| Date |
Text |
| 2006-07-21 00:00:00 | DENIED |
| | |
| | |
| | 1.SUBMIT TWO COPIES OF ENERGY CALCS |
| | PER 2004 FBC. |
| | |
| | 2.PRODUCT APPROVALS REQUIRED FOR |
| | STRAPS TIE-DOWNS AND LINTELS. |
| | |
| | 3.ALL PRODUCT APPROVALS SUBMITTED WITH |
| | QUALITY ASSURANCE SHALL HAVE THE |
| | FOLLOWING STATE APPROVAL ATTACHED. |
| | |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A STATE PRODUCT APPROVAL |
| | SHEETS THAT LISTS THE PRODUCT IDENTITY |
| | NUMBER FROM THE STATE. IF THE PRODUCT |
| | DOES NOT HAVE STATEWIDE APPROVAL, SUBMIT |
| | AN APPLICATION FOR LOCAL PRODUCT |
| | APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. |
| | WWW.FLORIDABUILDING.ORG |
| | |
| | 4.THOSE PRODUCT APPROVALS WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL.WPB |
| | AMENDMENT TO FBC 106.3.3. |
| | |
| | 5.SUBMIT TWO SETS OF TRUSS DRAWINGS |
| | FOR REVIEW PRIOR TO INSTALLATION. PER |
| | 2004 FBC R-802.10.1 |
| | |
| | 6.R401.3 DRAINAGE. |
| | SURFACE DRAINAGE SHALL BE DIVERTED TO A |
| | STORM SEWER CONVEYANCE OR OTHER APPROVED |
| | POINT OF COLLECTION SO AS TO NOT CREATE |
| | A HAZARD. LOTS SHALL BE GRADED SO AS TO |
| | DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| | WALLS. THE GRADE AWAY FROM FOUNDATION |
| | WALLS SHALL FALL A MINIMUM OF 6 INCHES |
| | WITHIN THE FIRST 10 FEET. |
| | |
| | 7.R302.1 EXTERIOR WALLS.PROJECTIONS |
| | SHALL NOT EXTEND TO A POINT CLOSER THAN |
| | 4 FEET FROM AN ADJACENT PROJECTION OR |
| | WALL. |
| | PROJECTIONS EXTENDING INTO THE 6-FOOT |
| | SEPARATION DISTANCE SHALL HAVE NOT LESS |
| | THAN 1-HOUR FIRE-RESISTIVE CONSTRUCTION |
| | ON THE UNDERSIDE. THE ABOVE PROVISIONS |
| | SHALL NOT APPLY TO WALLS WHICH ARE |
| | PERPENDICULAR TO A LINE EXTENDING FROM |
| | THE POINT FROM WHICH THE SEPARATION |
| | DISTANCE HAS BEEN MEASURED RUNNING AND |
| | PARALLEL TO THE PROPERTY LINE. |
| | |
| | 8.SHOW WINDOW BUCKS OFFERING FULL |
| | SUPPORT OF THE FRAME. PER FBC R 613.6.2 |
| | |
| | 9.CERTAINTEED ROOFING UNDERLAYMENT, |
| | ONLY THE WINTER GUARD HT IS PERMITTED |
| | UNDER METAL ROOFING. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. SUBMIT ONE COPY OF |
| | OLD PAGES FOR REFERENCE . A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF |
| | THE REVISION MADE, IDENTIFYING THE SHEET |
| | OR SPECIFICATION PAGE WHERE THE CHANGES |
| | CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | ART LANGE |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | BUILDING PLANS EXAMINER |
| | 561-805-6672 |
| | |