Plan Review Notes
Plan Review Notes For Permit 06070564
Permit Number 06070564
Review Stop B
Sequence Number 3
Notes
Date Text
2006-08-24 00:00:00BUILDING REVIEW 3RD CHECKLIST:
  
 1- PERMIT APPLICATION #06070564 IS FOR
 1901 PRESIDENTIAL WAY, WHILE THIS SAME
 PERMIT # SHOWS IN THE COMPUTER SYSTEM
 1731 PRESIDENTIAL WAY AS THE ADDRESS TO
 UNDERGO REPAIRS. NEED TO CLARIFY WHICH
 BUILDING IS THE ONE GOING TO BE
 REPAIRED. PLEASE, CORRECT INFORMATION
 WITH PERMIT CLERK AT TIME OF
 RE-SUBMITTAL. ALL INFORMATION NEED TO
 MATCH TO AVOID CONFLICTS.
  
 2- HARDISOFFIT PRODUCT APPROVAL REQUIRES
 INSTALLATION TO BE OVER MINIMUM 2"X4"
 WOOD JOISTS (OR TRUSSES) SPACED AT A
 MAXIMUM OF 16"O.C.SEE SHEET 3 OF 3
 PRODUCT APPROVAL SUBMITTED. ENGINEERED
 DRAWINGS SHOW TRUSSES SPACED AT 24"O.C.
 NEED TO PROVIDE MINIMUM SPACING AS
 REQUIRED ON PRODUCT APPROVAL. REVISE
 ENGINEERED DRAWINGS AS REQUIRED.
 ***NOTE: THIS IS THE FIRST TIME THIS
 PRODUCT APPROVAL WAS SUBMITTED FOR
 REVIEW. THAT'S WHY THIS COMMENT WAS NOT
 RAISED BEFORE.
  
 3- FLORIDA PRODUCT APPROVAL #1423:
 A) NEED TO PROVIDE 2004 CODE VERSION.
 ONE SUBMITTED IS FOR 2001.
  
 B) NEED TO PROVIDE DRAWING SHOWING THE
 SPECS OF SPECIFIED CONNECTOR. NO
 INFORMATION WAS SUBMITTED.
  
 4- FLORIDA PRODUCT APPROVAL #474 IS
 MISSING THE DRAWINGS SHOWING THE SPECS
 OF SPECIFIED CONNECTORS. NO INFORMATION
 WAS SUBMITTED.
  
 5- THERE IS A PRODUCT APPROVAL SUBMITTED
 FOR WOOD CONNECTORS U, LU, LUP, HU & WM.
 WHERE ARE THESE CONNECTORS SPECIFIED ON
 ENGINEERED DRAWINGS?.
  
 6- AS REQUESTED ON PREVIOUS CHECKLISTS,
 ENGINEER OF RECORD NEED TO REVIEW AND
 APPROVE IN WRITTING ALL PRODUCT
 APPROVALS AS REQUIRED BY SECTION 106.3.3
 CITY AMENDMENTS TO FBC 2004.
  
 7- PLEASE DON'T STAPLE PRODUCT APPROVALS
 TO ENGINEERING DRAWINGS.
  
  
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561) 805-6712