| 2007-01-13 12:29:04 | PAUL SCHMITZ |
| | [email protected] 2004 PLUMBING CODE |
| | PLAN REVIEWFBC2004 FUEL GAS CODEPLAN |
| | REVIEWFBC 2004 CH 11, FL ACESSIBILITY |
| | CODEAMENDMENTS TO THE FLORIDA BUILDING CODE |
| | CHAPT.1, ADMINISTRATION, 2004 EDITION |
| | |
| | DENIED, NEW COMMENTS |
| | |
| | 1) SHT P-2 , NOTE #16 REFERENCE TO A/C CONDENSATE |
| | DRAIN. |
| | SHT A/C -2 ROOF TOP UNIT DETAIL, IS NOT SHOWING |
| | DISPOSAL OF A/C CONDENSATE. |
| | PLEASE CLARIFY. |
| | |
| | 2) SHT P-2WATER HEATER DETAIL |
| | 607.3 THERMAL EXPANSION CONTROL. |
| | A MEANS OF CONTROLLING INCREASED PRESSURE CAUSED BY |
| | THERMAL EXPANSION SHALL BE PROVIDED WHERE REQUIRED IN |
| | ACCORDANCE WITH SECTIONS 607.3.1 AND 607.3.2. 607.3.2 |
| | BACKFLOW PREVENTION DEVICE OR CHECK VALVE. WHERE A |
| | BACKFLOW PREVENTION DEVICE, CHECK VALVE OR OTHER DEVICE |
| | IS INSTALLED ON A WATER SUPPLY SYSTEM UTILIZING STORAGE |
| | WATER HEATING EQUIPMENT SUCH THAT THERMAL EXPANSION |
| | CAUSES AN INCREASE IN PRESSURE, A DEVICE FOR |
| | CONTROLLING PRESSURE SHALL BE INSTALLED. |
| | |
| | 3) SHT P-2 WATER RISER DIAGRAM |
| | PLEASE CLARIFY WHAT IS BEING USED AT EACH WATER |
| | SUPPLIED FIXTURE. |
| | 604.9 WATER HAMMER. |
| | THE FLOW VELOCITY OF THE WATER DISTRIBUTION SYSTEM |
| | SHALL BE CONTROLLED TO REDUCE THE POSSIBILITY OF WATER |
| | HAMMER. A WATER-HAMMER ARRESTOR SHALL BE INSTALLED |
| | WHERE QUICK-CLOSING VALVES ARE UTILIZED. WATER-HAMMER |
| | ARRESTORS SHALL BE INSTALLED IN ACCORDANCE WITH THE |
| | MANUFACTURER?S SPECIFICATIONS. WATER-HAMMER ARRESTORS |
| | SHALL CONFORM TO ASSE 1010. |
| | |
| | END OF COMMENTS, QUESTIONS 561-805-6692 |