| Plan Review Notes For Permit 06070499 |
| Permit Number |
06070499 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-08-10 00:00:00 | DENIED | | | | | | 1)13-412.1.ABC.2.6 SWIMMING POOL AND | | | SPA TEMPERATURE CONTROLS. | | | | | | 13-412.1.ABC.2.6.1 TIME SWITCHES. | | | TIME SWITCHES SHALL BE INSTALLED ON | | | SWIMMING POOL HEATERS AND PUMPS. | | | | | | 2) POOL COVERS | | | 13-412.1.ABC.2.6.2 POOL COVERS . | | | HEATED POOLS SHALL BE EQUIPPED WITH A | | | VAPOR RETARDANT POOL COVER ON OR AT THE | | | WATER SURFACE. POOLS HEATED TO MORE THAN | | | 90?F (32?C) SHALL HAVE A POOL COVER WITH | | | A MINIMUM INSULATION VALUE OF R -12. | | | | | | 3) 13-412.1.ABC.2.6.3 POOL HEATERS. | | | POOL HEATERS SHALL BE EQUIPPED WITH A | | | READILY ACCESSIBLE ON-OFF SWITCH TO | | | ALLOW SHUTTING OFF THE HEATER WITHOUT | | | ADJUSTING THE THERMOSTAT SETTING. POOL | | | HEATERS FIRED BY NATURAL GAS SHALL NOT | | | HAVE CONTINUOUSLY BURNING PILOT LIGHTS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | |
|