Plan Review Notes
Plan Review Notes For Permit 06070499
Permit Number 06070499
Review Stop P
Sequence Number 2
Notes
Date Text
2006-09-18 00:00:00******DENIED 2ND TIME******
 REFERENCE: FBC-2004 SEC. 424.1 PUBLIC
 SWIMMING POOLS.
 FBC-2004 CHAPTER 1
 FBC-2004 PLUMBING
  
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLUMBING PLAN REVIEW:
  
 1. THE POOL WASTE LINE AIR GAP DETAIL
 INDICATED ON SHEETS SP-1.07 AND SP-2.04
 ARE UNACCEPTABLE. A MINIMUM AIR GAP OF
 6" IS REQUIRED FOR A 3" WASTE PIPE PER
 FBC-2004 PLUMBING SECTION 802.2.1.
 PLEASE NOTE THE DEFINITION OF AIR GAP.
 AIR GAP (DRAINAGE SYSTEM)- THE
 UNOBSTRUCTED VERTICAL DISTANCE THROUGH
 THE FREE ATMOSPHERE BETWEEN THE OUTLET
 OF THE WASTE PIPE AND THE FLOOD LEVEL
 RIM OF THE RECEPTACLE INTO WHICH THE
 WASTE PIPE IS DISCHARGING.
 NOTE: PLEASE SEE THE CORRECTED DRAWING
 IN RED ON SHEET SP-1.07 FOR REFERENCE
 FOR RESUBMITTAL.
 2. NOTE: THIS IS A THRESHOLD PROJECT, A
 MINIMUM OF THREE COPIES REQUIRED FOR
 REVIEW AND STAMPING PER FBC-2004 CHAPTER
 1 SECTION 106.1 AND SECTION 109.3.6.
  
 **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN
 RESUBMITTING, PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721