| 2006-10-25 20:37:29 | ***UNSAT *** | | | | | | 1) NOTE: PLEASE SEE NO GFI PROTECTION SHOWN FOR NEW | | | WHIRLPOOL EQUIPMENT. 680.71. | | | | | | 2) NOTE: PLEASE KNOW ON A RECENT INSPECTION AT THE | | | BUILDING LOCATION IT WAS DISCOVERED ALL OF THE FEEDERS | | | AND MAINS FEEDING THE 200A PANELS WHICH WERE SEEN BY | | | THIS REVIEWER AND FELLOW INSPECTOR WERE INDEED 150A | | | MAINS IN MAIN ELECTRICAL ROOMS WITH FEEDERS RATED ONLY | | | AT 150A'S. | | | | | | PLEASE VERFIY AND SHOW THIS INFORMATION ON PLANS AND | | | RISER AT THIS TIME. IF THESE ARE ONLY RATED AT 150A'S, | | | PLEASE REMOVE SOME LOADS OR RE-PULL FEEDERS. SUPPLY | | | CONDUCTOR TYOE AND CONDUIT SIZE AS CONDUIT IS NOT 2". | | | 215.5, 240.4,310.16 ETC. | | | PLEASE ALSO KNOW 310.15B6 MAY NOT BE USED. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|