| Date |
Text |
| 2006-10-01 00:00:00 | ***** UNSAT 2ND REVIEW ***** |
| | |
| | ** PLEASE SEE MANY OF THE COMMENTS FROM |
| | THE PREVIOUS REVIEW ARE STILL IN NEED OF |
| | BEING ADDRESSED. PLEASE ALSO SEE NEW |
| | NOTES FOR CHANGES IN PLANS MADE AND NEW |
| | NOTES. |
| | PLEASE SEE MOST COMMENTS ARE THE SAME AS |
| | PREVIOUS REVIEW AND ALL NOTES BELOW ARE |
| | TAKEN DIRECTLY FROM PREVIOUS REVIEW WITH |
| | NEW NOTES ADDED TO BOTTOM OF LIST. |
| | |
| | 1) NOTE: NO, PLEASE SEE AN AIC RATING IS |
| | SHOWN FOR METER CAN NOT NEW MAIN AND |
| | PANEL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: OK, SIZED CORRECTED HOWEVER |
| | PLEASE SEE OTHER COMMENT FOR FOOTER |
| | STEEL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 250.66 FOR THE NEW |
| | MIN SIZE GROUNDING ELECTRODE CONDUCTOR |
| | AS SERVICE HAS NOW INCREASED TO 300A'S. |
| | #2 MIN). |
| | |
| | 3) NOTE: YES, ADDED THESE FROM MAINS TO |
| | SUB PANELS, HOWEVER PLEASE SEE NOW |
| | "EQUIPMENT GROUNDING CONDCUTORS" HAVE |
| | ALSO NOW BEEN ADDED FROM METERCAN TO |
| | MAINS, WHICH NOW PARALLEL'S THE NEUTRAL. |
| | PLEASE SEE 250.6, 250.24B AS THIS IS NOT |
| | PERMITTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEEMISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAINS TO |
| | PANELS. |
| | 250.110,250.24B,250.122. |
| | |
| | 4) NOTE: NO, SAME NOTE, PLEASE SEE PANEL |
| | SCHEDULE STILL SHOW THE SAME. |
| | SEE FEEDERS AS SHOWN. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CLARIFY 3/0'S SHOWN FOR |
| | NEUTRAL'S FOR BOTHPANELS? PLEASE SEE |
| | THIS IS SHOWN FOR 100A PANELS? |
| | PLEASE KNOW, 3/0'S WILL NOT FIT INTO |
| | LUGS ON SMALLER EQUIPMENT. |
| | 106.1.2 |
| | |
| | 5) NOTE: NO, SAME COMMENT AS PANEL |
| | SCHEDULES STILL SHOW 300A PANELS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE CORRELATE RISER AND |
| | PANELS AS PANELS ARE SHOWN AS 300A'S |
| | EACH.? |
| | 240,215.5,106.1.2 |
| | |
| | 6) NOTE:NO, PLEASE SEE A #6 IS NOTED TO |
| | NEW SUB PANEL, HOWEVER PLEASE SEE THE |
| | SIZE SHALL BE AS STATED FOR NEW #2 AND |
| | SHALL EXTEND TO THEGROUNDING ELECTRODE |
| | SYSTEM. |
| | |
| | ** PREVIOUS REVIEW NOTE** |
| | PLEASE SEE NEW FOOTER STEEL IS |
| | REQUIRED TO BE PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. |
| | 250.50. |
| | |
| | 7) NOTE:NO, PLEASE PROVIDE LAYOUT FOR |
| | ALL SD'S EITHER EXISTING OR NEW TO BE |
| | INSTALLED WHICH CONFORM TO THE CURRENT |
| | NFPA-72 2002 AS NOTED. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING SD'S AS |
| | REQUIRED PER NFPA-72 11.5.1.1, 11.8.3, |
| | PLEASE ALSO PROVIDE A LAYOUT OF THE |
| | EXISTING SD'S IF EXISTING WHICH MEET THE |
| | CURRENT CODE OR NEW SHALL BE INSTALLED. |
| | R313 |
| | |
| | 8) NOTE: NO, PLEASE SEE CIRCUITING FOR |
| | DINING, KITCHEN SMALL APPL CIRCUITS TWO |
| | OR MORE SHALL NOT FEED ANY OTHER AREAS, |
| | AND RECEPTS. ONLY PERMITTED TO FEED THE |
| | AREAS OF THE LIKE. PLEASE SEE ELECTRICAL |
| | DEVICES IN OTHER AREAS ON THE DINING |
| | APPLIANCE CIRCUIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE LTS BEING SHOWN ON A |
| | SMALL APPL CIRCUIT? |
| | MECH RM? PLEASE KNOW, NO OTHER LOADS ARE |
| | PERMITTED ON THE SMALL APPL CIRCUITS. |
| | 210.52B1. |
| | |
| | 9) NOTE: OK, AS FIXTURE IS NOTED . |
| | |
| | 10) NOTE: OK. |
| | |
| | 11) NOTE: OK. |
| | |
| | 12) NOTE: OK. |
| | |
| | 13) NOTE: OK. |
| | |
| | 14) NOTE: NO, SAME NOTE> |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE PANEL SCHEDULE |
| | FOR AREAS AND RMS AS NOTED. 408.4. |
| | IE: BED RM LT, MASTER NEDRM RECEPTS ETC. |
| | |
| | 15) NOTE: NO, SAME NOTE, PLEASE SEE |
| | "BATH" GFI/ OR DEDICATED CIRCUIT(S) ARE |
| | NOT SHOWN ON PANEL SCHEDULE. SEE NOTE |
| | ABOVE #14. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) PER |
| | 210.52D,210.11C3. |
| | MUST ALSO BE 20A AND #12. SHOWS #14 AND |
| | 15A. |
| | |
| | 16) NOTE: NO, PLEASE SEE NOTE ABOVE WITH |
| | RESPECT TO NO OTHER ELECTRICAL DEVICES |
| | ON THIS CIRCUIT, HOWEVER SEE PREVIOUS |
| | NOTE FOR MIN VA FOR THIS CIRCUIT. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED |
| | DINING RM/AREA CIRCUITS PER |
| | 210.52B1,210.11C1, 220.16. |
| | |
| | 17) NOTE: NO, PLEASE SEE THERE ARE SOME |
| | ELECTRICAL DEVICES W/OUT CIRCUIT #'S |
| | ONLY MINOR. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE COMPLETE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE PANEL |
| | SCHEDULES SUBMITTED. |
| | 240.4,310.16,215.5 ETC |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 18) NOTE: NO, PLEASE SEE 2002 AND SEE |
| | ALL CIRCUITING AS SHOWN ON PLANS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE 2002 NEC 210.12B |
| | AND PLEASE LIST ALL THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS AS REQUIRED. |
| | PLEASE KNOW, AFCI IS NOT ONLY FOR |
| | RECEPTS. |
| | 408.4 |
| | |
| | 19) NOTE: NO, HOWEVER THIS COMMENT SEEM |
| | TO HAVE BEEN ADDRESSED BUT AS ONLY A |
| | MISPRINT AS TWO- NFPA-72'S ARE SHOWN. |
| | MISSING ONLY THE "70". THIS WOULD HAVE |
| | BEEN REDLINED, HOWEVER PLANS ARE COMING |
| | BACK FOR OTHER CORRECTIONS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE PLANS SHALL |
| | REFERENCE THE FOLLOWING CODES ADOPTED |
| | AND IN EFFECT FOR THIS PROJECT. |
| | NFPA-72 2002, NFPA-70 2002. FBC 2004 |
| | |
| | 20) NOTE: NO, PLEASE SEE PREVIOUS NOTE. |
| | PLEASE ALSO SEE THE PRINTED CA # IS NOT |
| | CLEAR AND VISABLEON ALL SHEETS, THIS |
| | WAS HAND-WRITTEN BY THISREVIEWER IN |
| | ORDER FOR OTHERS TO CLEARLY SEE #. |
| | PLEASE STILL SEE MISSING PRINTED NAME AS |
| | REQUIRED. |
| | THIS IS REQUIRED ON ALL SHEETS AND FOR |
| | ALL TRADES WHETHER OR NOT COMMENT IS |
| | MADE BY OTHER REVIEWER(S). |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE MISSING REQUIRED |
| | INFORMATION ON TITLE BLOCKS FOR THE |
| | ARCHITECT'S PRINTED NAME AND PRINTED |
| | LICENSE #. |
| | PLEASE ALSO SEE PLUMB NOTES AS THE |
| | SIGNATURE ON PLAUMB RISER ATTACHED TO |
| | PLANS IS NOT AN ORIGINAL"WET" SIGNATURE. |
| | PLAN CONTAINS A RAISED SEAL OVER A |
| | "PHOTO-COPIED" SIGNATURE.. |
| | FS 481.221, FAC 61G1-16.004 |
| | |
| | 21) NOTE: NO, PLEASE SEE NOTE ABOVE FOR |
| | AFCI PROTECTION AND NOTE FOR EXISTING. |
| | |
| | **PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE SD NOTE WHICH IS |
| | ADDED TO PLANS. |
| | PLEASE SEE IF THE CIRCUITING IS DONE AS |
| | NOTED, THEN ARC FAULT PROTECTION WILL BE |
| | REQUIRED FOR THOSE CIRCUITS ALSO. |
| | PLEASE KNOW, ALL SD'S ARE REQUIRED TO BE |
| | WIRED "INLINE". |
| | PLEASE INDICATE CIRCUITING FROM |
| | EXISTING. |
| | |
| | 22) NOTE: OK. |
| | |
| | 23) NOTE: NO/YES, PLEASE SEE CONDUITS |
| | WERE CORRECTED O RISER DIAGRAM, HOWEVER |
| | FEEDER SCHEDULE ON PANEL WAS NOT. |
| | PLEASE ADJUST. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE CONDUIT SIZES AS |
| | SHOWN AND CONDUCTORS AS SHOWN EXCEED THE |
| | MAXIMUM PIPE FILL AS SHOWN. PLEASE SEE |
| | MAX FIGURES IN TABLE CHAPTER 9. |
| | 215.5,106.1.2, ETC |
| | |
| | 24) NOTE: OK. |
| | |
| | 25) NOTE: OK, HOWEVER THIS WILL REMAIN |
| | AS A NOTE FOR NEXT SUBMITTIAL. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | *** IMPORTANT** |
| | ONCE ALL REVIEWS ARE COMPLETE, PLANS ARE |
| | PICKED UP AND BEFORE RESUBMITTING PLANS. |
| | PLEASE COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. ONLY ONE COPY |
| | OF THE OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED ALONG WITH NEW SETS FOR |
| | REFERENCE ONLY. |
| | |
| | |
| | ***** NEW NOTES***** |
| | |
| | 26) NOTE: PLEASE VERIFY THE NEW AND |
| | EXISTING MAINS ARE GROUPED ON |
| | SITE/OVERVIEW PLAN. |
| | 230.72 |
| | |
| | 27) NOTE: PLEASE SEE FLORIDA STATUES |
| | 553.80(2)(B) WITH RESPECT TO DESIGN |
| | PROFESSIONALS AND REPEAT COMMENTS FOR |
| | CODE COMPLIANCE. |
| | NOTICE TO FS ABOVE IS ONLY A NOTICE |
| | GIVEN AT THIS TIME. |
| | PLEASE KNOW ONE SET OF ELECTRICAL PLANS |
| | FROM EACHREVIEW HAVE BEEN RETAINED FOR |
| | FILE DUE TO THE EXTENT OF ELECTRICAL |
| | COMMENTS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTRUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |