVE CODE 61G15-23.002, AND
 FLORIDA STATUES 471.023.
 PLEASE SEE THE USE OF PROTECTED WORDS IS PROHIBITED
 UNLESS OBTAINING THE PROPER LICENSING THROUGH THE
 STATE.
 THIS COMMENT HAS BEEN MADE ON SEVERAL OTHER PROJECTS TO
 THIS COMPANY AND PLANS ARE BEING RETAINED BY THIS
 OFFICE.
 ANY FURTHER QUESTIONS ON THIS MATTER SHALL BE MADE TO
 THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 2) NOTE: PLEASE SEE THE "S" SHEETS WHICH CONTAIN A
 "RUBBER-STAMP" BY THE ENGINEER FOR THE REQUIRED
 ORIGINAL SIGNATURE. PLEASE SEE FLORIDA STATUES 471.025
 AND FLORIDA ADMINISTRATIVE CODE 61G15-23.002.
 ONE SET OF THESE PLANS ARE ALSO BEING RETAINED BY THIS
 OFFICE.
 ANY FURTHER QUESTIONS ON THIS SHALL BE MADE TO THE
 FLORIDA BOARD OF PROFESSIONAL ENGINEERS.
  
 3) NOTE: PLEASE SEE THE ELECTRICAL RISER DIAGRAM FOR
 SERVICE IS INCOMPLETE AT THIS TIME.
 PLEASE SEE THE RISER SHOWS AN ADDITIONAL EXISTING MAIN
 BREAKER PANEL WHICH A PANEL SCHEDULE WAS NOT SUBMITTED
 FOR? PLEASE SEE NO OVER CURRENT PROTECTION IS BEING
 SHOWN FOR THIS NEW FEEDER TO THE PANEL "B" WHICH IS
 SHOWN ON RISER.
 PLEASE COMPLETE.
 310.16, 240.4, 240.24
 FBC 106.1.2, 106.3.5.4 ADMIN SECTION.
  
 4) NOTE: PLEASE SEE MISSING THE REQUIRED FOOTER STEEL
 AT THE NEW DETACHED BUILDING AS REQUIRED PER 250.32,
 250.50
  
 5) NOTE: PLEASE SEE MISSING RECEPTACLES PER 210.52 2FT,
 6FT AND 12FT RULE.
  
 6) NOTE: PLEASE SEE MISSING THE REQUIRED LOADS FOR
 CIRCUITS FOR KITCHENS AND AREAS OF THE LIKE AS REQUIRED
 PER 210.52B1, 210.11C1, 220.52
  
 7) NOTE: PLEASE SUBMIT LOAD CALCULATIONS PER 220.83(A)
 AND (B).
 PLEASE INDICATE A LOAD SUMMARY WHICH CORRELATES WITH
 THE PLANS AND PANEL SCHEDULE(S). PLEASE SEE SMALL
 APPLIANCE CIRCUITS, WASHER/LAUNDRY ETC SHALL BE SHOWN
 AND COORDINATED WITH THE PANEL LOADS AS SHOWN.
  
 8) NOTE: PLEASE VERIFY AND CORRELATE THE NEW AHU HEAT
 LOAD AND OVER CURRENT PROTECTION WITH THE MECHANICAL
 PLANS. PLEASE SEE THE LOADS SHOWN FOR THE A/C LOADS ON
 LOAD CALCULATIONS DO NOT CORRELATE WITH THAT OF THE
 LOADS SHOWN ON THE PANEL SCHEDULE?
 PLEASE SEE 220.83(B) AND 220.60
  
 9) NOTE: PLEASE SEE 110.26 FOR MINIMUM CLEARANCES
 REQUIRED FOR ELECTRICAL PANELS. AS THE PLANS INDICATE A
 1/4INCH SCALE, THE ROOM WHERE THE PANEL IS LOCATED IS
 NOT LARGE ENOUGH.
  
 10) NOTE: PLEASE CORRELATE RISER, PANEL AND PLANS.
 PLEASE SEE THE NEW PANEL B IS BEING SHOWN WITH OUT ANY
 MAIN BREAKER OR DISCONNECTING MEANS AS REQUIRED PER
 225.31. PLEASE SEE PLANS HOWEVER SEEM TO SHOW SOME SORT
 OF DISCONNECT HOWEVER RISER DOES NOT SHOW ANY
 DISCONNECT.
 PLEASE CORRELATE THESE.
  
 11) NOTE: PLEASE SEE 210.8A6 AND 7 AS MISSING GFI
 DESIGNATION ON PLANS FOR AREAS AS STATED IN THESE
 SECTIONS.
  
 12) NOTE: PLEASE SEE PLANS SHALL STATE THE CODE IN
 WHICH THE DESIGN IS UNDER. PLEASE SEE THE PLANS SHALL
 STATE FOLLOWING AT A MINIMUM.
 2002 NFPA-70 (NEC).
 2002 NFPA-72
  
 13) NOTE: PLEASE 2002 NEC 210.12AS AFCI PROTECTION IS
 REQUIRED FOR ALL OUTLETS IN SLEEPING ROOMS.
 (ALL).
 PLEASE SEE MISSING PROTECTION FOR SOME AS NOTED ON
 PANEL SCHEDULE.
  
 14) NOTE: PLEASE SEE ZONING REVIEW COMMENTS AS THEY
 WILL AFFECT THE ELECTRICAL PLANS AND PERHAPS OTHER
 TRADES FOR ANY LAYOUT CHANGES ETC.
  
 15) NOTE: PLEASE SEE PLANS INDICATE A 220V RECEPTACLE
 FOR THE WATER HEATER CONNECTION HOWEVER AS REQUIRED PER
 422.30, 422.31 THIS IS REQUIRED TO BE HARDWIRED. MAY
 NOT BE CORD AND PLUG CONNECTED.
  
 16) NOTE: PLEASE KNOW THAT A MEETING WAS HELD AT THE
 SOUTHERN SECTION MEETING IN OCT 06 WHERE WE WERE
 DIRECTLY INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE
 DETECTORS ON PLANS FOR RESIDENTIAL HOMES IS NOT
 ACCEPTABLE WHEN THESE DEVICES ANY ACTUALLY FALL UNDER
 THE DEFINITIONS OF SMOKE ALARMS WHICH WOULD BE SHOWN AS
 SA/SMOKE ALARMS.
 THIS INFORMATION WAS NEW TO THIS AHJ AS THE GENERAL USE
 OF THE SD FOR SMOKE DETECTORS WAS ALWAYS ACCEPTED.
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 ** PLEASEKNOW THAT BASED ON THE PLANS SUBMITTED AND
 SOME INFORMATION WHICH WAS NOT SUBMITTED WHICH IS
 NEEDED FOR PLAN REVIEW, THERE MAY BE NEW COMMENTS ON
 THE NEXT REVIEW WHICH MAY NOT HAVE BEEN MADE ON THIS
 REVIEW.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]