| 2006-07-20 00:00:00 | ********* UNSAT *********** |
| | |
| | ** PLEASE KNOW, PLANS SHALL BE SPECIFIC |
| | TO EACH SITE AND DESIGN. |
| | |
| | 1) NOTE: PLEASE SUBMIT COMPLETE LOAD |
| | CALCULATIONS FOR ALL EXISTING LOADS AND |
| | NEW LOADS ADDED. |
| | PLEASE INDICATE THE SIZE OF THE EXISTING |
| | SERVICE. |
| | 220.31B,215.5, FBC ADMIN SECT 106.1.2 |
| | |
| | 2) NOTE: PLEASE SEE PLANS INDICATE A NEW |
| | PANEL, HOWEVER NO INFORMATIONTHE |
| | BRANCH CIRCUITS, OCP FOR EACH. THIS CAN |
| | BE DONE BY THE ELECTRICAL CONTRACTOR. |
| | PLEASE SEE THAT ANY ADDITIONAL |
| | INFORMATION SUBMITTED FOR PANEL |
| | SCHEDULES OR LOADS SHALL BEAR THE |
| | PRINTED NAME AND SIGNATURE OF THE PERSON |
| | RESPONSIBLE FOR PLANS/DESIGN. |
| | 240.4,310.16,215.5 ETC |
| | FBC 106.1.2 ADMIN SECT |
| | |
| | 3) NOTE: PLEASE SEE MANY CONDUCTOR SIZES |
| | ARE BEING SHOWN AS #8'S TO PUMPS, BLOWER |
| | ETC. PLEASE KNOW THIS SEEMS TO BE A |
| | MISPRINT AS #8'S WILL NOT FIT INTO THESE |
| | PUMPS ETC. |
| | TABLES(9)AND 430 FOR SIZING OF |
| | CONDUCTORS CONDUITS. |
| | |
| | 4) NOTE: PLEASE SEE MISSING 'EQUIPMENT |
| | GROUNDING CONDUCTOR' FROM SERVICE TO THE |
| | NEW POOL PANEL. |
| | 250.110, 250.122 ETC. |
| | |
| | 5) NOTE: PLEASE SEE BLDG REVIEW COMMENTS |
| | AS VALUE FOR THE COMPLETE SCOPE PF WORK |
| | SEEMS LOW. PLEASE KNOW, A VALUE FOR |
| | COMPLETE SCOPE FOR POOL/ SPA/HEATER, |
| | TILE, NEW DECK ETC SHALL BE FIGURED. |
| | FBC 108.3 |
| | |
| | 6) NOTE: PLEASE CLARIFY WIRING RISER AS |
| | ONLY ONE DISC SEEMS TO BE SHOWN FOR ALL |
| | THREE PUMPS?? |
| | PLEASE CLARIFY. 430.101 ETC. |
| | |
| | 7) NOTE: PLEASE KNOW A NEW RECORDED NOC |
| | WILL BE REQUIRED UPON PICKING UP OF |
| | PERMIT. PLEASE SEE FS 713.13(2) AS THE |
| | NOC HAS EXPIRED. |
| | WORK WHICH HAS NOT COMMENCED WITHIN 90 |
| | DAYS OF RECORDING NOC, THAT NOC BECOMES |
| | VOID. |
| | |
| | |
| | ** WHEN REQ'D** |
| | PLEASE SEE FAC 61G17 AND FS 421.025, |
| | PLEASE SEE THAT THE SURVEY SHALL CONTAIN |
| | THE RAISED SEAL AND THE ORIGINAL |
| | SIGNATURE AND DATE. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |