Plan Review Notes
Plan Review Notes For Permit 06070544
Permit Number 06070544
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-20 00:00:00********** UNSAT ***********
  
 1) NOTE: PLEASE KNOW PLANS ARE REQUIRED
 TO CONTAIN THE CURRENT CODE RELEVANT AND
 IN EFFECT FOR THE JOB. PLEASE SEE THAT
 PLANS REFLECT THE FOLLOWING AT A MIN
 2004 FBC, 2002 NFPA-70, NFPA-72 2002
 PLEASE SEE OTHER CODES FOR OTHER TRADES
 WHICH MAY BE NEEDED.
 106.1.2
 ** PLEASE ALSO SEE PLANS MENTIONS WORK
 PER "PALM BEACH COUNTY", HOWEVER PLEASE
 SEE THAT THE SCOPE OF WORK IS IN THE
 CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE MANY RECEPTS MISSING
 PER 210.52
 PLEASE SEE MANY OF THESE AREAS AARE
 REDLINED ON PLANS SUBMITTED.
 PLEASE SHOW ALL EXISTING RECEPTS WHICH
 MEET CODE AND SHOW AS "E" NEXT TO THE
 RECEPTS. PLEASE KNOW, DUE TO THE AMOUNT
 OF RENOVATION AND ADDITION, RECEPTS MAY
 NEED TO BE BROUGHT UP TO CODE.
  
 3) NOTE: PLEASE SEE NOTE MENTIONS ARC
 FAULT FOR EXISTING BEDRMS WILL BE
 BROUGHT UP TO CODE WITH ARROWS, HOWEVER
 PLEASE SEE THESE ARROWS AND THIS NOTE IS
 IN THE GARAGE??
 PLEASE SEE OTHER COMMENTS AS ALL ARC
 FAULT CIRCUITS WILL BE REQUIRED ON A
 PANEL SCHEDULE.
 210.12B
  
 4) NOTE: PLEASE SEE THAT ALL SLEEPINGS
 RMS AND ADAPTABLE SLEEPING RMS SHALL
 CONTAIN SD'S INSIDE AND OUTSIDE. PLEASE
 PROVIDE A LAYOUT FOR ALL NEW OR EXISTING
 MEETING CURRENT CODES. PLEASE ALSO KNOW
 , ALL SHALL BE WIRED INLINE ETC AS
 REQUIRED PER NFPA-72 11.5.1.1, 11.8.3
 R313
  
 5) NOTE: PLEASE SUBMIT AND PROVIDE A
 COMPLETE PANEL SCHEDULE SHOWING ALL
 CIRCUITS AND MIN REQUIRED DEDICATED
 CIRCUITS. PLEASE INDICATE ALL OCP AND
 MIN CONDUCTORS SIZES.
 408.4, 240.4,310.16 ETC.
  
 6) NOTE: PLEASE SEE MISSING DEDICATED
 BATH(S) CIRCUIT(S) PER 210.52D,
 210.11C3, MUST BE 20A AND #12.
  
 7) NOTE: PLEASE SEE RISER SEEMS TO
 INDICATE AN "O" ABOVE MAIN, IS THIS
 ACTUALLY THE METER? IS THIS A METER/MAIN
 COMBO?
 PLEASE BE SURE TO SHOW LOCATION OF ALL
 SERVICE EQUIPMENT ON PLANS.
 PLEASE SEE 240.24, 230.70, 110.26 ETC
 FOR LOCATIONS NOT PERMITTED AND
 LOCATIONS REQUIRED.
  
 8) NOTE: PLEASE THE LOAD CALCS INDICATE
 ONLY ONE GDO CIRCUIT, HOWEVER TWO DOORS
 ARE SHOWN. PLEASE VERIFY AND INDICATE OF
 EXISTING.
 106.1.2
  
 9) NOTE: PLEASE SEE PLANS DO NOT
 INDICATE THE EXISTING OR NEW A/C SYSTEM.
 PLEASE SHOW THE LOCATION OF THE AHU AND
 CU'S ALONG W/ DISCONNECTS AS REQUIRED
 PER 440.11.
 PLEASE ALSO SEE 210.70 IF IN ATTIC AND
 PLEASE SEE 210.63 FOR GFI REQUIRED
 OUTSIDE.
  
 10) NOTE: PLEASE SEE MISSING GFI ALONG
 WALL SPACE ON KITCHEN COUNTER SPACE.
 210.52C1
  
 11) NOTE: PLEASE SEE MIN VA REQUIRED FOR
 WASHER AND LAUNDRY PER 220.169, 210.11C2
  
 12) NOTE: PLEASE SEE MISSING INFORMATION
 ON TITLE BLOCKS FOR THE ARCHOTECTURAL
 FIRM AS REQUIRED UNDER THE FAC
 61G1-16.004 AND FS 481.219
 MISSING CERTIFICATE OF AUTHORIZATION #.
  
 13) NOTE: PLEASE SEE THAT TWO SETS OF
 ALL PLANS ARE SUBMITTED FOR REVIEW AND
 STAMPING. ONE SET REMAINS ONFILE AND
 ONE SET GOES BACK TO JOBSITE FOR
 INSPECTIONS.
  
 14) NOTE: PLEASE SEE 210.52B1 FOR MIN
 CIRCUIT(S) FOR DINING, BREAKFAST AREAS
 ETC OF THE LIKE. PLEASE SEE THESE SHALL
 BE 20A AND #12 ALONG WITH MIN VA PER
 210.11C1,220.16
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  