2006-07-19 00:00:00***DENIED***
  
 1) PLEASE SEE ELECTRICAL REVIEW COMMENT
 REGARDING 'EXISTING' SMOKE DETECTORS.
 PLEASE INDICATE IF THIS WILL BE NEW
 INSTALLATION.
  
 2) THE SECOND BEDROOM SEEMS TO SHOW AN
 EXISTING SPRINKLER HEAD IN THE SAME AREA
 AS A SIDEWALL TYPE THAT WOULD BE
 OBSTRUCTED BY A SOFFIT. A MINIMUM OF 18"
 SHALL BE MAINTAINED BENEATH SPRINKLER
 HEADS.
  
 3) SEPARATE SHOP DRAWINGS AND PERMIT
 REQUIRED FOR FIRE SPRINKLER REMODEL.
  
 4) THE SECOND BEDROOM DOES NOT SHOW A
 SPEAKER. PLEASE EXPLAIN.
  
  
 MIKE WENNERGREN, CAPTAIN/WPBFR
 FIRE PLAN REVIEW (561) 805-6722