| 2006-07-22 00:00:00 | ********** UNSAT ************ |
| | |
| | 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 2) NOTE: PLEASE SEE 250.66 FOR THE NEW |
| | MIN SIZE GROUNDIGN ELECTRODE CONDUCTOR |
| | AS SERVICE HAS NOW INCREASED TO 300A'S. |
| | #2 MIN). |
| | |
| | 3) NOTE: PLEASE SEEMISSING EQUIPMENT |
| | GROUNDING CONDUCTOR FROM MAINS TO |
| | PANELS. |
| | 250.110,250.24B,250.122. |
| | |
| | 4) NOTE: PLEASE CLARIFY 3/0'S SHOWN FOR |
| | NEUTRAL'S FOR BOTHPANELS? PLEASE SEE |
| | THIS IS SHOWN FOR 100A PANELS? |
| | PLEASE KNOW, 3/0'S WILL NOT FIT INTO |
| | LUGS ON SMALLER EQUIPMENT. |
| | 106.1.2 |
| | |
| | 5) NOTE: PLEASE CORRELATE RISER AND |
| | PANELS AS PANELS ARE SHOWN AS 300A'S |
| | EACH.? |
| | 215.5,106.1.2 |
| | |
| | 6) NOTE: PLEASE SEE NEW FOOTER STEEL IS |
| | REQUIRED TO BE PART OF THE GROUNDING |
| | ELECTRODE SYSTEM. |
| | 250.50. |
| | |
| | 7) NOTE: PLEASE SEE MISSING SD'S AS |
| | REQUIRED PER NFPA-72 11.5.1.1, 11.8.3, |
| | PLEASE ALSO PROVIDE A LAYOUT OF THE |
| | EXISTING SD'S IF EXISTING WHICH MEET THE |
| | CURRENT CODE OR NEW SHALL BE INSTALLED. |
| | R313 |
| | |
| | 8) NOTE: PLEASE SEE LTS BEING SHOWN ON A |
| | SMALL APPL CIRCUIT? |
| | MECH RM? PLEASE KNOW, NO OTHER LOADS ARE |
| | PERMITTED ON THE SMALL APPL CIRCUITS. |
| | 210.52B1. |
| | |
| | 9) NOTE: PLEASE PROVIDE A FIXTURE |
| | SCHEDULE FOR CLOSET LTS. PLEASE SEE |
| | 410.8 FOR MIN CLEARENCES. |
| | |
| | 10) NOTE: PLEASE SEE 424.3B FOR MIN OPC |
| | FOR AHU HEAT. PLEASE SEE 10+ KW UNIT |
| | WITH 40A OCP??? AND #8 AWG. |
| | PLEASE CORRECT. |
| | |
| | 11) NOTE: PLEASE SEE MISSING A/C |
| | DISCONNECTS AS REQUIRED PER 440.11 AND |
| | MIN CLEARENCES PER 110.26. |
| | |
| | 12) NOTE: PLEASE SEE MISSING GFI |
| | REQUIRED FOR CU'S. 210.63, 210.8A |
| | |
| | 13) NOTE: PLEASE SEE MISSING EGRESS LT |
| | AND CONTROL FROM MASTER BEDRM. 210.70, |
| | LS 101 7.8 |
| | |
| | 14) NOTE: PLEASE COMPLETE PANEL SCHEDULE |
| | FOR AREAS AND RMS AS NOTED. 408.4. |
| | IE: BED RM LT, MASTER NEDRM RECEPTS ETC. |
| | |
| | 15) NOTE: PLEASE SEE MISSING REQUIRED |
| | DEDICATED BATH(S) CIRCUIT(S) PER |
| | 210.52D,210.11C3. |
| | MUST ALSO BE 20A AND #12. SHOWS #14 AND |
| | 15A. |
| | |
| | 16) NOTE: PLEASE SEE MISSING REQUIRED |
| | DINING RM/AREA CIRCUITS PER |
| | 210.52B1,210.11C1, 220.16. |
| | |
| | 17) NOTE: PLEASE COMPLETE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH THE PANEL |
| | SCHEDULES SUBMITTED. |
| | 240.4,310.16,215.5 ETC |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 18) NOTE: PLEASE SEE 2002 NEC 210.12B |
| | AND PLEASE LIST ALL THE REQUIRED ARC |
| | FAULT PROTECTED CIRCUITS AS REQUIRED. |
| | PLEASE KNOW, AFCI IS NOT ONLY FOR |
| | RECEPTS. |
| | 408.4 |
| | |
| | 19) NOTE: PLEASE SEE PALSN SHALL |
| | REFERENCE THE FOLLOWING CODES ADOPTED |
| | AND IN EFFECT FOR THIS PROJECT. |
| | NFPA-72 2002, NFPA-70 2002. FBC 2004 |
| | |
| | 20) NOTE: PLEASE SEE MISSING REQUIRED |
| | INFORMATION ON TITLE BLOCKS FOR THE |
| | ARCHITECT'S PRINTED NAME AND PRINTED |
| | LICENSE #. |
| | PLEASE ALSO SEE PLUMB NOTES AS THE |
| | SIGNATURE ON PLAUMB RISER ATTACHED TO |
| | PLANS IS NOT AN ORIGINAL"WET" SIGNATURE. |
| | PLAN CONTAINS A RAISED SEAL OVER A |
| | "PHOTO-COPIED" SIGNATURE.. |
| | FS 481.221, FAC 61G1-16.004 |
| | |
| | 21) NOTE: PLEASE SEE SD NOTE WHICH IS |
| | ADDED TO PLANS. |
| | PLEASE SEE IF THE CIRCUITING IS DONE AS |
| | NOTED, THEN ARC FAULT PROTECTION WILL BE |
| | REQUIRED FOR THOSE CIRCUITS ALSO. |
| | PLEASE KNOW, ALL SD'S ARE REQUIRED TO BE |
| | WIRED "INLINE". |
| | PLEASE INDICATE CIRCUITING FROM |
| | EXISTING. |
| | |
| | 22) NOTE: PLEASE CLARIFY AND VERIFY |
| | WHERE THE CWP IS FOR THE GROUNDING |
| | ELECTRODE SYSTEM. PLEASE SEE |
| | 250.50,250.52 ETC. |
| | PLEASE SHOW. |
| | |
| | 23) NOTE: PLEASE SEE CONDUIT SIZES AS |
| | SHOWN AND CONDUCTORS AS SHOWN EXCEED THE |
| | MAXIMUM PIPE FILL AS SHOWN. PLEASE SEE |
| | MAX FIGURES IN TABLE CHAPTER 9. |
| | 215.5,106.1.2, ETC |
| | |
| | 24) NOTE: PLEASE SEE MAIN DISCONNECTS |
| | ARE MISSING THE SIZE AND OCP FOR EACH. |
| | 240.4,310.16,230.70 ETC. |
| | |
| | 25) NOTE: *** IMPORTANT** |
| | ONCE ALL REVIEWS ARE COMPLETE, PLANS ARE |
| | PICKED UP AND BEFORE RESUBMITTING PLANS. |
| | PLEASE COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO COMPLETE SETS FOR REVIEW AND |
| | STAMPING. PLEASE DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. ONLY ONE COPY |
| | OF THE OLD/VOIDED SHEETS SHOULD BE |
| | SUBMITTED ALONG WITH NEW SETS FOR |
| | REFERENCE ONLY. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |
| | |
| | |
| | |
| 2006-07-21 00:00:00 | REVIEW TO CONTINUE. PLANS WILL GO INTO |
| | "F" STATUS. |
| | NOTES TO FOLLOW WHEN REVIEW IS COMPLETE. |