| 2007-04-08 08:13:12 | ** UNSAT ** |
| | |
| | 1) NOTE: PLEASE SEE THE SHEETS SUBMITTED HAVE BEEN |
| | REVISED WITH SHEET DESIGNATIONS AND THE INFORMATION |
| | WHICH DOES NOT CORRELATE WITH THE RECORD SET OF PLANS. |
| | PLEASE SEE THAT SEVERAL CHANGES HAVE BEEN MADE WHICH |
| | ARE NOW IN QUESTION. |
| | PLEASE CLARIFY THE REVISED SITE PLAN IN E-1 WHICH USED |
| | TO BE E-2 AND CONTAIN INFORMATION ON THE EXISTING AND |
| | NEW SMOKE ALARMS? |
| | PLEASE REVISE AND INCLUDE THE INFORMATION AS PREVIOUSLY |
| | PERMITTED. PLEASE ALSO SEE THE FOLLOWING COMMENTS WITH |
| | RESPECT TO PANEL LOCATIONS. |
| | |
| | 2) NOTE: PLEASE SEE THE REVISED PLANS NOW SEEM TO PLACE |
| | THE NEW ELECTRICAL SUB PANEL IN A CLOSET OR STORAGE |
| | ROOM WHICH IS NOT PERMITTED. PLEASE SEE 240.24, 110.26, |
| | AND 408.7. |
| | |
| | 3) NOTE: PLEASE SEE THE REVISED SITE PLAN WHICH DOES |
| | NOT INCLUDE THE METER ON PLANS FOR SERVICE LOCATION? |
| | PLEASE SHOW. |
| | 230.70,71. |
| | FBC 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE RISER DIAGRAM HAS NOW BEEN REVISED |
| | TO SHOW A 320AMP BREAKER IN THE 400A RATED ENCLOSURE? |
| | PLEASE SEE 240.6 AS 320 IS NOT A BREAKER SIZE. PLEASE |
| | CLARIFY AND ADJUST PLANS. |
| | PLEASE ALSO SEE THE RISER AND PLANS SEEM TO HAVE |
| | REVISED THE SUB PANEL *B* TO A 125AMP PANEL YET THE |
| | OCP/BREAKER FEEDING THIS PANEL REMAINS 100AMPS? PLEASE |
| | SEE THE LOAD ON THIS PANEL HAS NOW ALSO INCREASED |
| | HOWEVER THE LOADS ON THE PANEL REMAIN THE SAME AS THE |
| | PREVIOUS REVIEWED PLANS? |
| | PLEASE SEE THE REVISED SHEET NOW NO LONGER CONTAINS ANY |
| | LOAD CALCULATIONS FOR THE SERVICE AT ALL? |
| | PLEASE COMPLETE AND SUBMIT COMPLETED REVISED LOAD |
| | CALCULATIONS PER 220.31B. |
| | FBC 106.3.5.1.2,106.1.2. NEC 215.5 |
| | |
| | 5) NOTE: PLEASE SEE LOCATIONS ON PLANS WHICH INDICATE |
| | LIGHTING BEING CONTROLLED FROM MORE THAN ONE LOCATION |
| | YET THE SWITCHES ARE NOT 3-WAY? |
| | |
| | 6) NOTE: PLEASE SE THE SMOKE ALARMS ARE CIRCUITED TO |
| | CIRCUIT 12, YET THE PANEL SCHEDULE SHOWS THIS CIRCUIT |
| | AS SPARE? |
| | PLEASE REVISE PANEL SCHEDULE TO INCLUDE ALL DESIGNATED |
| | LOCATIONS AND AREAS IN WHICH THE CIRCUITS FEED. THE USE |
| | OF GEN LTS AND GEN RECPTS IS NOT LONGER PERMITTED. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM |
| | THE NEC HANDBOOK. 408.4 |
| | CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY |
| | CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE |
| | LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR |
| | WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME |
| | PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR |
| | EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY |
| | OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN |
| | COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL |
| | APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD, |
| | THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL |
| | RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR |
| | ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.'' |
| | CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH |
| | ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE |
| | SUFFICIENT DETAIL REQUIRED BY THIS SECTION.* |
| | 408.4, 240.4, 310.16. |
| | PLEASE PROVIDE THE PANEL DESIGNATION TO THE CIRCUITS |
| | SHOWN. ARE THEY ALL FROM THE NEW SUB PANEL? |
| | |
| | 7) NOTE: PLEASE SEE 110.26 AS THE DISC FOR THE CU IS |
| | SHOWN BEHIND THE UNIT. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2007-04-08 07:59:14 | IN REVIEW |
| 2007-04-07 16:00:59 | 2007-04-07 16:00:59 |
| | NOTES TO FOLLOW ON 4/8 |