| 2006-08-07 00:00:00 | ***** UNSAT2ND REVIEW ***** |
| | |
| | PLEASE SEE SOME NOTES FROM PREVIOUS |
| | REVIEW STILL NEED TO NE VERIFIED ETC. |
| | |
| | 1) NOTE: NO, PLEASE SEE SPECS UBMITTED |
| | DO NOT SEEM TO CONTAIN THE DISCONNECITNG |
| | MEANS AS REQUIRED. IF THIS UNIT IS ONE |
| | OF THE NEW ONES WHICH CONTAINS A BRKR |
| | FOR NORMAL SIDE AND AND ADDTIONAL BRKR |
| | FOR EM/GEN SIDE, PLEASE BE SURE SPECS |
| | CLEARLY SHOW THIS. |
| | PLEASE KNOW, MANY OF GENERAC'S ONLY |
| | DISCONNECT POWER FROM THE NORMAL SIDE. |
| | THE TOGGLE SWITCH LOCATED IN SOME DO NOT |
| | MEET CODE. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY THE USE OF A SE |
| | RATED ATS. PLEASE SEE THE EXISTING MAIN |
| | FOR HOUSE IS STILL THE SERVICE MAIN. |
| | PLEASE SEE THAT THE ATS AS SPECIFIED |
| | DOES NOT DICONNECT POWER FROM GEN OR |
| | FEEDERS COMING FROM THE GEN AS REQUIRED |
| | PER 225.31-225.39. |
| | |
| | 2) NOTE:NO, PLEASE SEE I COULD NOT |
| | LOCATE THE MIN CLEARENCE REQUIRED FOR |
| | THIS GEN IN THE SPECS. PLEASE KNOW, THIS |
| | OFFICE HAS OBTAINED LTR FROMGENERAC |
| | WHICH REQUIRES A MIN OF 5' FOR THIS TYOE |
| | OF GEN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PROVIDE ALL THE SETBACKS |
| | AND DISTANCES AROUND GENERATOR. |
| | PLEASE SEE THAT THE SPECS PROVIDE |
| | INFORMATION ON MIN CLEARENCES. |
| | 110.3, 90.7 |
| | |
| | 3) NOTE: OK. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |