| Date |
Text |
| 2007-04-22 13:28:04 | |
| | ******* UNSAT 3RD REVIEW ****** |
| | |
| | ** PLEASE SEE THAT THERE ARE STILL MANY ITEMS FROM |
| | PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN ADDRESSED FOR |
| | CODE COMPLIANCE. |
| | |
| | ** PLEASE SEE THE RESPONSE LETTER FROM THE DESIGNER |
| | ONLY RESPONDED TO NOTES 1-8 AND NEW NOTES FROM LAST |
| | REVIEW WERE NOT NOTED AND LETTER DID NOT CONTAIN ANY |
| | RESPONSE??A RESPONSE LETTER IS NOT REQUIRED HOWEVER |
| | WILL SOMETIMES HELP TO EXPLAIN ITEMS OR EXPEDITE THE |
| | REVIEW PROCESS. |
| | |
| | |
| | 1) NOTE:PLEASE SEE THE NOTE FOR THE VALUE FOR |
| | COMPLETE SCOPE OF WORK STILL REMAINS. RESPONSE FROM |
| | DESIGNER MENTIONS FOR CONTRACTOR TO ADDRESS HOWEVER NO |
| | CHANGES TO APPLIED VALUE HAS BEEN DONE. PLEASE KNOW |
| | THAT A VALUE WILL BE ASSESSED BY THIS OFFICE IF AN |
| | APPROPRIATE VALUE IS NOT INDICATED. |
| | AS STATED ON PREVIOUS REVIEW THE VALUE SHALL INCLUDE |
| | ALL LABOR AND MATERIALS, INCLUDING ALL EQUIPMENT, A/C |
| | EQUIPMENT, ELECTRICAL EQUIPMENT, LIGHTING FIXTURES ETC. |
| | PLEASE KNOW A VALUE WILL BE ASSESSED USING THE FBC |
| | TABLES FOR INTERIOR BUILD OUT OF THE SQ FT AND WILL BE |
| | SUBSTANTIALLY INCREASED IF AN APPROPRIATE VALUE IS NOT |
| | APPLIED. PLEASE SEE FS 553.79, 553.792, AND FS 489. |
| | ** THE VALUE OF THE ELECTRICAL EQUIPMENT ALONE IS |
| | HIGHER THAN THE APPLIED VALUE FOR THE COMPLETE SCOPE OF |
| | WORK AS APPLIED. |
| | *FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE |
| | CITY OF WEST PALM BEACH. |
| | |
| | 2) NOTE:PLEASE COORDINATE THE ELECTRICAL SERVICE ON |
| | THE BUILD OUT PLANS AS WELL AS THE ELECTRICAL PLANS FOR |
| | THE SHELL PERMITTED PLANS. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT |
| | CORRELATE. |
| | |
| | A) PLEASE SEE THE MAIN SWITCH IN TENANT SPACE |
| | ELECTRICAL ROOM IS STILL BEING SHOWN AS 600AMP WITH |
| | 400AMP OVER CURRENT PROTECTION YET THE RISER AND OTHER |
| | PLANS INDICATE THIS DISCONNECT AS BEING 600AMP WITH |
| | 600AMP OVER CURRENT PROTECTION. NOTED ON BOTH PREVIOUS |
| | REVIEWS, YET PLANS STILL SHOW THIS? |
| | |
| | B) PLEASE THE FEEDERS ARE STILL SHOWN AS OVER HEAD TO |
| | THE TENANT ELECTRICAL ROOM AND WELL AS BEING NOTED AS |
| | UNDERGROUND ON SHELL PLANS AND THESE PLANS. |
| | |
| | C) PLEASE SEE THE FEEDER CONDUITS ARE SHOWN AS 3INCH ON |
| | SOME SHEETS AND 4INCH ON OTHERS AND SHELL PLANS? |
| | |
| | D) PLEASE SEE THE FEEDERS NOW FROM THE MAIN ELECTRICAL |
| | ROOM HAVE BEEN CHANGED FROM THE PREVIOUS 600MCM DOWN TO |
| | 350MCM YET THE VOLTAGE DROP CALCULATIONS STILL INDICATE |
| | 600MCM. PLEASE SEE SHELL PLANS. |
| | 13-413.1ABC.1 AS NOTED ON PREVIOUS REVIEW FOR VOLTAGE |
| | DROP) |
| | |
| | E) PLEASE SEE THE ONE-LINE DIAGRAM ON THE TENANT BUILD |
| | OUT PLANS SHALL INDICATE THE OCP AND MAIN WHICH IS |
| | LOCATED IN THE MAIN SWITCH BOARD ON THE SHELL PLANS. |
| | 230.70, 230.71, 230.72. |
| | |
| | ** PLEASE COORDINATE ALL ELECTRICAL EQUIPMENT ON BOTH |
| | SETS OF PLANS UNDER EACH PERMIT AND ADJUST FOR THE CODE |
| | COMPLIANCE COMMENTS. |
| | |
| | 3) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS |
| | FOR CHAPTER 13 COMPLIANCE. |
| | PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES. |
| | PLEASE SEE MISSING SCHEDULING OF SYSTEM. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | NEW LIGHTING CONTROL PANEL. |
| | 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE |
| | VERIFIED AS SHOWN. |
| | SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE |
| | LISTING FROM A NRTL(NATION RECOGNIZED TESTING |
| | LABORATORY). |
| | PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND |
| | OCCUPANCY DEVICES. |
| | PLEASE SEE MANY ROOMS WHICH STILL ONLY INDICATE A *S* |
| | SWITCH FOR CONTROL OF LIGHTING. PLEASE SEE |
| | 13-415.1.ABC.1.2 FOR SPACE CONTROL. |
| | PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS |
| | BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL |
| | BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR |
| | SUBMITTED BACK FOR REVIEW. |
| | PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING |
| | WITH MANUAL CONTROL FOR LIGHTING WHICH IS NOT POSSIBLE |
| | WHEN AN AUTOMATED SYSTEM IS BEING INSTALLED AND |
| | REQUIRED. |
| | PLEASE CORRELATE THE FIXTURES ON PLANS WITH THAT OF THE |
| | FIXTURES ON ENERGY CALCULATIONS FOR THE TYPE, WATTAGE |
| | AND THE NUMBER OF FIXTURES ON PLANS AND IN |
| | CALCULATIONS. |
| | ** PLEASE SEE THAT THE EXACT SAME ENERGY CALCULATIONS |
| | WERE SUBMITTED BACK. |
| | PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW, |
| | THERE MAY BE SOME FUTURE COMMENTS. |
| | |
| | PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A |
| | WORST CASE SCENARIO. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| | 13-415.1.AB.1, |
| | 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1 |
| | PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC. |
| | |
| | |
| | 4) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF |
| | CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL |
| | INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL |
| | DEVICES. |
| | PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES |
| | SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE |
| | MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2, |
| | .3(4). |
| | THIS IS REQUIRED FOR BASE DESIGN AND LOCATIONS FOR ADA |
| | COMPLIANCE ON BASE BUILDINGS AND PLANS. |
| | THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS |
| | EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND |
| | PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE |
| | BUILDING. |
| | FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2) |
| | |
| | 5) NOTE: PLEASE CORRELATE RISER AND PANELS. |
| | PLEASE SEE THE CONDUCTORS FROM THE TRANSFORMER TO PANEL |
| | P2 WAS CORRECTED TO MEET THE MINIMUM AMPERAGE REQUIRED |
| | PER 240.21C6, 310.16, 240.4, HOWEVER THE |
| | CONDUCTORS/FEEDERS LOCATED FROM P2 TO P3 HAVE NOT BEEN |
| | CORRECTED. |
| | PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT |
| | SIZES MAIN CIRCUIT BREAKERS, PLEASE CORRELATE AND |
| | ADJUST. |
| | RISER STILL SHOWS 150A MCB AND PANEL P1 STILL SHOWS A |
| | 100A MCB. |
| | PLEASE SEE THE RISER SHOWS 150AMP RATED CONDUCTORS FROM |
| | THE MDP TO TRANSFORMER ON A 175AMP RATED BREAKER |
| | |
| | 6) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON |
| | EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE |
| | THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP |
| | EXCEEDS THE RATING OF THE 112KVA RATING. THIS IS THE |
| | SAME COMMENT. PLEASE SEE THE LOAD SHOWN ON THE |
| | MDP.(120,908VA) |
| | PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED. |
| | 230,240, 408, ETC. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE NOTICE |
| | TO FS 553.80(2)(B) WITH RESPECT TO REPEAT CODE |
| | COMPLIANT COMMENTS. |
| | PLEASE SEE A FEE HAS NOW BEEN ASSESSED IN THE AMOUNT OF |
| | $3,300 WHICH IS REQUIRED BEFORE PLANS MAY BE |
| | RE-SUBMITTED FOR REVIEW. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |