Plan Review Notes
Plan Review Notes For Permit 06070451
Permit Number 06070451
Review Stop P
Sequence Number 2
Notes
Date Text
2007-01-13 12:29:04PAUL SCHMITZ
 [email protected] 2004 PLUMBING CODE
 PLAN REVIEWFBC2004 FUEL GAS CODEPLAN
 REVIEWFBC 2004 CH 11, FL ACESSIBILITY
 CODEAMENDMENTS TO THE FLORIDA BUILDING CODE
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
 DENIED, NEW COMMENTS
  
 1) SHT P-2 , NOTE #16 REFERENCE TO A/C CONDENSATE
 DRAIN.
 SHT A/C -2 ROOF TOP UNIT DETAIL, IS NOT SHOWING
 DISPOSAL OF A/C CONDENSATE.
 PLEASE CLARIFY.
  
 2) SHT P-2WATER HEATER DETAIL
 607.3 THERMAL EXPANSION CONTROL.
 A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY
 THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN
 ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2
 BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A
 BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE
 IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE
 WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION
 CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR
 CONTROLLING PRESSURE SHALL BE INSTALLED.
  
 3) SHT P-2 WATER RISER DIAGRAM
 PLEASE CLARIFY WHAT IS BEING USED AT EACH WATER
 SUPPLIED FIXTURE.
 604.9 WATER HAMMER.
 THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM
 SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER
 HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED
 WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER
 ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS
 SHALL CONFORM TO ASSE 1010.
  
 END OF COMMENTS, QUESTIONS 561-805-6692