Plan Review Notes
Plan Review Notes For Permit 06070462
Permit Number 06070462
Review Stop E
Sequence Number 2
Notes
Date Text
2006-08-10 00:00:00 
 PROVISO
  
 PLEASE RESUBMIT SHOWING ACTUAL
 CONDITIONS PRIOR TO CALLING ROUGH
 ELECTRICAL INSPECTION.
 THE REVIEWED PLAN MUST BE ON THE JOB
 SITE AT TIME OF INSPECTION. ALLOW ONE
 WEEK (PER TRADE) FOR PLAN REVIEW.
 CORRECT THE FOLLOWING
  
  
 1} THE FEEDERS FROM THE METER/MAIN MUST
 INCLUDE THE EQUIPMENT GROUND REQUIRED BY
 250.110 AND SIZED PER 250.122. TO ALL
 PANELS.
  
 2} THE RISER SHOWS A DISCONNECT PER
 225.31 BUT LOCATION NOT SHOWN ON THE
 PLAN AT THE CABANA, WHERE IT IS REQUIRED
 PER 225.32.
  
 3} THE CABANA KITCHEN COUNTERTOP IS
 MISSING A RECEPTACLE PER 210.52(C)(1).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
  
  
  