Plan Review Notes
Plan Review Notes For Permit 06070505
Permit Number 06070505
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-16 00:00:00******** UNSAT **********
  
 1) NOTE: PLEASE INDICATE LOADS INTENDED
 FOR NEW FEED AND LOADS ON EXISTING
 PANEL.
 220.31., 215.5
  
 2) NOTE: PLEASE SEE 225.31-225.39 FOR
 MEANS OF DISONNECT REQUIRED AT THE
 DETACHED BLDG/SHED.
 PLEASE KNOW, MIN CLEARENECES SHALL BE
 MAINTAINED PER 110.26
  
 3)NOTE: PLEASE PROVIDE GROUNDING
 ELECTRODE SYSTEM AT THE DETACHED BLDG
 PER 250.32
  
 ** PLEASE KNOW, DEPTH MUST BE PER 300.5
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.