2006-07-21 00:00:00******DENIED******
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. PER FBC-2004, CHAPTER 1, SECTION
 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND
 REGULATIONS, AS DETERMINED BY THE
 BUILDING OFFICIAL. (NOTE: THE SANITARY
 ISOMETRIC RISER DIAGRAM INDICATED ON
 SHEET A3 DOES NOT REFLECT THE FLOOR
 PLAN)
 2. PER FBC-2004, CHAPTER 1, SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO
 FAMILY) SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL
 WASTE, VENTS, TRAPS WITH SIZES, AND
 CLEANOUT LOCATIONS.(NOTE: NOT ALL PIPES
 ARE SIZED ON THE PLUMBING RISER)
 3. PER FBC-2004 PLUMBING, SECTION 420.
 WATER CLOSETS HAVE INTREGRAL TRAPS,
 THEREFORE THE TRAPS INDICATED ON THE
 PLMG. RISER DIAGRAM ON SHEET A3 SHALL BE
 ELIMINATED ON THE RESUBMITTAL.
 4. PER FBC-2004, SECTION 708, PLEASE
 INDICATE THE FOLLOWING ON SHEET A3,
 PLMG. RISER DIAGRAM FOR THE RESUBMITTAL.
 (A) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 (B) ELIMINATE "OPTION W/C AND SHOWER
 DRAIN BE USED AS CLEANOUTS" ON SHEET A3
 PLMG. RISER DIAGRAM.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  