Plan Review Notes
Plan Review Notes For Permit 06070462
Permit Number 06070462
Review Stop E
Sequence Number 1
Notes
Date Text
2006-07-13 00:00:00 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDERS FROM THE METER/MAIN MUST
 INCLUDE THE EQUIPMENT GROUND REQUIRED BY
 250.110 AND SIZED PER 250.122.
  
 2} THE #8 NEUTRAL FEEDING PANEL "D"
 APPEARS TOO SMALL FOR THE UNBALANCE.
 PROVIDE A CALCULATION PER 220.22.
  
  
 3} CIRCUITS 10&12, PANEL "B" HAVE AN OCP
 OF 35 AMPS ON #10 WIRE AND DO NOT COMPLY
 WITH 310.16 RE: 240.4(D).
  
 4} CIRCUITS 5&7 PANEL "D", SAME COMMENT
 AS ABOVE (NOTE #3).
  
 5} PLEASE SEE THE NUMBER AIR HANDLERS
 AND COMPRESSERS LISTED IN THE PANEL
 SCHEDULES DO NOT CORRELATE TO THE ACTUAL
 SYSTEMS.
  
 6} PLEASE SEE THE NOTE ON ALL "E" SHEETS
 REGARDING SMOKE DETECTORS, SHOULD
 REFERENCE 313.1 FBC (RESIDENTIAL), NOT
 905.2.
  
 7} PLEASE SEE THE CABANA NEEDS ADDED
 RECEPTACLES TO COMPLY WITH 210.52(A)
 SPACING REQUIREMENTS, AT THE ENTRY.
  
 THE RECEPTACLES WITHIN 6' OF THE WET BAR
 IN THE CABANA MUST BE GFI PROTECTED PER
 210.8(A)(7}.
  
 8} PLEASE SHOW THE "POOL PANEL" LISTED
 IN PANEL "D". LOCATE SAME ON PLAN AND ON
 THE RISER. ALSO PROVIDE A PANEL SCHEDULE
 FOR SAME. 408.4 NEC AND 106.3.5.4 FBC.
  
 9} PLEASE INDICATE THE FEEDER SIZES FOR
 PANEL "A".
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561) 805-6718
  
  
  
  
  