| Plan Review Notes For Permit 06070462 |
| Permit Number |
06070462 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2006-08-10 00:00:00 | | | | PROVISO | | | | | | PLEASE RESUBMIT SHOWING ACTUAL | | | CONDITIONS PRIOR TO CALLING ROUGH | | | ELECTRICAL INSPECTION. | | | THE REVIEWED PLAN MUST BE ON THE JOB | | | SITE AT TIME OF INSPECTION. ALLOW ONE | | | WEEK (PER TRADE) FOR PLAN REVIEW. | | | CORRECT THE FOLLOWING | | | | | | | | | 1} THE FEEDERS FROM THE METER/MAIN MUST | | | INCLUDE THE EQUIPMENT GROUND REQUIRED BY | | | 250.110 AND SIZED PER 250.122. TO ALL | | | PANELS. | | | | | | 2} THE RISER SHOWS A DISCONNECT PER | | | 225.31 BUT LOCATION NOT SHOWN ON THE | | | PLAN AT THE CABANA, WHERE IT IS REQUIRED | | | PER 225.32. | | | | | | 3} THE CABANA KITCHEN COUNTERTOP IS | | | MISSING A RECEPTACLE PER 210.52(C)(1). | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | | | | | | | |
|