Plan Review Notes
Plan Review Notes For Permit 06070451
Permit Number 06070451
Review Stop E
Sequence Number 3
Notes
Date Text
2007-04-22 13:28:04 
 ******* UNSAT 3RD REVIEW ******
  
 ** PLEASE SEE THAT THERE ARE STILL MANY ITEMS FROM
 PREVIOUS REVIEWS WHICH HAVE NOT YET BEEN ADDRESSED FOR
 CODE COMPLIANCE.
  
 ** PLEASE SEE THE RESPONSE LETTER FROM THE DESIGNER
 ONLY RESPONDED TO NOTES 1-8 AND NEW NOTES FROM LAST
 REVIEW WERE NOT NOTED AND LETTER DID NOT CONTAIN ANY
 RESPONSE??A RESPONSE LETTER IS NOT REQUIRED HOWEVER
 WILL SOMETIMES HELP TO EXPLAIN ITEMS OR EXPEDITE THE
 REVIEW PROCESS.
  
  
 1) NOTE:PLEASE SEE THE NOTE FOR THE VALUE FOR
 COMPLETE SCOPE OF WORK STILL REMAINS. RESPONSE FROM
 DESIGNER MENTIONS FOR CONTRACTOR TO ADDRESS HOWEVER NO
 CHANGES TO APPLIED VALUE HAS BEEN DONE. PLEASE KNOW
 THAT A VALUE WILL BE ASSESSED BY THIS OFFICE IF AN
 APPROPRIATE VALUE IS NOT INDICATED.
 AS STATED ON PREVIOUS REVIEW THE VALUE SHALL INCLUDE
 ALL LABOR AND MATERIALS, INCLUDING ALL EQUIPMENT, A/C
 EQUIPMENT, ELECTRICAL EQUIPMENT, LIGHTING FIXTURES ETC.
 PLEASE KNOW A VALUE WILL BE ASSESSED USING THE FBC
 TABLES FOR INTERIOR BUILD OUT OF THE SQ FT AND WILL BE
 SUBSTANTIALLY INCREASED IF AN APPROPRIATE VALUE IS NOT
 APPLIED. PLEASE SEE FS 553.79, 553.792, AND FS 489.
 ** THE VALUE OF THE ELECTRICAL EQUIPMENT ALONE IS
 HIGHER THAN THE APPLIED VALUE FOR THE COMPLETE SCOPE OF
 WORK AS APPLIED.
 *FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE
 CITY OF WEST PALM BEACH.
  
 2) NOTE:PLEASE COORDINATE THE ELECTRICAL SERVICE ON
 THE BUILD OUT PLANS AS WELL AS THE ELECTRICAL PLANS FOR
 THE SHELL PERMITTED PLANS.
 PLEASE SEE THERE ARE SEVERAL ITEMS WHICH DO NOT
 CORRELATE.
  
 A) PLEASE SEE THE MAIN SWITCH IN TENANT SPACE
 ELECTRICAL ROOM IS STILL BEING SHOWN AS 600AMP WITH
 400AMP OVER CURRENT PROTECTION YET THE RISER AND OTHER
 PLANS INDICATE THIS DISCONNECT AS BEING 600AMP WITH
 600AMP OVER CURRENT PROTECTION. NOTED ON BOTH PREVIOUS
 REVIEWS, YET PLANS STILL SHOW THIS?
  
 B) PLEASE THE FEEDERS ARE STILL SHOWN AS OVER HEAD TO
 THE TENANT ELECTRICAL ROOM AND WELL AS BEING NOTED AS
 UNDERGROUND ON SHELL PLANS AND THESE PLANS.
  
 C) PLEASE SEE THE FEEDER CONDUITS ARE SHOWN AS 3INCH ON
 SOME SHEETS AND 4INCH ON OTHERS AND SHELL PLANS?
  
 D) PLEASE SEE THE FEEDERS NOW FROM THE MAIN ELECTRICAL
 ROOM HAVE BEEN CHANGED FROM THE PREVIOUS 600MCM DOWN TO
 350MCM YET THE VOLTAGE DROP CALCULATIONS STILL INDICATE
 600MCM. PLEASE SEE SHELL PLANS.
 13-413.1ABC.1 AS NOTED ON PREVIOUS REVIEW FOR VOLTAGE
 DROP)
  
 E) PLEASE SEE THE ONE-LINE DIAGRAM ON THE TENANT BUILD
 OUT PLANS SHALL INDICATE THE OCP AND MAIN WHICH IS
 LOCATED IN THE MAIN SWITCH BOARD ON THE SHELL PLANS.
 230.70, 230.71, 230.72.
  
 ** PLEASE COORDINATE ALL ELECTRICAL EQUIPMENT ON BOTH
 SETS OF PLANS UNDER EACH PERMIT AND ADJUST FOR THE CODE
 COMPLIANCE COMMENTS.
  
 3) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS
 FOR CHAPTER 13 COMPLIANCE.
 PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES.
 PLEASE SEE MISSING SCHEDULING OF SYSTEM.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW LIGHTING CONTROL PANEL.
 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE
 VERIFIED AS SHOWN.
 SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE
 LISTING FROM A NRTL(NATION RECOGNIZED TESTING
 LABORATORY).
 PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND
 OCCUPANCY DEVICES.
 PLEASE SEE MANY ROOMS WHICH STILL ONLY INDICATE A *S*
 SWITCH FOR CONTROL OF LIGHTING. PLEASE SEE
 13-415.1.ABC.1.2 FOR SPACE CONTROL.
 PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS
 BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL
 BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR
 SUBMITTED BACK FOR REVIEW.
 PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING
 WITH MANUAL CONTROL FOR LIGHTING WHICH IS NOT POSSIBLE
 WHEN AN AUTOMATED SYSTEM IS BEING INSTALLED AND
 REQUIRED.
 PLEASE CORRELATE THE FIXTURES ON PLANS WITH THAT OF THE
 FIXTURES ON ENERGY CALCULATIONS FOR THE TYPE, WATTAGE
 AND THE NUMBER OF FIXTURES ON PLANS AND IN
 CALCULATIONS.
 ** PLEASE SEE THAT THE EXACT SAME ENERGY CALCULATIONS
 WERE SUBMITTED BACK.
 PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW,
 THERE MAY BE SOME FUTURE COMMENTS.
  
 PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A
 WORST CASE SCENARIO.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1,
 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1
 PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC.
  
  
 4) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF
 CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL
 INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL
 DEVICES.
 PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES
 SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE
 MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2,
 .3(4).
 THIS IS REQUIRED FOR BASE DESIGN AND LOCATIONS FOR ADA
 COMPLIANCE ON BASE BUILDINGS AND PLANS.
 THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS
 EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND
 PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE
 BUILDING.
 FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2)
  
 5) NOTE: PLEASE CORRELATE RISER AND PANELS.
 PLEASE SEE THE CONDUCTORS FROM THE TRANSFORMER TO PANEL
 P2 WAS CORRECTED TO MEET THE MINIMUM AMPERAGE REQUIRED
 PER 240.21C6, 310.16, 240.4, HOWEVER THE
 CONDUCTORS/FEEDERS LOCATED FROM P2 TO P3 HAVE NOT BEEN
 CORRECTED.
 PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT
 SIZES MAIN CIRCUIT BREAKERS, PLEASE CORRELATE AND
 ADJUST.
 RISER STILL SHOWS 150A MCB AND PANEL P1 STILL SHOWS A
 100A MCB.
 PLEASE SEE THE RISER SHOWS 150AMP RATED CONDUCTORS FROM
 THE MDP TO TRANSFORMER ON A 175AMP RATED BREAKER
  
 6) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON
 EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE
 THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP
 EXCEEDS THE RATING OF THE 112KVA RATING. THIS IS THE
 SAME COMMENT. PLEASE SEE THE LOAD SHOWN ON THE
 MDP.(120,908VA)
 PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED.
 230,240, 408, ETC.
 FBC 106.1.2 ADMIN SECTION.
  
 7) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH GAVE NOTICE
 TO FS 553.80(2)(B) WITH RESPECT TO REPEAT CODE
 COMPLIANT COMMENTS.
 PLEASE SEE A FEE HAS NOW BEEN ASSESSED IN THE AMOUNT OF
 $3,300 WHICH IS REQUIRED BEFORE PLANS MAY BE
 RE-SUBMITTED FOR REVIEW.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]