Plan Review Notes
Plan Review Notes For Permit 06070501
Permit Number 06070501
Review Stop E
Sequence Number 6
Notes
Date Text
2007-04-08 08:13:12** UNSAT **
  
 1) NOTE: PLEASE SEE THE SHEETS SUBMITTED HAVE BEEN
 REVISED WITH SHEET DESIGNATIONS AND THE INFORMATION
 WHICH DOES NOT CORRELATE WITH THE RECORD SET OF PLANS.
 PLEASE SEE THAT SEVERAL CHANGES HAVE BEEN MADE WHICH
 ARE NOW IN QUESTION.
 PLEASE CLARIFY THE REVISED SITE PLAN IN E-1 WHICH USED
 TO BE E-2 AND CONTAIN INFORMATION ON THE EXISTING AND
 NEW SMOKE ALARMS?
 PLEASE REVISE AND INCLUDE THE INFORMATION AS PREVIOUSLY
 PERMITTED. PLEASE ALSO SEE THE FOLLOWING COMMENTS WITH
 RESPECT TO PANEL LOCATIONS.
  
 2) NOTE: PLEASE SEE THE REVISED PLANS NOW SEEM TO PLACE
 THE NEW ELECTRICAL SUB PANEL IN A CLOSET OR STORAGE
 ROOM WHICH IS NOT PERMITTED. PLEASE SEE 240.24, 110.26,
 AND 408.7.
  
 3) NOTE: PLEASE SEE THE REVISED SITE PLAN WHICH DOES
 NOT INCLUDE THE METER ON PLANS FOR SERVICE LOCATION?
 PLEASE SHOW.
 230.70,71.
 FBC 106.1.2
  
 4) NOTE: PLEASE SEE RISER DIAGRAM HAS NOW BEEN REVISED
 TO SHOW A 320AMP BREAKER IN THE 400A RATED ENCLOSURE?
 PLEASE SEE 240.6 AS 320 IS NOT A BREAKER SIZE. PLEASE
 CLARIFY AND ADJUST PLANS.
 PLEASE ALSO SEE THE RISER AND PLANS SEEM TO HAVE
 REVISED THE SUB PANEL *B* TO A 125AMP PANEL YET THE
 OCP/BREAKER FEEDING THIS PANEL REMAINS 100AMPS? PLEASE
 SEE THE LOAD ON THIS PANEL HAS NOW ALSO INCREASED
 HOWEVER THE LOADS ON THE PANEL REMAIN THE SAME AS THE
 PREVIOUS REVIEWED PLANS?
 PLEASE SEE THE REVISED SHEET NOW NO LONGER CONTAINS ANY
 LOAD CALCULATIONS FOR THE SERVICE AT ALL?
 PLEASE COMPLETE AND SUBMIT COMPLETED REVISED LOAD
 CALCULATIONS PER 220.31B.
 FBC 106.3.5.1.2,106.1.2. NEC 215.5
  
 5) NOTE: PLEASE SEE LOCATIONS ON PLANS WHICH INDICATE
 LIGHTING BEING CONTROLLED FROM MORE THAN ONE LOCATION
 YET THE SWITCHES ARE NOT 3-WAY?
  
 6) NOTE: PLEASE SE THE SMOKE ALARMS ARE CIRCUITED TO
 CIRCUIT 12, YET THE PANEL SCHEDULE SHOWS THIS CIRCUIT
 AS SPARE?
 PLEASE REVISE PANEL SCHEDULE TO INCLUDE ALL DESIGNATED
 LOCATIONS AND AREAS IN WHICH THE CIRCUITS FEED. THE USE
 OF GEN LTS AND GEN RECPTS IS NOT LONGER PERMITTED.
 PLEASE SEE THE FOLLOWING TEXT WHICH IS EXTRACTED FROM
 THE NEC HANDBOOK. 408.4
 CODE TO REQUIRE THAT THE IDENTIFICATION FOR EVERY
 CIRCUIT SUPPLIED BY A PANEL-BOARD OR SWITCHBOARD BE
 LEGIBLE AND CLEARLY STATE THE SPECIFIC PURPOSE FOR
 WHICH THE CIRCUIT IS USED. CIRCUITS USED FOR THE SAME
 PURPOSE MUST BE IDENTIFIED AS TO THEIR LOCATION. FOR
 EXAMPLE, SMALL APPLIANCE BRANCH CIRCUITS CAN SUPPLY
 OUTLETS IN THE KITCHEN, DINING ROOM, AND KITCHEN
 COUNTERTOPS. IDENTIFYING THE CIRCUITS AS SMALL
 APPLIANCE BRANCH CIRCUITS IS NOT ACCEPTABLE; INSTEAD,
 THEY SHOULD BE IDENTIFIED AS ``KITCHEN WALL
 RECEPTACLES,'' ``DINING ROOM FLOOR RECEPTACLE,'' OR
 ``KITCHEN COUNTERTOP RECEPTACLES LEFT OF SINK.''
 CIRCUIT DIRECTORIES CONTAINING MULTIPLE ENTRIES WITH
 ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT PROVIDE THE
 SUFFICIENT DETAIL REQUIRED BY THIS SECTION.*
 408.4, 240.4, 310.16.
 PLEASE PROVIDE THE PANEL DESIGNATION TO THE CIRCUITS
 SHOWN. ARE THEY ALL FROM THE NEW SUB PANEL?
  
 7) NOTE: PLEASE SEE 110.26 AS THE DISC FOR THE CU IS
 SHOWN BEHIND THE UNIT.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-04-08 07:59:14IN REVIEW
2007-04-07 16:00:592007-04-07 16:00:59
 NOTES TO FOLLOW ON 4/8