Plan Review Notes
Plan Review Notes For Permit 06070501
Permit Number 06070501
Review Stop E
Sequence Number 2
Notes
Date Text
2006-10-01 00:00:00***** UNSAT 2ND REVIEW *****
  
 ** PLEASE SEE MANY OF THE COMMENTS FROM
 THE PREVIOUS REVIEW ARE STILL IN NEED OF
 BEING ADDRESSED. PLEASE ALSO SEE NEW
 NOTES FOR CHANGES IN PLANS MADE AND NEW
 NOTES.
 PLEASE SEE MOST COMMENTS ARE THE SAME AS
 PREVIOUS REVIEW AND ALL NOTES BELOW ARE
 TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH
 NEW NOTES ADDED TO BOTTOM OF LIST.
  
 1) NOTE: NO, PLEASE SEE AN AIC RATING IS
 SHOWN FOR METER CAN NOT NEW MAIN AND
 PANEL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: OK, SIZED CORRECTED HOWEVER
 PLEASE SEE OTHER COMMENT FOR FOOTER
 STEEL.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 250.66 FOR THE NEW
 MIN SIZE GROUNDING ELECTRODE CONDUCTOR
 AS SERVICE HAS NOW INCREASED TO 300A'S.
 #2 MIN).
  
 3) NOTE: YES, ADDED THESE FROM MAINS TO
 SUB PANELS, HOWEVER PLEASE SEE NOW
 "EQUIPMENT GROUNDING CONDCUTORS" HAVE
 ALSO NOW BEEN ADDED FROM METERCAN TO
 MAINS, WHICH NOW PARALLEL'S THE NEUTRAL.
 PLEASE SEE 250.6, 250.24B AS THIS IS NOT
 PERMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEEMISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO
 PANELS.
 250.110,250.24B,250.122.
  
 4) NOTE: NO, SAME NOTE, PLEASE SEE PANEL
 SCHEDULE STILL SHOW THE SAME.
 SEE FEEDERS AS SHOWN.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CLARIFY 3/0'S SHOWN FOR
 NEUTRAL'S FOR BOTHPANELS? PLEASE SEE
 THIS IS SHOWN FOR 100A PANELS?
 PLEASE KNOW, 3/0'S WILL NOT FIT INTO
 LUGS ON SMALLER EQUIPMENT.
 106.1.2
  
 5) NOTE: NO, SAME COMMENT AS PANEL
 SCHEDULES STILL SHOW 300A PANELS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE CORRELATE RISER AND
 PANELS AS PANELS ARE SHOWN AS 300A'S
 EACH.?
 240,215.5,106.1.2
  
 6) NOTE:NO, PLEASE SEE A #6 IS NOTED TO
 NEW SUB PANEL, HOWEVER PLEASE SEE THE
 SIZE SHALL BE AS STATED FOR NEW #2 AND
 SHALL EXTEND TO THEGROUNDING ELECTRODE
 SYSTEM.
  
 ** PREVIOUS REVIEW NOTE**
 PLEASE SEE NEW FOOTER STEEL IS
 REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
 250.50.
  
 7) NOTE:NO, PLEASE PROVIDE LAYOUT FOR
 ALL SD'S EITHER EXISTING OR NEW TO BE
 INSTALLED WHICH CONFORM TO THE CURRENT
 NFPA-72 2002 AS NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING SD'S AS
 REQUIRED PER NFPA-72 11.5.1.1, 11.8.3,
 PLEASE ALSO PROVIDE A LAYOUT OF THE
 EXISTING SD'S IF EXISTING WHICH MEET THE
 CURRENT CODE OR NEW SHALL BE INSTALLED.
 R313
  
 8) NOTE: NO, PLEASE SEE CIRCUITING FOR
 DINING, KITCHEN SMALL APPL CIRCUITS TWO
 OR MORE SHALL NOT FEED ANY OTHER AREAS,
 AND RECEPTS. ONLY PERMITTED TO FEED THE
 AREAS OF THE LIKE. PLEASE SEE ELECTRICAL
 DEVICES IN OTHER AREAS ON THE DINING
 APPLIANCE CIRCUIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE LTS BEING SHOWN ON A
 SMALL APPL CIRCUIT?
 MECH RM? PLEASE KNOW, NO OTHER LOADS ARE
 PERMITTED ON THE SMALL APPL CIRCUITS.
 210.52B1.
  
 9) NOTE: OK, AS FIXTURE IS NOTED .
  
 10) NOTE: OK.
  
 11) NOTE: OK.
  
 12) NOTE: OK.
  
 13) NOTE: OK.
  
 14) NOTE: NO, SAME NOTE>
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE PANEL SCHEDULE
 FOR AREAS AND RMS AS NOTED. 408.4.
 IE: BED RM LT, MASTER NEDRM RECEPTS ETC.
  
 15) NOTE: NO, SAME NOTE, PLEASE SEE
 "BATH" GFI/ OR DEDICATED CIRCUIT(S) ARE
 NOT SHOWN ON PANEL SCHEDULE. SEE NOTE
 ABOVE #14.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3.
 MUST ALSO BE 20A AND #12. SHOWS #14 AND
 15A.
  
 16) NOTE: NO, PLEASE SEE NOTE ABOVE WITH
 RESPECT TO NO OTHER ELECTRICAL DEVICES
 ON THIS CIRCUIT, HOWEVER SEE PREVIOUS
 NOTE FOR MIN VA FOR THIS CIRCUIT.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 DINING RM/AREA CIRCUITS PER
 210.52B1,210.11C1, 220.16.
  
 17) NOTE: NO, PLEASE SEE THERE ARE SOME
 ELECTRICAL DEVICES W/OUT CIRCUIT #'S
 ONLY MINOR.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE COMPLETE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 240.4,310.16,215.5 ETC
 FBC 106.1.2, 106.3.5.4
  
 18) NOTE: NO, PLEASE SEE 2002 AND SEE
 ALL CIRCUITING AS SHOWN ON PLANS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE 2002 NEC 210.12B
 AND PLEASE LIST ALL THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRED.
 PLEASE KNOW, AFCI IS NOT ONLY FOR
 RECEPTS.
 408.4
  
 19) NOTE: NO, HOWEVER THIS COMMENT SEEM
 TO HAVE BEEN ADDRESSED BUT AS ONLY A
 MISPRINT AS TWO- NFPA-72'S ARE SHOWN.
 MISSING ONLY THE "70". THIS WOULD HAVE
 BEEN REDLINED, HOWEVER PLANS ARE COMING
 BACK FOR OTHER CORRECTIONS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE PLANS SHALL
 REFERENCE THE FOLLOWING CODES ADOPTED
 AND IN EFFECT FOR THIS PROJECT.
 NFPA-72 2002, NFPA-70 2002. FBC 2004
  
 20) NOTE: NO, PLEASE SEE PREVIOUS NOTE.
 PLEASE ALSO SEE THE PRINTED CA # IS NOT
 CLEAR AND VISABLEON ALL SHEETS, THIS
 WAS HAND-WRITTEN BY THISREVIEWER IN
 ORDER FOR OTHERS TO CLEARLY SEE #.
 PLEASE STILL SEE MISSING PRINTED NAME AS
 REQUIRED.
 THIS IS REQUIRED ON ALL SHEETS AND FOR
 ALL TRADES WHETHER OR NOT COMMENT IS
 MADE BY OTHER REVIEWER(S).
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCKS FOR THE
 ARCHITECT'S PRINTED NAME AND PRINTED
 LICENSE #.
 PLEASE ALSO SEE PLUMB NOTES AS THE
 SIGNATURE ON PLAUMB RISER ATTACHED TO
 PLANS IS NOT AN ORIGINAL"WET" SIGNATURE.
 PLAN CONTAINS A RAISED SEAL OVER A
 "PHOTO-COPIED" SIGNATURE..
 FS 481.221, FAC 61G1-16.004
  
 21) NOTE: NO, PLEASE SEE NOTE ABOVE FOR
 AFCI PROTECTION AND NOTE FOR EXISTING.
  
 **PREVIOUS REVIEW NOTE **
 PLEASE SEE SD NOTE WHICH IS
 ADDED TO PLANS.
 PLEASE SEE IF THE CIRCUITING IS DONE AS
 NOTED, THEN ARC FAULT PROTECTION WILL BE
 REQUIRED FOR THOSE CIRCUITS ALSO.
 PLEASE KNOW, ALL SD'S ARE REQUIRED TO BE
 WIRED "INLINE".
 PLEASE INDICATE CIRCUITING FROM
 EXISTING.
  
 22) NOTE: OK.
  
 23) NOTE: NO/YES, PLEASE SEE CONDUITS
 WERE CORRECTED O RISER DIAGRAM, HOWEVER
 FEEDER SCHEDULE ON PANEL WAS NOT.
 PLEASE ADJUST.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE CONDUIT SIZES AS
 SHOWN AND CONDUCTORS AS SHOWN EXCEED THE
 MAXIMUM PIPE FILL AS SHOWN. PLEASE SEE
 MAX FIGURES IN TABLE CHAPTER 9.
 215.5,106.1.2, ETC
  
 24) NOTE: OK.
  
 25) NOTE: OK, HOWEVER THIS WILL REMAIN
 AS A NOTE FOR NEXT SUBMITTIAL.
  
 ** PREVIOUS REVIEW NOTE **
 *** IMPORTANT**
 ONCE ALL REVIEWS ARE COMPLETE, PLANS ARE
 PICKED UP AND BEFORE RESUBMITTING PLANS.
 PLEASE COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS. ONLY ONE COPY
 OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE ONLY.
  
  
 ***** NEW NOTES*****
  
 26) NOTE: PLEASE VERIFY THE NEW AND
 EXISTING MAINS ARE GROUPED ON
 SITE/OVERVIEW PLAN.
 230.72
  
 27) NOTE: PLEASE SEE FLORIDA STATUES
 553.80(2)(B) WITH RESPECT TO DESIGN
 PROFESSIONALS AND REPEAT COMMENTS FOR
 CODE COMPLIANCE.
 NOTICE TO FS ABOVE IS ONLY A NOTICE
 GIVEN AT THIS TIME.
 PLEASE KNOW ONE SET OF ELECTRICAL PLANS
 FROM EACHREVIEW HAVE BEEN RETAINED FOR
 FILE DUE TO THE EXTENT OF ELECTRICAL
 COMMENTS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTRUCTION SERVICES DEPT.
 561-805-6717