| 2006-07-18 00:00:00 | ****** UNSAT ******** |
| | |
| | 1) NOTE: PLEASE INDICATE CIRCUITING ON |
| | PLANS FOR NEW RECEPTS, SD, LTS ETC |
| | PLEASE SEE INDICATE CONTROL FOR ALL |
| | ITEMS(LTS). |
| | PLEASE SEE MISSING LIGHTING AND CONTROL |
| | FOR BEDRM. |
| | PLEASE CORRELATE WITH A PANEL SCHEDULE |
| | TO BE SUBMITTED.408.4, 210.12B, 210.70 |
| | |
| | 2) NOTE: PLEASE SEE SD'S ARE NOTED AS |
| | BEING EXISTING, HOWEVER EXISTING PLANS |
| | DO NOT INDICATE SD'S AND IT IS THE |
| | KNOWLEDGE OF THIS OFFICE SINCE THESE |
| | RMS/AREAS WERE NOT BUILT OUT UNDER BASE |
| | BLDG, THAT SD'S DID NOT MEETING REQUIRED |
| | SPACES AS SPACE WAS OPEN. |
| | PLEASE SEE NFPA-72 11.5.1.1, AND PLEASE |
| | SEE NEC 210.12B AS ALL ARE REQUIRED TO |
| | BE ARC FAULT PROTECTED, WIRED INLINE |
| | ETC. |
| | |
| | 3) NOTE: PLEASE CLEARLY SPECIFY ALL |
| | EXISTING AND ALL NEW. |
| | 106.1.2 |
| | |
| | 4) NOTE: PLEASE KNOW, AS FOR EELCTRICAL |
| | SCOPE OF WORK, THE PLANS DO NOT NEEDS TO |
| | BE SIGNED,AND SEALED BY AN ARCHITECT OR |
| | ENGINEER, HOWEVER PLANS ARE REQUIRED TO |
| | CONTAIN THE PRINTED NAME AND SIGNATURE |
| | OF THE PERSON RESPONSIBLE FOR PLANS AND |
| | SAID DESIGN. |
| | PLEASE SEE ANY POSSIBLE COMMENTS FROM |
| | OTHER TRADES WHICH MAY REQUIRE PLANS TO |
| | BE DONE BY AN ARCHITECT. |
| | FBC 106.1.2 |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |