Plan Review Notes
Plan Review Notes For Permit 06070461
Permit Number 06070461
Review Stop E
Sequence Number 3
Notes
Date Text
2006-10-14 17:15:28**** UNSAT**
  
 1) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW
 AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE.
 SOME CIRCUITS FOR CODE COMPLIANCE CAN NOT BE VERIFIED
 AT THIS TIME.
 FBC ADMIN SECT 106.3.5.1.2, NEC 240.4, 408.4 310.16
 ETC
  
 2) NOTE: PLEASE SEE 210.52C1-5 FOR KITCHEN GFI RECEPTS
 REQUIRED , LOCATIONS ETC. PLEASE SEE 210.8A6 FOR ALL
 RECEPTS SERVING KITCHEN COUNTER SPACE SHALL BE GFI .
  
 3) NOTE: PLEASE CORRELATE ALL ELECTRICAL CIRCUITS ON
 PANEL SCHEDULE AND BE SURE DEVICES ARE SHOWN ON PLANS.
 DISPOSAL? WATER HEATER?
 FBC ADMIN SECT. 106.1.2
  
 4) NOTE: PLEASE VERIFY THE EXISTING RISER AS SHOWN.
 THIS REVIEWER WAS JUST ON SITE AT THIS BUIDLING FOR
 OTHER UNIT AND METER ROOM SHOWED A "TYPICAL" BREAKER
 SIZE AND FEEDERS, FOR EACH OF THE PH UNITS, HOWEVER
 THESE WERE NOT 200A MCB AND NOT 200A FEEDERS. THE
 CONDUITS WERE NOT LARGE ENOUGH FOR 200A FEEDS WHEN
 BUILT.
 ** PLEASE KNOW, IF SHOWN THIS WAY ON PLANS, THIS WILL
 BE INSPECTED AND EXPECTED TO SHOW THIS. IF NOT
 ACCURATE, THEN PLANS WILL BE REQUIRED TO BE REVISED ONE
 AGAIN. IT MAY BE OF INTEREST FOR EVERYONE INVOLVED THIS
 BE VERIFIED AT THIS TIME.
 310.16, 240.4 ETC. PLEASE SPECIFY TYPE OF CONDUCTOR.
 (ALUM/COPPER). ETC
  
 5) NOTE:: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR MIN
 VA FOR EACH OF THE SMALL APPLIANCE CIRCUITS ALONG WITH
 AREAS OF THE LIKE. PLEASE SEE ONE KITCHEN CIRCUIT BEING
 SHOWN WITH NO LOAD. PLEASE SEE DINING ROOM/AREA FOR
 EXISITING.
  
 6) NOTE: PLEASE SEE BATH GFI CIRCUIT IS BEING SHOWN
 WITH 7.2 KW ON CIRCUIT. THIS APPEARS TO BE A MISPRINT
 PERHAPS FOR GEN LTS/RECEPT LOAD WHICH SHOULD BE SHOWN
 ON PANEL LOAD CALCULATIONS.
 220.31,
  
 7) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SD' S AND
 SA'S. PLEASE VERIFY IF THESE ARE INDEED SMOKE DETECTORS
 OR ARE THEY SMOKE ALARMS?
 THIS IS ONLY NOTED, AS IF THEY ARE SD'S THEN PLEASE
 INDICATE THE "SOUNDING DEVICES".
 2002 -72.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved