Plan Review Notes
Plan Review Notes For Permit 06070568
Permit Number 06070568
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-24 00:00:00BUILDING REVIEW 3RD CHECKLIST:
  
 1- HARDISOFFIT PRODUCT APPROVAL REQUIRES
 INSTALLATION TO BE OVER MINIMUM 2"X4"
 WOOD JOISTS (OR TRUSSES) SPACED AT A
 MAXIMUM OF 16"O.C.SEE SHEET 3 OF 3
 PRODUCT APPROVAL SUBMITTED. ENGINEERED
 DRAWINGS SHOW TRUSSES SPACED AT 24"O.C.
 NEED TO PROVIDE MINIMUM SPACING AS
 REQUIRED ON PRODUCT APPROVAL. REVISE
 ENGINEERED DRAWINGS AS REQUIRED.
 ***NOTE: THIS IS THE FIRST TIME THIS
 PRODUCT APPROVAL WAS SUBMITTED FOR
 REVIEW. THAT'S WHY THIS COMMENT WAS NOT
 RAISED BEFORE.
  
 2- FLORIDA PRODUCT APPROVAL #1423:
 A) NEED TO PROVIDE 2004 CODE VERSION.
 ONE SUBMITTED IS FOR 2001.
  
 B) NEED TO PROVIDE DRAWING SHOWING THE
 SPECS OF SPECIFIED CONNECTOR. NO
 INFORMATION WAS SUBMITTED.
  
 3- FLORIDA PRODUCT APPROVAL #474 IS
 MISSING THE DRAWINGS SHOWING THE SPECS
 OF SPECIFIED CONNECTORS. NO INFORMATION
 WAS SUBMITTED.
  
 4- THERE IS A PRODUCT APPROVAL SUBMITTED
 FOR WOOD CONNECTORS U, LU, LUP, HU & WM.
 WHERE ARE THESE CONNECTORS SPECIFIED ON
 ENGINEERED DRAWINGS?.
  
 5- AS REQUESTED ON PREVIOUS CHECKLISTS,
 ENGINEER OF RECORD NEED TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS AS REQUIRED BY SECTION 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 6- PLEASE DON'T STAPLE PRODUCT APPROVALS
 TO ENGINEERING DRAWINGS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712