Plan Review Notes
Plan Review Notes For Permit 06070451
Permit Number 06070451
Review Stop M
Sequence Number 3
Notes
Date Text
2007-04-26 12:09:30*** DENIED ***
 1) THE FIRM'S LICENSE FOR STEVEN L. COHEN AND
 ASSOCIATES, P.A. HAS EXPIRED ON 2-28-2005 AND IS NOW
 NULL AND VOID, PLEASE CORRECT.
  
 2) ENGINEERING DESIGN ASSOCIATES, INC. CERTIFICATE OF
 AUTHORIZATION EXPIRED 2-28-2007, PLEASE CORRECT.
  
 *** FAC 61G1-16.004 TITLE BLOCK.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER. (NULL AND VOID).
 (3) NAME OR IDENTIFICATION OF PROJECT. ("JOB ADDRESS"
 SEE CITY WPB AMEND. 106.1.1).
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 *** FAC 61G15-23.002 (2)A TITLE BLOCK ON EACH SHEET
 CONTAINING THE PRINTED NAME, ADDRESS, AND LICENSE
 NUMBER OF THE ENGINEER OR IF APPLICABLE, THE NAME AND
 LICENSE NUMBER OF THE ENGINEER, AND THE NAME, ADDRESS
 AND CERTIFICATE OF AUTHORIZATION NUMBER OF THE
 ENGINEERING BUSINESS WILL SATISFY THIS REQUIREMENT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.