Plan Review Notes
Plan Review Notes For Permit 06070499
Permit Number 06070499
Review Stop P
Sequence Number 3
Notes
Date Text
2006-10-02 00:00:00DENIED 3RD TIME
  
 THE FOLLOWING INFORMATION IS STILL
 REQUIRED FOR PLUMBING PLAN REVIEW:
  
 1. PER FBC-2004 PLUMBING, SECTION
 802.2.1 AIR GAP:THE AIR GAP BETWEEN
 THE INDIRECT WASTE AND THE FLOOD RIM OF
 THE WATSTE RECEPTOR SHALL BE A MINIMUM
 OF TWICE THE EFFECTIVE OPENING OF THE
 INDIRECT WASTE PIPE.
 NOTE: PLEASE CORRECT SHEET SP-1.07 POOL
 WASTE LINE DETAIL FROM A THREE INCH AIR
 GAP TO A SIX INCH AIR GAP FOR THE
 RESUBMITTAL.
 2. THE RESUBMITTED PRINTS ON SHEETS
 SP-1.07 AND SP-2.03 NEED TO HAVE A NEW
 REVISION DATE FOR THE NEW RESUBMITTED
 DETAILS INDICATING THE NEW REVISED POOL
 AND SPA WASTE LINE DETAILS.
 3. THE RESUBMITTED PRINTS NEED TO BE
 CORRELATED SO THAT THE NEW POOL AND SPA
 WASTE LINE DETAILS ARE IN ALL THREE
 RESUBMITTED SETS OF PRINTS.
 NOTE: A) REVISED SHEET SP-1.07 IS
 MISSING ON ONE OF THE THREE RESUBMITTED
 SETS.
 B) REVISED SHEET SP-2.03 IS
 MISSING ON TWO OF THE THREE RESUBMITTED
 SETS.
 4. PLEASE DELETE THE POOL AND SPA WASTE
 DETAILS THAT HAVE BEEN CROSSED OUT IN
 RED INK AND ARE NOT CODE COMPLIANT ON
 SHEETS SP-2.03 AND SP-2.04 AND ONLY
 RESUBMIT THE NEW POOL AND SPA WASTE
 DETAILS.
 5. SEE ATTACHED NOTICE FLORIDA STATUTE
 553.80(2)(B) REGUARDING FOUR (4) TIMES
 THE FEE.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  