Plan Review Notes
Plan Review Notes For Permit 06070501
Permit Number 06070501
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-22 00:00:00********** UNSAT ************
  
 1) NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 2) NOTE: PLEASE SEE 250.66 FOR THE NEW
 MIN SIZE GROUNDIGN ELECTRODE CONDUCTOR
 AS SERVICE HAS NOW INCREASED TO 300A'S.
 #2 MIN).
  
 3) NOTE: PLEASE SEEMISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAINS TO
 PANELS.
 250.110,250.24B,250.122.
  
 4) NOTE: PLEASE CLARIFY 3/0'S SHOWN FOR
 NEUTRAL'S FOR BOTHPANELS? PLEASE SEE
 THIS IS SHOWN FOR 100A PANELS?
 PLEASE KNOW, 3/0'S WILL NOT FIT INTO
 LUGS ON SMALLER EQUIPMENT.
 106.1.2
  
 5) NOTE: PLEASE CORRELATE RISER AND
 PANELS AS PANELS ARE SHOWN AS 300A'S
 EACH.?
 215.5,106.1.2
  
 6) NOTE: PLEASE SEE NEW FOOTER STEEL IS
 REQUIRED TO BE PART OF THE GROUNDING
 ELECTRODE SYSTEM.
 250.50.
  
 7) NOTE: PLEASE SEE MISSING SD'S AS
 REQUIRED PER NFPA-72 11.5.1.1, 11.8.3,
 PLEASE ALSO PROVIDE A LAYOUT OF THE
 EXISTING SD'S IF EXISTING WHICH MEET THE
 CURRENT CODE OR NEW SHALL BE INSTALLED.
 R313
  
 8) NOTE: PLEASE SEE LTS BEING SHOWN ON A
 SMALL APPL CIRCUIT?
 MECH RM? PLEASE KNOW, NO OTHER LOADS ARE
 PERMITTED ON THE SMALL APPL CIRCUITS.
 210.52B1.
  
 9) NOTE: PLEASE PROVIDE A FIXTURE
 SCHEDULE FOR CLOSET LTS. PLEASE SEE
 410.8 FOR MIN CLEARENCES.
  
 10) NOTE: PLEASE SEE 424.3B FOR MIN OPC
 FOR AHU HEAT. PLEASE SEE 10+ KW UNIT
 WITH 40A OCP??? AND #8 AWG.
 PLEASE CORRECT.
  
 11) NOTE: PLEASE SEE MISSING A/C
 DISCONNECTS AS REQUIRED PER 440.11 AND
 MIN CLEARENCES PER 110.26.
  
 12) NOTE: PLEASE SEE MISSING GFI
 REQUIRED FOR CU'S. 210.63, 210.8A
  
 13) NOTE: PLEASE SEE MISSING EGRESS LT
 AND CONTROL FROM MASTER BEDRM. 210.70,
 LS 101 7.8
  
 14) NOTE: PLEASE COMPLETE PANEL SCHEDULE
 FOR AREAS AND RMS AS NOTED. 408.4.
 IE: BED RM LT, MASTER NEDRM RECEPTS ETC.
  
 15) NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH(S) CIRCUIT(S) PER
 210.52D,210.11C3.
 MUST ALSO BE 20A AND #12. SHOWS #14 AND
 15A.
  
 16) NOTE: PLEASE SEE MISSING REQUIRED
 DINING RM/AREA CIRCUITS PER
 210.52B1,210.11C1, 220.16.
  
 17) NOTE: PLEASE COMPLETE ALL CIRCUITING
 ON PLANS AND CORRELATE WITH THE PANEL
 SCHEDULES SUBMITTED.
 240.4,310.16,215.5 ETC
 FBC 106.1.2, 106.3.5.4
  
 18) NOTE: PLEASE SEE 2002 NEC 210.12B
 AND PLEASE LIST ALL THE REQUIRED ARC
 FAULT PROTECTED CIRCUITS AS REQUIRED.
 PLEASE KNOW, AFCI IS NOT ONLY FOR
 RECEPTS.
 408.4
  
 19) NOTE: PLEASE SEE PALSN SHALL
 REFERENCE THE FOLLOWING CODES ADOPTED
 AND IN EFFECT FOR THIS PROJECT.
 NFPA-72 2002, NFPA-70 2002. FBC 2004
  
 20) NOTE: PLEASE SEE MISSING REQUIRED
 INFORMATION ON TITLE BLOCKS FOR THE
 ARCHITECT'S PRINTED NAME AND PRINTED
 LICENSE #.
 PLEASE ALSO SEE PLUMB NOTES AS THE
 SIGNATURE ON PLAUMB RISER ATTACHED TO
 PLANS IS NOT AN ORIGINAL"WET" SIGNATURE.
 PLAN CONTAINS A RAISED SEAL OVER A
 "PHOTO-COPIED" SIGNATURE..
 FS 481.221, FAC 61G1-16.004
  
 21) NOTE: PLEASE SEE SD NOTE WHICH IS
 ADDED TO PLANS.
 PLEASE SEE IF THE CIRCUITING IS DONE AS
 NOTED, THEN ARC FAULT PROTECTION WILL BE
 REQUIRED FOR THOSE CIRCUITS ALSO.
 PLEASE KNOW, ALL SD'S ARE REQUIRED TO BE
 WIRED "INLINE".
 PLEASE INDICATE CIRCUITING FROM
 EXISTING.
  
 22) NOTE: PLEASE CLARIFY AND VERIFY
 WHERE THE CWP IS FOR THE GROUNDING
 ELECTRODE SYSTEM. PLEASE SEE
 250.50,250.52 ETC.
 PLEASE SHOW.
  
 23) NOTE: PLEASE SEE CONDUIT SIZES AS
 SHOWN AND CONDUCTORS AS SHOWN EXCEED THE
 MAXIMUM PIPE FILL AS SHOWN. PLEASE SEE
 MAX FIGURES IN TABLE CHAPTER 9.
 215.5,106.1.2, ETC
  
 24) NOTE: PLEASE SEE MAIN DISCONNECTS
 ARE MISSING THE SIZE AND OCP FOR EACH.
 240.4,310.16,230.70 ETC.
  
 25) NOTE: *** IMPORTANT**
 ONCE ALL REVIEWS ARE COMPLETE, PLANS ARE
 PICKED UP AND BEFORE RESUBMITTING PLANS.
 PLEASE COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. PLEASE DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS. ONLY ONE COPY
 OF THE OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED ALONG WITH NEW SETS FOR
 REFERENCE ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  
  
  
  
  
2006-07-21 00:00:00REVIEW TO CONTINUE. PLANS WILL GO INTO
 "F" STATUS.
 NOTES TO FOLLOW WHEN REVIEW IS COMPLETE.