| Date |
Text |
| 2007-05-31 09:47:40 | DENIED... |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE FLORIDA |
| | STATUTES |
| | |
| | ******FROM 1ST REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. ALL ARCHITECTURAL SHEETS. THE CERTIFICATE OF |
| | AUTHORIZATION, (BUSINESS NUMBER), IS INDICATED AS |
| | DELINQUENT PER DBPR WEBSITE. THIS SHALL BE TAKEN CARE |
| | OF PRIOR TO RESUBMITTING FOR REVIEW. FAC 61G1-16.004(1) |
| | & FS 481.219. |
| | ****NO RESPONSE, NOT ADDRESSED |
| | |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SHT A-7 SHOW COMPLIANCE WITH THE FOLLOWING: |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | |
| | 6. SHT A-9 DETAIL #2 SHOW COMPLIANCE WITH THE |
| | FOLLOWING: |
| | A. OK |
| | B. OK |
| | C. OK |
| | |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | |
| | ******FROM 2ND REVIEW: |
| | |
| | 1) SHT P-2,NOTE #16 REFERENCE TO A/C CONDENSATE |
| | DRAIN. SHT A/C-2 ROOF TOP UNIT DETAIL, IS NOT SHOWING |
| | DISPOSAL OF A/C CONDENSATE. PLEASE CLARIFY. |
| | ****RESPONSE NOTED, BUT THE CONDENSATE SHALL NOT DRAIN |
| | ONTO THE ROOF. THE CONDENSATE SHALL BE PIPED TO THE |
| | ROOF DRAINS AND DRAIN INDIRECTLY OVER THE DRAINS. |
| | PLEASE SUBMIT A DETAIL SHOWING THE PIPE SUPPORTS |
| | INDICATING THE SPACING PER TABLE 308.5. INDICATE HOW |
| | THE SUPPORTS WILL BE ATTACHED TO THE ROOF SHOWING |
| | COMPLIANCE WITH 140 MPH WINDLOAD REQUIREMENTS. SHOW THE |
| | ROUTING FOR THE PIPE FOR EACH A/C UNIT ON SHT P-1 OR ON |
| | A ROOF PLAN SHOWING ALL ROOF DRAINS. SECTION 106.1.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |