| 2006-12-28 16:28:53 | *****DENIED***** |
| | |
| | |
| | |
| | 1.PLEASE CLARIFY IF THE PROPOSED SCOPE OF WORK AT |
| | THIS LOCATION IS FOR INTERIOR ALTERATION, BUILDING |
| | CONSTRUCTION, OR A COMBINATION OF THE TWO.ALSO, |
| | STAPLES IS LISTED AS BAY 2; ARE THERE ANY OTHER |
| | TENANTS/BAYS FOR 2029 OKEECHOBEE BOULEVARD?THE USE OF |
| | SUITE/TENANT/BAY SHOULD ONLY BE USED WHEN THERE ARE |
| | MORE THAN ONE UNIT WITH THE SAME NUMERICAL ADDRESS. |
| | |
| | 2.ON DRAWING A10, SHOW/DISPLAY THE NUMERICAL ADDRESS |
| | ON THE BUILING AS PER WEST PALM BEACH CODE (NUMBERS |
| | SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH). |
| | |
| | 3.DRAWING NUMBER E-1 THRU FS-2 HAVE THE INCORRECT |
| | NUMERICAL ADDRESS (2015 OKEECHOBEE BLVD.) IN THE TITLE |
| | SECTION OF THE PLAN. |
| | |
| | 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101 (2003 |
| | EDITION) AND THE FLORIDA FIRE PREVENTION CODE (2004 |
| | EDITION). |
| | |
| | 5.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 6.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT |
| | INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO THE |
| | SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE |
| | LANES). |
| | |
| | 7.ON DRAWING AC-2, MAKE CHANGE TO GENERAL AIR |
| | CONDITIONING NOTE #17 TO REFLECT THAT DUCT SMOKE |
| | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |
| | |
| | 8. |