| 2006-09-18 00:00:00 | ******DENIED 2ND TIME****** |
| | REFERENCE: FBC-2004 SEC. 424.1 PUBLIC |
| | SWIMMING POOLS. |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 PLUMBING |
| | |
| | |
| | THE FOLLOWING INFORMATION IS REQUIRED |
| | FOR PLUMBING PLAN REVIEW: |
| | |
| | 1. THE POOL WASTE LINE AIR GAP DETAIL |
| | INDICATED ON SHEETS SP-1.07 AND SP-2.04 |
| | ARE UNACCEPTABLE. A MINIMUM AIR GAP OF |
| | 6" IS REQUIRED FOR A 3" WASTE PIPE PER |
| | FBC-2004 PLUMBING SECTION 802.2.1. |
| | PLEASE NOTE THE DEFINITION OF AIR GAP. |
| | AIR GAP (DRAINAGE SYSTEM)- THE |
| | UNOBSTRUCTED VERTICAL DISTANCE THROUGH |
| | THE FREE ATMOSPHERE BETWEEN THE OUTLET |
| | OF THE WASTE PIPE AND THE FLOOD LEVEL |
| | RIM OF THE RECEPTACLE INTO WHICH THE |
| | WASTE PIPE IS DISCHARGING. |
| | NOTE: PLEASE SEE THE CORRECTED DRAWING |
| | IN RED ON SHEET SP-1.07 FOR REFERENCE |
| | FOR RESUBMITTAL. |
| | 2. NOTE: THIS IS A THRESHOLD PROJECT, A |
| | MINIMUM OF THREE COPIES REQUIRED FOR |
| | REVIEW AND STAMPING PER FBC-2004 CHAPTER |
| | 1 SECTION 106.1 AND SECTION 109.3.6. |
| | |
| | **IN ORDER TO EXPIDITE PLAN REVIEW: WHEN |
| | RESUBMITTING, PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| | IN RED INK FOR REFERENCE FOR |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |