| 2006-10-14 17:15:28 | **** UNSAT** |
| | |
| | 1) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW |
| | AND CORRELATE WITH THE SUBMITTED PANEL SCHEDULE. |
| | SOME CIRCUITS FOR CODE COMPLIANCE CAN NOT BE VERIFIED |
| | AT THIS TIME. |
| | FBC ADMIN SECT 106.3.5.1.2, NEC 240.4, 408.4 310.16 |
| | ETC |
| | |
| | 2) NOTE: PLEASE SEE 210.52C1-5 FOR KITCHEN GFI RECEPTS |
| | REQUIRED , LOCATIONS ETC. PLEASE SEE 210.8A6 FOR ALL |
| | RECEPTS SERVING KITCHEN COUNTER SPACE SHALL BE GFI . |
| | |
| | 3) NOTE: PLEASE CORRELATE ALL ELECTRICAL CIRCUITS ON |
| | PANEL SCHEDULE AND BE SURE DEVICES ARE SHOWN ON PLANS. |
| | DISPOSAL? WATER HEATER? |
| | FBC ADMIN SECT. 106.1.2 |
| | |
| | 4) NOTE: PLEASE VERIFY THE EXISTING RISER AS SHOWN. |
| | THIS REVIEWER WAS JUST ON SITE AT THIS BUIDLING FOR |
| | OTHER UNIT AND METER ROOM SHOWED A "TYPICAL" BREAKER |
| | SIZE AND FEEDERS, FOR EACH OF THE PH UNITS, HOWEVER |
| | THESE WERE NOT 200A MCB AND NOT 200A FEEDERS. THE |
| | CONDUITS WERE NOT LARGE ENOUGH FOR 200A FEEDS WHEN |
| | BUILT. |
| | ** PLEASE KNOW, IF SHOWN THIS WAY ON PLANS, THIS WILL |
| | BE INSPECTED AND EXPECTED TO SHOW THIS. IF NOT |
| | ACCURATE, THEN PLANS WILL BE REQUIRED TO BE REVISED ONE |
| | AGAIN. IT MAY BE OF INTEREST FOR EVERYONE INVOLVED THIS |
| | BE VERIFIED AT THIS TIME. |
| | 310.16, 240.4 ETC. PLEASE SPECIFY TYPE OF CONDUCTOR. |
| | (ALUM/COPPER). ETC |
| | |
| | 5) NOTE:: PLEASE SEE 210.52B1, 210.11C1, 220.16 FOR MIN |
| | VA FOR EACH OF THE SMALL APPLIANCE CIRCUITS ALONG WITH |
| | AREAS OF THE LIKE. PLEASE SEE ONE KITCHEN CIRCUIT BEING |
| | SHOWN WITH NO LOAD. PLEASE SEE DINING ROOM/AREA FOR |
| | EXISITING. |
| | |
| | 6) NOTE: PLEASE SEE BATH GFI CIRCUIT IS BEING SHOWN |
| | WITH 7.2 KW ON CIRCUIT. THIS APPEARS TO BE A MISPRINT |
| | PERHAPS FOR GEN LTS/RECEPT LOAD WHICH SHOULD BE SHOWN |
| | ON PANEL LOAD CALCULATIONS. |
| | 220.31, |
| | |
| | 7) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SD' S AND |
| | SA'S. PLEASE VERIFY IF THESE ARE INDEED SMOKE DETECTORS |
| | OR ARE THEY SMOKE ALARMS? |
| | THIS IS ONLY NOTED, AS IF THEY ARE SD'S THEN PLEASE |
| | INDICATE THE "SOUNDING DEVICES". |
| | 2002 -72. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |