2006-12-24 15:57:45**UNSAT 4TH REVIEW**
  
 ***PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE 680.71 FOR GFI DESIGNATION IS
 REQUIRED FOR THE JACUZZI CIRCUIT EITHER AT THE RECEPT
 OR THE BRANCH BREAKER FEEDING THIS.
  
 2) NOTE:PLEASE SEE SHEET E-2 AND E-1. PLEASE SEE LOAD
 CALCULATIONS FOR PANEL "B" WHICH ARE COMPLETELY
 DIFFERENT FROM EACH CALCULATION. PLEASE SEE THE PANEL
 "B" LOAD CALCULATION SUBMITTED ON E-1 AND E-2 DO NOT
 COMPLY WITH THE NEC 220.31 EITHER PART. A/C LOADS SHOWN
 AT 16,080 AND DE-RATED AT 40%. THERE IS NO LOCATION IN
 THE CODE WHERE THIS AMOUNT OF UNITSOR UNIT CAN BE
 DE-RATED AT 40%. PLEASE SEE THERE ARE LOADS ON
 NEUTRAL CALCULATIONS FOR EQUIPMENT WHICH IS NOT ON
 PANEL SCHEDULE OR STANDARD CALCULATIONS. PLEASE SEE
 LOADS ON PANEL "B" NOT ON E-2 CALCULATIONS AND VICE
 VERSA.
 PLEASE SEE MISSING THE LOADS PER 220.31, 220.16,
 220.19, 220.31B ETC.
 PLEASE SEE LOAD CALCULATION FOR SERVICE CAN NOT
 VERIFIED AT THIS TIME AS LOADS MAY OR MAY NOT EXCEED
 THE RATING OF THE NEW 300A MCB AS SHOWN.
 *** FYI, WHEN USING AND INSTALLING A FULL SIZED
 NEUTRAL, NEUTRAL LOAD CALCULATIONS ARE NOT REQUIRED BY
 THIS AHJ, HOWEVER ARE PERMITTED TO BE SUBMITTED. PLEASE
 KNOW IF THESE ARE SHOWN ON PLANS, THEN THEY MUST BE
 CODE COMPLIANT AND CORRELATE WITH PANEL SCHEDULES AND
 LOADS
  
 3) NOTE: PLEASE SEE RISER IS NOW COMPLETELY REVISED
 FROM PREVIOUS PLANS. PLEASE SEE MISSING THE FEEDERS
 FROM THE NEW MAIN BREAKER PANEL BOARD TO THE EXISTING
 PANEL "A". PLEASE SEE 310.15B6, 310.16, AND PLEASE SEE
 MISSING EQUIPMENT GROUNDING CONDUCTOR PER 250.24,
 250.110, 250.122.
  
  
 4 NOTE: PLEASE SHOW A LAYOUT OF THE ELECTRICAL SERVICE
 ON PLANS. PLEASE SEE SHEET E-2 INDICATES THE EXISTING
 200A SERVICE, HOWEVER DOES NOT INDICATE IF THIS IS
 WHERE THE NEW PROPOSED SERVICE IS GOING TO BE
 INSTALLED.
 PLEASE SHOW.
 FBC 106.1.2, 230.70, 110.26 , NEED TO VERIFY AND SHOW.
  
 ** NOTE: PLEASE SEE NOTE ON RISER STILL INDICATES ALL
 MAINS AND BREAKERS TO BE 22K?
 THIS IS OK, HOWEVER IF NOTED, THEN 22K RATED BREAKERS
 WILL BE REQUIRED.
  
 5) NOTE: PLEASE SEE FS 481.221 (3) AND 4).
  
 ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE REMOVED
 FROM SETS AND WILL BE PLACED WITH PREVIOUS RETAINED
 PLANS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]