| Date |
Text |
| 2006-07-20 00:00:00 | ********** UNSAT *********** |
| | |
| | 1) NOTE: PLEASE KNOW PLANS ARE REQUIRED |
| | TO CONTAIN THE CURRENT CODE RELEVANT AND |
| | IN EFFECT FOR THE JOB. PLEASE SEE THAT |
| | PLANS REFLECT THE FOLLOWING AT A MIN |
| | 2004 FBC, 2002 NFPA-70, NFPA-72 2002 |
| | PLEASE SEE OTHER CODES FOR OTHER TRADES |
| | WHICH MAY BE NEEDED. |
| | 106.1.2 |
| | ** PLEASE ALSO SEE PLANS MENTIONS WORK |
| | PER "PALM BEACH COUNTY", HOWEVER PLEASE |
| | SEE THAT THE SCOPE OF WORK IS IN THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE: PLEASE SEE MANY RECEPTS MISSING |
| | PER 210.52 |
| | PLEASE SEE MANY OF THESE AREAS AARE |
| | REDLINED ON PLANS SUBMITTED. |
| | PLEASE SHOW ALL EXISTING RECEPTS WHICH |
| | MEET CODE AND SHOW AS "E" NEXT TO THE |
| | RECEPTS. PLEASE KNOW, DUE TO THE AMOUNT |
| | OF RENOVATION AND ADDITION, RECEPTS MAY |
| | NEED TO BE BROUGHT UP TO CODE. |
| | |
| | 3) NOTE: PLEASE SEE NOTE MENTIONS ARC |
| | FAULT FOR EXISTING BEDRMS WILL BE |
| | BROUGHT UP TO CODE WITH ARROWS, HOWEVER |
| | PLEASE SEE THESE ARROWS AND THIS NOTE IS |
| | IN THE GARAGE?? |
| | PLEASE SEE OTHER COMMENTS AS ALL ARC |
| | FAULT CIRCUITS WILL BE REQUIRED ON A |
| | PANEL SCHEDULE. |
| | 210.12B |
| | |
| | 4) NOTE: PLEASE SEE THAT ALL SLEEPINGS |
| | RMS AND ADAPTABLE SLEEPING RMS SHALL |
| | CONTAIN SD'S INSIDE AND OUTSIDE. PLEASE |
| | PROVIDE A LAYOUT FOR ALL NEW OR EXISTING |
| | MEETING CURRENT CODES. PLEASE ALSO KNOW |
| | , ALL SHALL BE WIRED INLINE ETC AS |
| | REQUIRED PER NFPA-72 11.5.1.1, 11.8.3 |
| | R313 |
| | |
| | 5) NOTE: PLEASE SUBMIT AND PROVIDE A |
| | COMPLETE PANEL SCHEDULE SHOWING ALL |
| | CIRCUITS AND MIN REQUIRED DEDICATED |
| | CIRCUITS. PLEASE INDICATE ALL OCP AND |
| | MIN CONDUCTORS SIZES. |
| | 408.4, 240.4,310.16 ETC. |
| | |
| | 6) NOTE: PLEASE SEE MISSING DEDICATED |
| | BATH(S) CIRCUIT(S) PER 210.52D, |
| | 210.11C3, MUST BE 20A AND #12. |
| | |
| | 7) NOTE: PLEASE SEE RISER SEEMS TO |
| | INDICATE AN "O" ABOVE MAIN, IS THIS |
| | ACTUALLY THE METER? IS THIS A METER/MAIN |
| | COMBO? |
| | PLEASE BE SURE TO SHOW LOCATION OF ALL |
| | SERVICE EQUIPMENT ON PLANS. |
| | PLEASE SEE 240.24, 230.70, 110.26 ETC |
| | FOR LOCATIONS NOT PERMITTED AND |
| | LOCATIONS REQUIRED. |
| | |
| | 8) NOTE: PLEASE THE LOAD CALCS INDICATE |
| | ONLY ONE GDO CIRCUIT, HOWEVER TWO DOORS |
| | ARE SHOWN. PLEASE VERIFY AND INDICATE OF |
| | EXISTING. |
| | 106.1.2 |
| | |
| | 9) NOTE: PLEASE SEE PLANS DO NOT |
| | INDICATE THE EXISTING OR NEW A/C SYSTEM. |
| | PLEASE SHOW THE LOCATION OF THE AHU AND |
| | CU'S ALONG W/ DISCONNECTS AS REQUIRED |
| | PER 440.11. |
| | PLEASE ALSO SEE 210.70 IF IN ATTIC AND |
| | PLEASE SEE 210.63 FOR GFI REQUIRED |
| | OUTSIDE. |
| | |
| | 10) NOTE: PLEASE SEE MISSING GFI ALONG |
| | WALL SPACE ON KITCHEN COUNTER SPACE. |
| | 210.52C1 |
| | |
| | 11) NOTE: PLEASE SEE MIN VA REQUIRED FOR |
| | WASHER AND LAUNDRY PER 220.169, 210.11C2 |
| | |
| | 12) NOTE: PLEASE SEE MISSING INFORMATION |
| | ON TITLE BLOCKS FOR THE ARCHOTECTURAL |
| | FIRM AS REQUIRED UNDER THE FAC |
| | 61G1-16.004 AND FS 481.219 |
| | MISSING CERTIFICATE OF AUTHORIZATION #. |
| | |
| | 13) NOTE: PLEASE SEE THAT TWO SETS OF |
| | ALL PLANS ARE SUBMITTED FOR REVIEW AND |
| | STAMPING. ONE SET REMAINS ONFILE AND |
| | ONE SET GOES BACK TO JOBSITE FOR |
| | INSPECTIONS. |
| | |
| | 14) NOTE: PLEASE SEE 210.52B1 FOR MIN |
| | CIRCUIT(S) FOR DINING, BREAKFAST AREAS |
| | ETC OF THE LIKE. PLEASE SEE THESE SHALL |
| | BE 20A AND #12 ALONG WITH MIN VA PER |
| | 210.11C1,220.16 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |