| 2006-12-23 18:40:45 | *** UNSAT 2ND REVIEW *** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL |
| | NEED TO BE ADDRESSED ALONG WITH SOME NEW NOTES. PLEASE |
| | SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS |
| | REVIEW AND IN THE EXACT NUMERICAL ORDER WITH NEW NOTES |
| | ADDED TO THE BOTTOM OF THE FIRST REVIEW NOTES. |
| | |
| | ** PLEASE SEE NOTES ARE NOTED WITH A NO, OK,OR SOME |
| | MAY CONTAIN A NO/OK, WHICH WOULD INDICATE PART OF THE |
| | COMMENT MAY HAVE BEEN ADDRESSED HOWEVER NOT FULLY OR |
| | THERE STILL MAY BE SOME UNCERTAINLY OF RESPONSE/PLANS. |
| | |
| | 1) NOTE:NO, PLEASE SEE THE VALUE WAS INCREASED ON |
| | PERMIT APPLICATION BY $5K. AS STATED ON PREVIOUS REVIEW |
| | THE VALUE SHALL INCLUDE ALL LABOR AND MATERIALS, |
| | INCLUDING ALL EQUIPMENT, A/C EQUIPMENT, ELECTRICAL |
| | EQUIPMENT, LIGHTING FIXTURES ETC. PLEASE KNOW A VALUE |
| | WILL BE ASSESSED USING THE FBC TABLES FOR INTERIOR |
| | BUILD OUT OF THE SQ FT AND WILL BE SUBSTANTIALLY |
| | INCREASED IF AN APPROPRIATE VALUE IS NOT APPLIED. |
| | PLEASE SEE FS 553.79, 553.792, AND FS 489. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE VALUE FOR PROPOSED SCOPE OF WORK IS WAY |
| | LOW. PLEASE KNOW VALUE FOR COMPLETE SCOPE OF WORK ON |
| | PLANS NEEDS TO BE ADJUSTED. PLEASE SEE VALUE BE BASED |
| | ON ALL LABOR AND MATERIALS WHETHER OR NOT ANY |
| | EQUIPMENT, LIGHTING ETC IS OWNER SUPPLIED. |
| | FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY |
| | OF WEST PALM BEACH. |
| | ** PLEASE ALSO PROVIDE THE DESCRIPTION ON APPLICATION |
| | FOR ACTUAL SCOPE OF WORK BEING PERFORMED AS THE DETAIL |
| | GIVEN SEEMS TO BE ABOUT THE SAME AS THE SHELL BLDG |
| | APPLICATION. |
| | ** NOTE FOR CONTRACTOR AND DOES NOT APPLY TO PLANS. |
| | |
| | 2) NOTE: OK. |
| | |
| | 3) NOTE: NO/OK. PLEASE SEE THE CODES WERE ADDED TO |
| | PLANS; HOWEVER THERE ARE STILL SEVERAL SECTIONS OF THE |
| | CODES BEING NOTED ON PLANS WHICH ARE OUT OF THE 1996 |
| | NFPA-70. |
| | PLEASE KNOW WHEN SPECIFICALLY NOTED CODE SECTIONS ON |
| | PLANS, AND THEN THEY MUST REFLECT AND CORRELATE WITH |
| | THE CODE WHICH THEY ARE UNDER AND CORRELATE. PLEASE SEE |
| | MISSING REFERENCE TO NFPA-101 2003 |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING CODES AT |
| | A MINIMUM FOR ELECTRICAL REVIEW. |
| | 2002 NFPA-70(NEC), 2002 NFPA-72, 2003 |
| | NFPA-101 AND THE 2004 FBC. |
| | PLEASE SEE THERE ARE CODE ARTICLES REFERENCED ON PLANS |
| | WHICH ARE FROM THE |
| | 1996 NEC> |
| | PLEASE SEE REDLINED SET. |
| | |
| | 4) NOTE:NO, PLEASE KNOW AS OF THIS REVIEW THE PLANS |
| | FOR THE MAIN BUILDING/SHELL HAS NOT BEEN IN FOR REVIEW. |
| | PLEASE SEE PREVIOUS NOTES UNDER THEIR PERMIT. PLEASE |
| | SEE PLANS STILL DO NOT CORRELATE AND THE SERVICE AS |
| | SHOWN IS NOT PERMITTED. 230.2. |
| | PLEASE KNOW IN EITHER CASE, PLANS INDICATE UNDERGROUND |
| | AND OVERHEAD, 400A AND 600A, PLEASE SEE 230.70 AS NO |
| | MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED |
| | INSIDE THE BUILDING. (230.6) PLEASE ALSO SEE NEW NOTES |
| | FOR SERVICE ITEMS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE THIS PLAN AND RISER IS SHOWING A NEW AND |
| | SEPARATE ELECTRICAL SERVICE WHICH DOES NOT CORRELATE |
| | WITH THE SHELL BUILDING PLANS. PLEASE REVISE RISER TO |
| | INCLUDE THE MAIN FEED FROM THE MAIN ELECTRICAL ROOM. |
| | PLEASE ALSO SEE ELECTRICAL PLANS SHOW 400A MAIN AND |
| | RISER SHOWS 600A. |
| | THIS IS ONE BUILDING AND THE SEPARATION PROVIDED IN THE |
| | ARCHITECTURAL AND STRUCTURAL PLANS DO NOT SEEM TO LEND |
| | TO THE DEFINITION OF A "BUILDING" WHICH WOULD CONTAIN A |
| | "FIRE WALL". PLEASE SEE DEFINITIONS OF "FIRE WALL" 4HR |
| | RATED AND ABLE TO COLLAPSE ON BOTH SIDES WITHOUT |
| | AFFECTING THE STRUCTURAL INTEGRITY OF THE OTHER |
| | STRUCTURE. |
| | PLEASE SEE 230.2, AND GRANTING OF AN ADDITIONAL SERVICE |
| | AT THIS TIME IS NOT GRANTED. |
| | |
| | 5) NOTE: NO/OK, PLEASE SEE THE NOTE WAS ADDED TO THE |
| | LOWER NOTE WHICH APPEARS TO BE 15A, YET SEE NOTE #1 IS |
| | STILL NOTED AND SHOWN AS BEFORE. PLEASE ADJUST THIS |
| | NOTE #1 WITH THE NEW NOTE ADDED TO 15A. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE PLACE NOTE ON PLANS WITH NOTE #1 AS NOTED FOR |
| | PANEL SCHEDULES AND PROPOSED LOCK OFF DEVICES ON |
| | BRKRS. |
| | PLEASE KNOW ALL "LOCK-OFF/ON" DEVICES MUST BE AN |
| | INTEGRAL PART OF THE BREAKER AND NOT CAPABLE OF BEING |
| | REMOVED WITHOUT THE BREAKER BEING REMOVED. |
| | ** MANY OF THE PROPOSED DEVICES EASILY FALL OFF WHEN |
| | REMOVING PANEL COVERS OR CAN BE READILY REMOVED. |
| | |
| | 6) NOTE:OK, HOWEVER SEE NEW NOTES. |
| | |
| | 7) NOTE: OK. |
| | |
| | 8) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS |
| | FOR CHAPTER 13 COMPLIANCE. |
| | PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES. PLEASE |
| | SEE MISSING SCHEDULING OF SYSTEM. |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE |
| | NEW LIGHTING CONTROL PANEL. |
| | 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE |
| | VERIFIED AS SHOWN. |
| | SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE |
| | LISTING FROM A NRTL(NATION RECOGNIZED TESTING |
| | LABORATORY). |
| | PLEASE SUBMIT A DETAIL FOR THIS PANEL AND HOW ALL |
| | EMERGENCY AND EXIT LIGHTING WILL BE WIRED AHEAD OF ALL |
| | LIGHTING CONTROLS AND OCCUPANCY DEVICES. |
| | PLEASE SEE 13-415.1.ABC.3 FOR NOTES AND INDICATION OF |
| | TANDEM WIRING. |
| | PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND |
| | OCCUPANCY DEVICES. (SOME SHOWN AND NOTED AT 10MINS |
| | WHICH ARE OK). |
| | PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS |
| | BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL |
| | BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR |
| | SUBMITTED BACK FOR REVIEW. |
| | PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING |
| | WITH MANUAL CONTROL. THIS IS NOT POSSIBLE AS AUTOMATED |
| | SYSTEMS ARE BEING INSTALLED AND REQUIRED. |
| | PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW, |
| | THERE MAY BE SOME FUTURE COMMENTS. |
| | |
| | ** PREVIOUS REVIEW NOTE ** |
| | PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A |
| | WORST CASE SCENARIO. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE |
| | 13-415.1.AB.1, |
| | 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1 PLEASE |
| | ALSO SEE NO ENERGY CALCULATIONS WERE SUBMITTED FOR |
| | REVIEW. |
| | PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC. |
| | |
| | *** NEW NOTES** |
| | |
| | 1) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF |
| | CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL |
| | INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL |
| | DEVICES. |
| | PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES |
| | SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE |
| | MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2, |
| | .3(4). |
| | PLEASE KNOW THIS COMMENT WAS NOT PART OF PREVIOUS |
| | REVIEW AS THIS HAS NOW BECOME PART OF THE ELECTRICAL |
| | REVIEW TO REVIEW DEVICES FOR CHAPTER 11 REQUIREMENTS. |
| | THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS |
| | EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND |
| | PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE |
| | BUILDING. |
| | FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2) |
| | |
| | 2) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH |
| | RESPECT TO DESIGN PROFESSIONALS ANDREPEAT COMMENTS |
| | FOR CODE COMPLIANCE. |
| | |
| | 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE |
| | BASED ON THE PANELS, LARGER CONDUCTORS FOR PANEL P2 |
| | WILL BE REQUIRED. PLEASE SEE BOTH 250A MCB AND 300A MCB |
| | ARE BEING SHOWN ON PLANS. |
| | PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT |
| | SIZES MCB'S PLEASE CORRELATE AND ADJUST. |
| | |
| | 4) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON |
| | EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE |
| | THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP |
| | EXCEEDS THE RATING OF THE 112KVA RATING. |
| | PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED. |
| | FBC 106.1.2 ADMIN SECTION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |