| 2006-07-18 00:00:00 | ********* UNSAT ********** |
| | |
| | 1) NOTE: PLEASE INDICATE ALL ROOM AND |
| | AREA DESIGNATIONS ON PLANS. |
| | SOME ITEMS FOR CODE COMPLIANCE CAN NOT |
| | BE VERIFIED AT THIS TIME. |
| | DINING? BEDRMS ETC |
| | 210.52B1, 210.11C1, ETC |
| | |
| | 2) NOTE: PLEASE INDICATE ALL CIRCUITING |
| | ON PLANS AND CORRELATE WITH PANEL |
| | SCHEDULE TO BE SUBMITTED. PLEASE SEE |
| | PANEL SCHEDULE/LOAD CALCS IS OK. PLEASE |
| | KNOW,UNABLE TO VERIFY THE REQUIRED |
| | DEDICATED CIRCUITS FOR DINING, BATHS |
| | ETC? |
| | 210.52B1,210.11C1,408.4 ETC |
| | |
| | 3) NOTE: PLEASE SUBMIT MANUFACTURES |
| | SPECS/CUT SHEETS FOR THE TL WH. PLEASE |
| | SEE LOADS ARE SHOWN AT 24KW, AND YET THE |
| | OCP IS SHOWN AT 60A'S? PLEASE SEE MIN |
| | BRANCH CIRCUIT SIZING ETC. |
| | PLEASE SEE 422.30, 422.17, |
| | |
| | 4) NOTE: PLEASE VERIFY OCP SHOWN FOR |
| | 11KW OVEN AS THE LOAD FAR EXCEEDS THE |
| | RATING OF BRANCH CIRCUIT. |
| | PLEASE VERIFY 240.4,310.16, ETC |
| | |
| | 5) NOTE: PLEASE SEE SD WILL BE REQUIRED |
| | IN ALL SLEEPING RMS OR ADAPTABLE |
| | SLEEPING RMS. THESE RMS CONTAIN A CLOSET |
| | OR BATHRM, THEN THEY ARE CONSIDERED |
| | SLEEPING RMS. |
| | PLEASE SEE NFPA-72 2002 11.5.1.1,11.8.3 |
| | |
| | 6) NOTE: PLEASE BE SURE PLANS REFLECT |
| | THE FOLLOWING CODES. |
| | NFPA-70 2002, NFPA-72 2002. |
| | |
| | 7) NOTE: PLEASE CLARIFY THE RECEPTS NOW |
| | SHOWN IN THE CLOSET. PLEASE KNOW THAT |
| | RECEPTS IN SPACES WHICH CLOSE TO EASILY |
| | IGNITIBLE MATERIALS SHALL NOT BE USED |
| | FOR "PLUG-IN" TYPE TRANSFORMER ETC. |
| | PLEASE SEE 240.24,110.26 ETC |
| | THIS IS AND HAS BEEN A DIRECT FIRE |
| | HAZARD IN THIS AREA. |
| | |
| | 8 )NOTE: PLEASE SEE 220.3B4. |
| | PLEASE SHOW ALL RECESSED LTS BASED ON |
| | MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT |
| | BE FIGURED IN W/ 3W/PER SQ FT. |
| | PLEASE PROVIDE FIXTURE INFORMATION ON |
| | LEGEND. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |