Plan Review Notes
Plan Review Notes For Permit 06070501
Permit Number 06070501
Review Stop E
Sequence Number 3
Notes
Date Text
2006-11-21 18:38:29*** UNSAT3RD REVIEW ***
  
 ** PLEASE SEE SOME COMMENTS BELOW ARE FROM THE PREVIOUS
 REVIEWS WHICH ARE STILL IN NEED OF ADDRESSING. PLEASE
 ALSO SEE SOME NEW NOTES DUE TO CHANGES IN PLANS AND HOW
 THINGS ARE NOW SHOWN ON THE PLANS SUBMITTED. PLEASE
 ALSO SEE A NEW ELECTRICAL SHEET WHICH WAS NOT ON EITHER
 OF THE FIRST TWO REVIEWS.
 PLEASE SEE TWO NEW NOTES WHICH WERE MISSED BY THIS
 REVIEWER FROM THE PREVIOUS SET OF PLANS. ( MASTER BATH
 GFI RECEPT LOCATION/LOADS FOR A/C'S ON EXIST PANEL
 "A").
  
  
 1) NOTE: PLEASE PROVIDE A LAYOUT FOR THE SMOKE ALARM
 DEVICE IN THE EXISTING DWELLING AREAS EITHER EXISTING
 WHICH MEET THE CURRENT CODE OR NEW TO BE INSTALLED.
 THIS WAS REQUESTED ON PREVIOUS REVIEWS.
 NEED TO SHOW THE SA DEVICES INSIDE AND OUTSIDE ALL
 SLEEPING ROOMS.
 PLEASE ALSO SEE A DETAIL WAS SUBMITTED WHICH MENTIONED
 NEW AND EXISTING BEING TIED TO CIRCUIT B-12, HOWEVER
 PLEASE SEE SMOKE DETECTOR DETAIL WHICH SHOWS THESE
 BEING CIRCUITED TO THE KITCHEN OR BATH LIGHTING
 CIRCUIT.
 PLEASE KNOW AS PER A RECENT CONFERENCE; PLEASE INDICATE
 THESE DEVICES AS "SA" FOR SMOKE ALARM PER THE
 DEFINITIONS FROM NFPA-72. PLEASE KNOW AS PER AN
 INTERPRETATION FROM NFPA A SD(SMOKE DETECTOR) IS A
 DEVICE WHICH ONLY "DETECTS" AND DOES NOT SOUND AN
 AUDIBLE ALARM, WHERE A SA (SMOKE ALARM) DOES BOTH. THIS
 COMMENT WAS NOT MADE ON THE PREVIOUS REVIEWS AS THIS
 WAS ONLY BROUGHT TO ATTENTION RECENTLY. PLEASE BE SURE
 TO ADJUST CIRCUITING AS DETAIL SHOWS KIT/BATH CIRCUIT
 AND PLANS CALL FOR B-12.
 NFPA-72 11.5.1.1,11.8.3, FBC R313
  
 2) NOTE: PLEASE SEE PLANS NOW CALL FOR 22K AIC RATINGS
 FOR ALL MAIN AND BREAKERS. PLEASE VERIFY THIS STATEMENT
 AS 22K RATED BRANCH BREAKERS WOULD BE ALMOST UNHEARD OF
 FOR A SINGE FAMILY DWELLING AND IT DOES NOT SEEM THIS
 IS THE INTENT OF WHAT THE DESIGN IS SUGGESTING. THE
 EXSPENSE OF ALL BREAKERS BEING 22K WOULD ALSO BE
 SUBSTANITAL. IS THE INTENT TO MAKE THE MAINS 22K RATED
 WITH A SERIES RATING FOR THE BRANCH BREAKERS? IF SO,
 PLEASE INDICATE THIS .
 PLEASE SEE 110.9, 240.12.
 PLEASE SEE PANEL SCHEDULE AND MIS-PRINT FOR PANELS
 WHICH SHOWS "ACI" RATINGS.
  
 3) NOTE: PLEASE SEE A GFI IS BEING SHOWN IN JACUZZI
 AREA WHICH IS PART OF THE BATH ROOM RECEPT CIRCUIT
 HOWEVER ON THE PREVIOUS REVIEW THIS GFI DESIGNATION WAS
 BEING TAKEN FOR THE JACCUZZI TUB, HOWEVER UPON REVIEW
 THE PLANS APPEAR TO BE SHOWING A GFI RECEPT LOCATED
 ABOVE AND IN THE TUB AREA WHICH IS STRICTLY PROHIBITED.
 PLEASE SEE 210.52D. PLEASE SEE 680.71 FOR GFI
 DESIGNATION IS REQUIRED FOR THE JACUZZI CIRCUIT EITHER
 AT THE RECEPT OR THE BRANCH BREAKER FEEDING THIS.
 PLEASE ALSO SEE THE FOLLOWING COMMENT.
  
 4) NOTE: PLEASE SEE THE PLANS APPEAR TO HAVE INTENDED A
 DEDICATED CIRCUIT FOR THE MASTER BATH GFI AND OTHER
 BATH GFI, HOWEVER THE PANEL DESIGNATION DOES NOT
 INCLUDE "BATH" GFI, ONLY SHOWS BEDROOM GFIFOR EACH OF
 THESE.
 PLEASE SEE 210.52D, 210.11.C3
  
 5) NOTE: PLEASE SEE THE DINING ROOM DESIGNATION WAS
 REMOVED FROM THE ELECTRICAL PLANS.
 PLEASE PLACE ON PLANS.
 FBC 106.1.2, ADMIN SECT. 210.52B1
  
 6) NOTE: PLEASE SEE THERE IS NOW A SHEET E-2 WITH LOAD
 CALCULATIONS FOR PANEL "B" WHICH IS COMPLETELY
 DIFFERENT FROM THE PANEL "B" LOAD CALCULATION SUBMITTED
 ON E-1.??
 PLEASE SEE MISSING THE LOADS PER 220.31, 220.16 ETC.
  
 7) NOTE:PLEASE ALSO SEE PANEL "A" SHOWS LOAD
 CALCULATIONS WHICH INDICATE 20KW OF HEAT LOADS YET
 PANEL SCHEDULE ONLY INDICATES A TOTAL OF 15KW OF HEAT.
 (ONE AT 10KW AND THE OTHER AT 5KW).
 PLEASE SEE LOAD CALCULATIONS ALSO SHOW A "SHIFT" OF
 SOME KIND ON THE LOADS TO THE RIGHT OF ALL THE
 APPLIANCES.
 BOTH OF THESE ITEMS WERE SHOWN THE SAME WAY ON PREVIOUS
 PLANS(2ND SET) HOWEVER WAS NOT COMMENTED ON. 220.31.
  
 8) NOTE: PLEASE SEE RISER IS STILL SHOWING "EQUIPMENT
 GROUNDING CONDUCTORS" BEFORE THE FIRST MEANS OF
 DISCONNECT WHICH IS NOT PERMITTED. PLEASE SEE 250.6,
 AND 250.24B. THE FOLLOWING IS TAKEN FROM THE CODE.
  
 250.6 OBJECTIONABLE CURRENT OVER GROUNDING CONDUCTORS.
 (A) ARRANGEMENT TO PREVENT OBJECTIONABLE CURRENT. THE
 GROUNDING OF ELECTRICAL SYSTEMS, CIRCUIT CONDUCTORS,
 SURGE ARRESTERS, AND CONDUCTIVE NON-CURRENT-CARRYING
 MATERIALS AND EQUIPMENT SHALL BE INSTALLED AND ARRANGED
 IN A MANNER THAT WILL PREVENT OBJECTIONABLE CURRENT
 OVER THE GROUNDING CONDUCTORS OR GROUNDING PATHS.
  
 THE REST OF 250.6 AND 250.24B TALKS OF THE EQUIPMENT
 GROUNDING CONDUCTORS AFTER THE FIRST MEANS OF
 DISCONNECT ONLY.
  
 9) NOTE: PLEASE SHOW A LAYOUT OF THE ELECTRICAL SERVICE
 ON PLANS TO VERIFY GROUPING OF MAINS PER 230.72.
  
  
 10) NOTE: PLEASE SEE THAT ON THE PREVIOUS REVIEW A
 NOTICE WAS GIVEN WITH REFERENCE TO FLORIDA STATUTES
 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS. PLEASE
 KNOW SOME OF THE ABOVE COMMENTS ARE THE SAME FROM THE
 FIRST AND SECOND REVIEW, HOWEVER THE PLANS SEEM TO HAVE
 INTENT AND AN ATTEMPT TO ADDRESS COMMENT(S), EVEN
 THOUGH IT MAY NOT HAVE BEEN ADDRESSED FULLY. THE 4X FEE
 FOR THE PLAN REVIEW PORTION OF THE PERMIT FEE IS NOT
 ASSESSED AT THIS TIME.
 PLEASE SEE SOME OTHER COMMENTS WERE ORIGINATED ON THE
 SECOND REVIEW WHICH WILL NEED TO BE ADDRESSED BY THE
 NEXT REVIEW SO THE NOTICE IS STILL GIVEN AS A NOTICE
 ONLY.
 AS ON PREVIOUS REVIEW ONE SET OF EACH OF THE ELECTRICAL
 PLANS ARE BEING RETAINED BY THIS OFFICE FOR FILE. ONE
 SET OF THE REDLINED PLANS ARE BEING RETURNED. ** IT IS
 RECOMMENDED THAT IF THERE ARE NAY QUESTIONS, COMMENTS
 OR THE NOTES TYPED ABOVE ARE NOT CLEAR IN ANY FASHION,
 PLEASE DO NOT HESITATE IN CONTACTING THIS OFFICE TO GO
 OVER COMMENTS.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 **PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717