| 2006-12-24 15:57:45 | **UNSAT 4TH REVIEW** |
| | |
| | ***PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE 680.71 FOR GFI DESIGNATION IS |
| | REQUIRED FOR THE JACUZZI CIRCUIT EITHER AT THE RECEPT |
| | OR THE BRANCH BREAKER FEEDING THIS. |
| | |
| | 2) NOTE:PLEASE SEE SHEET E-2 AND E-1. PLEASE SEE LOAD |
| | CALCULATIONS FOR PANEL "B" WHICH ARE COMPLETELY |
| | DIFFERENT FROM EACH CALCULATION. PLEASE SEE THE PANEL |
| | "B" LOAD CALCULATION SUBMITTED ON E-1 AND E-2 DO NOT |
| | COMPLY WITH THE NEC 220.31 EITHER PART. A/C LOADS SHOWN |
| | AT 16,080 AND DE-RATED AT 40%. THERE IS NO LOCATION IN |
| | THE CODE WHERE THIS AMOUNT OF UNITSOR UNIT CAN BE |
| | DE-RATED AT 40%. PLEASE SEE THERE ARE LOADS ON |
| | NEUTRAL CALCULATIONS FOR EQUIPMENT WHICH IS NOT ON |
| | PANEL SCHEDULE OR STANDARD CALCULATIONS. PLEASE SEE |
| | LOADS ON PANEL "B" NOT ON E-2 CALCULATIONS AND VICE |
| | VERSA. |
| | PLEASE SEE MISSING THE LOADS PER 220.31, 220.16, |
| | 220.19, 220.31B ETC. |
| | PLEASE SEE LOAD CALCULATION FOR SERVICE CAN NOT |
| | VERIFIED AT THIS TIME AS LOADS MAY OR MAY NOT EXCEED |
| | THE RATING OF THE NEW 300A MCB AS SHOWN. |
| | *** FYI, WHEN USING AND INSTALLING A FULL SIZED |
| | NEUTRAL, NEUTRAL LOAD CALCULATIONS ARE NOT REQUIRED BY |
| | THIS AHJ, HOWEVER ARE PERMITTED TO BE SUBMITTED. PLEASE |
| | KNOW IF THESE ARE SHOWN ON PLANS, THEN THEY MUST BE |
| | CODE COMPLIANT AND CORRELATE WITH PANEL SCHEDULES AND |
| | LOADS |
| | |
| | 3) NOTE: PLEASE SEE RISER IS NOW COMPLETELY REVISED |
| | FROM PREVIOUS PLANS. PLEASE SEE MISSING THE FEEDERS |
| | FROM THE NEW MAIN BREAKER PANEL BOARD TO THE EXISTING |
| | PANEL "A". PLEASE SEE 310.15B6, 310.16, AND PLEASE SEE |
| | MISSING EQUIPMENT GROUNDING CONDUCTOR PER 250.24, |
| | 250.110, 250.122. |
| | |
| | |
| | 4 NOTE: PLEASE SHOW A LAYOUT OF THE ELECTRICAL SERVICE |
| | ON PLANS. PLEASE SEE SHEET E-2 INDICATES THE EXISTING |
| | 200A SERVICE, HOWEVER DOES NOT INDICATE IF THIS IS |
| | WHERE THE NEW PROPOSED SERVICE IS GOING TO BE |
| | INSTALLED. |
| | PLEASE SHOW. |
| | FBC 106.1.2, 230.70, 110.26 , NEED TO VERIFY AND SHOW. |
| | |
| | ** NOTE: PLEASE SEE NOTE ON RISER STILL INDICATES ALL |
| | MAINS AND BREAKERS TO BE 22K? |
| | THIS IS OK, HOWEVER IF NOTED, THEN 22K RATED BREAKERS |
| | WILL BE REQUIRED. |
| | |
| | 5) NOTE: PLEASE SEE FS 481.221 (3) AND 4). |
| | |
| | ** PLEASE KNOW ONE SET OF ELECTRICAL PLANS ARE REMOVED |
| | FROM SETS AND WILL BE PLACED WITH PREVIOUS RETAINED |
| | PLANS. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |