Plan Review Notes
Plan Review Notes For Permit 06070486
Permit Number 06070486
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-18 00:00:00****** UNSAT ********
  
 1) NOTE: PLEASE INDICATE CIRCUITING ON
 PLANS FOR NEW RECEPTS, SD, LTS ETC
 PLEASE SEE INDICATE CONTROL FOR ALL
 ITEMS(LTS).
 PLEASE SEE MISSING LIGHTING AND CONTROL
 FOR BEDRM.
 PLEASE CORRELATE WITH A PANEL SCHEDULE
 TO BE SUBMITTED.408.4, 210.12B, 210.70
  
 2) NOTE: PLEASE SEE SD'S ARE NOTED AS
 BEING EXISTING, HOWEVER EXISTING PLANS
 DO NOT INDICATE SD'S AND IT IS THE
 KNOWLEDGE OF THIS OFFICE SINCE THESE
 RMS/AREAS WERE NOT BUILT OUT UNDER BASE
 BLDG, THAT SD'S DID NOT MEETING REQUIRED
 SPACES AS SPACE WAS OPEN.
 PLEASE SEE NFPA-72 11.5.1.1, AND PLEASE
 SEE NEC 210.12B AS ALL ARE REQUIRED TO
 BE ARC FAULT PROTECTED, WIRED INLINE
 ETC.
  
 3) NOTE: PLEASE CLEARLY SPECIFY ALL
 EXISTING AND ALL NEW.
 106.1.2
  
 4) NOTE: PLEASE KNOW, AS FOR EELCTRICAL
 SCOPE OF WORK, THE PLANS DO NOT NEEDS TO
 BE SIGNED,AND SEALED BY AN ARCHITECT OR
 ENGINEER, HOWEVER PLANS ARE REQUIRED TO
 CONTAIN THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR PLANS AND
 SAID DESIGN.
 PLEASE SEE ANY POSSIBLE COMMENTS FROM
 OTHER TRADES WHICH MAY REQUIRE PLANS TO
 BE DONE BY AN ARCHITECT.
 FBC 106.1.2
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  