| 2006-11-08 14:22:44 | | | | REVISION DENIED | | | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | | | 1}REFERENCE SHEET E-1. THE GENERARTOR GROUNDING | | | DETAIL INDICATES THE NEUTRAL AND GROUND NOT BE BONDED | | | AT THE GENERATOR. HAVING ESTABLISHED THIS GENERATOR AS | | | A SEPARATELY DERIVED SYSTEM IT MUST BONDED PER | | | 250.30(A)(1). PLEASE MAKE THE NOTE CHANGE. | | | | | | 2} |
|