Plan Review Notes
Plan Review Notes For Permit 06070451
Permit Number 06070451
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2006-12-28 16:28:53*****DENIED*****
  
  
  
 1.PLEASE CLARIFY IF THE PROPOSED SCOPE OF WORK AT
 THIS LOCATION IS FOR INTERIOR ALTERATION, BUILDING
 CONSTRUCTION, OR A COMBINATION OF THE TWO.ALSO,
 STAPLES IS LISTED AS BAY 2; ARE THERE ANY OTHER
 TENANTS/BAYS FOR 2029 OKEECHOBEE BOULEVARD?THE USE OF
 SUITE/TENANT/BAY SHOULD ONLY BE USED WHEN THERE ARE
 MORE THAN ONE UNIT WITH THE SAME NUMERICAL ADDRESS.
  
 2.ON DRAWING A10, SHOW/DISPLAY THE NUMERICAL ADDRESS
 ON THE BUILING AS PER WEST PALM BEACH CODE (NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND 1" IN WIDTH).
  
 3.DRAWING NUMBER E-1 THRU FS-2 HAVE THE INCORRECT
 NUMERICAL ADDRESS (2015 OKEECHOBEE BLVD.) IN THE TITLE
 SECTION OF THE PLAN.
  
 4.LIFE SAFETY SHALL COMPLY WITH NFPA 101 (2003
 EDITION) AND THE FLORIDA FIRE PREVENTION CODE (2004
 EDITION).
  
 5.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 6.CONSTRUCTION AND/OR DEMOLITION OPERATIONS SHALL NOT
 INTERFERE OR HINDER EMERGENCY RESPONDER ACCESS TO THE
 SAID PROPERTY OR THE VICINITY THEREOF (INCLUDING FIRE
 LANES).
  
 7.ON DRAWING AC-2, MAKE CHANGE TO GENERAL AIR
 CONDITIONING NOTE #17 TO REFLECT THAT DUCT SMOKE
 DETECTORS SHALL INITIATE A GENERAL FIRE ALARM.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 SHEET INDICATING HOW/WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW