Plan Review Notes
Plan Review Notes For Permit 06070459
Permit Number 06070459
Review Stop E
Sequence Number 5
Notes
Date Text
2006-10-25 20:37:29***UNSAT ***
  
 1) NOTE: PLEASE SEE NO GFI PROTECTION SHOWN FOR NEW
 WHIRLPOOL EQUIPMENT. 680.71.
  
 2) NOTE: PLEASE KNOW ON A RECENT INSPECTION AT THE
 BUILDING LOCATION IT WAS DISCOVERED ALL OF THE FEEDERS
 AND MAINS FEEDING THE 200A PANELS WHICH WERE SEEN BY
 THIS REVIEWER AND FELLOW INSPECTOR WERE INDEED 150A
 MAINS IN MAIN ELECTRICAL ROOMS WITH FEEDERS RATED ONLY
 AT 150A'S.
  
 PLEASE VERFIY AND SHOW THIS INFORMATION ON PLANS AND
 RISER AT THIS TIME. IF THESE ARE ONLY RATED AT 150A'S,
 PLEASE REMOVE SOME LOADS OR RE-PULL FEEDERS. SUPPLY
 CONDUCTOR TYOE AND CONDUIT SIZE AS CONDUIT IS NOT 2".
 215.5, 240.4,310.16 ETC.
 PLEASE ALSO KNOW 310.15B6 MAY NOT BE USED.
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  