| 2006-07-13 00:00:00 | |
| | |
| | |
| | NONCOMPLIANT |
| | |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE FEEDERS FROM THE METER/MAIN MUST |
| | INCLUDE THE EQUIPMENT GROUND REQUIRED BY |
| | 250.110 AND SIZED PER 250.122. |
| | |
| | 2} THE #8 NEUTRAL FEEDING PANEL "D" |
| | APPEARS TOO SMALL FOR THE UNBALANCE. |
| | PROVIDE A CALCULATION PER 220.22. |
| | |
| | |
| | 3} CIRCUITS 10&12, PANEL "B" HAVE AN OCP |
| | OF 35 AMPS ON #10 WIRE AND DO NOT COMPLY |
| | WITH 310.16 RE: 240.4(D). |
| | |
| | 4} CIRCUITS 5&7 PANEL "D", SAME COMMENT |
| | AS ABOVE (NOTE #3). |
| | |
| | 5} PLEASE SEE THE NUMBER AIR HANDLERS |
| | AND COMPRESSERS LISTED IN THE PANEL |
| | SCHEDULES DO NOT CORRELATE TO THE ACTUAL |
| | SYSTEMS. |
| | |
| | 6} PLEASE SEE THE NOTE ON ALL "E" SHEETS |
| | REGARDING SMOKE DETECTORS, SHOULD |
| | REFERENCE 313.1 FBC (RESIDENTIAL), NOT |
| | 905.2. |
| | |
| | 7} PLEASE SEE THE CABANA NEEDS ADDED |
| | RECEPTACLES TO COMPLY WITH 210.52(A) |
| | SPACING REQUIREMENTS, AT THE ENTRY. |
| | |
| | THE RECEPTACLES WITHIN 6' OF THE WET BAR |
| | IN THE CABANA MUST BE GFI PROTECTED PER |
| | 210.8(A)(7}. |
| | |
| | 8} PLEASE SHOW THE "POOL PANEL" LISTED |
| | IN PANEL "D". LOCATE SAME ON PLAN AND ON |
| | THE RISER. ALSO PROVIDE A PANEL SCHEDULE |
| | FOR SAME. 408.4 NEC AND 106.3.5.4 FBC. |
| | |
| | 9} PLEASE INDICATE THE FEEDER SIZES FOR |
| | PANEL "A". |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | WILLIAM R. TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561) 805-6718 |
| | |
| | |
| | |
| | |
| | |