Plan Review Notes
Plan Review Notes For Permit 06070451
Permit Number 06070451
Review Stop E
Sequence Number 2
Notes
Date Text
2006-12-23 18:40:45*** UNSAT 2ND REVIEW ***
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW STILL
 NEED TO BE ADDRESSED ALONG WITH SOME NEW NOTES. PLEASE
 SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM PREVIOUS
 REVIEW AND IN THE EXACT NUMERICAL ORDER WITH NEW NOTES
 ADDED TO THE BOTTOM OF THE FIRST REVIEW NOTES.
  
 ** PLEASE SEE NOTES ARE NOTED WITH A NO, OK,OR SOME
 MAY CONTAIN A NO/OK, WHICH WOULD INDICATE PART OF THE
 COMMENT MAY HAVE BEEN ADDRESSED HOWEVER NOT FULLY OR
 THERE STILL MAY BE SOME UNCERTAINLY OF RESPONSE/PLANS.
  
 1) NOTE:NO, PLEASE SEE THE VALUE WAS INCREASED ON
 PERMIT APPLICATION BY $5K. AS STATED ON PREVIOUS REVIEW
 THE VALUE SHALL INCLUDE ALL LABOR AND MATERIALS,
 INCLUDING ALL EQUIPMENT, A/C EQUIPMENT, ELECTRICAL
 EQUIPMENT, LIGHTING FIXTURES ETC. PLEASE KNOW A VALUE
 WILL BE ASSESSED USING THE FBC TABLES FOR INTERIOR
 BUILD OUT OF THE SQ FT AND WILL BE SUBSTANTIALLY
 INCREASED IF AN APPROPRIATE VALUE IS NOT APPLIED.
 PLEASE SEE FS 553.79, 553.792, AND FS 489.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE VALUE FOR PROPOSED SCOPE OF WORK IS WAY
 LOW. PLEASE KNOW VALUE FOR COMPLETE SCOPE OF WORK ON
 PLANS NEEDS TO BE ADJUSTED. PLEASE SEE VALUE BE BASED
 ON ALL LABOR AND MATERIALS WHETHER OR NOT ANY
 EQUIPMENT, LIGHTING ETC IS OWNER SUPPLIED.
 FBC 108.3 ADMINISTRATIVE SECTION AS ADOPTED BY THE CITY
 OF WEST PALM BEACH.
 ** PLEASE ALSO PROVIDE THE DESCRIPTION ON APPLICATION
 FOR ACTUAL SCOPE OF WORK BEING PERFORMED AS THE DETAIL
 GIVEN SEEMS TO BE ABOUT THE SAME AS THE SHELL BLDG
 APPLICATION.
 ** NOTE FOR CONTRACTOR AND DOES NOT APPLY TO PLANS.
  
 2) NOTE: OK.
  
 3) NOTE: NO/OK. PLEASE SEE THE CODES WERE ADDED TO
 PLANS; HOWEVER THERE ARE STILL SEVERAL SECTIONS OF THE
 CODES BEING NOTED ON PLANS WHICH ARE OUT OF THE 1996
 NFPA-70.
 PLEASE KNOW WHEN SPECIFICALLY NOTED CODE SECTIONS ON
 PLANS, AND THEN THEY MUST REFLECT AND CORRELATE WITH
 THE CODE WHICH THEY ARE UNDER AND CORRELATE. PLEASE SEE
 MISSING REFERENCE TO NFPA-101 2003
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING CODES AT
 A MINIMUM FOR ELECTRICAL REVIEW.
 2002 NFPA-70(NEC), 2002 NFPA-72, 2003
 NFPA-101 AND THE 2004 FBC.
 PLEASE SEE THERE ARE CODE ARTICLES REFERENCED ON PLANS
 WHICH ARE FROM THE
 1996 NEC>
 PLEASE SEE REDLINED SET.
  
 4) NOTE:NO, PLEASE KNOW AS OF THIS REVIEW THE PLANS
 FOR THE MAIN BUILDING/SHELL HAS NOT BEEN IN FOR REVIEW.
 PLEASE SEE PREVIOUS NOTES UNDER THEIR PERMIT. PLEASE
 SEE PLANS STILL DO NOT CORRELATE AND THE SERVICE AS
 SHOWN IS NOT PERMITTED. 230.2.
 PLEASE KNOW IN EITHER CASE, PLANS INDICATE UNDERGROUND
 AND OVERHEAD, 400A AND 600A, PLEASE SEE 230.70 AS NO
 MORE THAN 8FT OF UNPROTECTED CONDUCTORS ARE PERMITTED
 INSIDE THE BUILDING. (230.6) PLEASE ALSO SEE NEW NOTES
 FOR SERVICE ITEMS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE THIS PLAN AND RISER IS SHOWING A NEW AND
 SEPARATE ELECTRICAL SERVICE WHICH DOES NOT CORRELATE
 WITH THE SHELL BUILDING PLANS. PLEASE REVISE RISER TO
 INCLUDE THE MAIN FEED FROM THE MAIN ELECTRICAL ROOM.
 PLEASE ALSO SEE ELECTRICAL PLANS SHOW 400A MAIN AND
 RISER SHOWS 600A.
 THIS IS ONE BUILDING AND THE SEPARATION PROVIDED IN THE
 ARCHITECTURAL AND STRUCTURAL PLANS DO NOT SEEM TO LEND
 TO THE DEFINITION OF A "BUILDING" WHICH WOULD CONTAIN A
 "FIRE WALL". PLEASE SEE DEFINITIONS OF "FIRE WALL" 4HR
 RATED AND ABLE TO COLLAPSE ON BOTH SIDES WITHOUT
 AFFECTING THE STRUCTURAL INTEGRITY OF THE OTHER
 STRUCTURE.
 PLEASE SEE 230.2, AND GRANTING OF AN ADDITIONAL SERVICE
 AT THIS TIME IS NOT GRANTED.
  
 5) NOTE: NO/OK, PLEASE SEE THE NOTE WAS ADDED TO THE
 LOWER NOTE WHICH APPEARS TO BE 15A, YET SEE NOTE #1 IS
 STILL NOTED AND SHOWN AS BEFORE. PLEASE ADJUST THIS
 NOTE #1 WITH THE NEW NOTE ADDED TO 15A.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE PLACE NOTE ON PLANS WITH NOTE #1 AS NOTED FOR
 PANEL SCHEDULES AND PROPOSED LOCK OFF DEVICES ON
 BRKRS.
 PLEASE KNOW ALL "LOCK-OFF/ON" DEVICES MUST BE AN
 INTEGRAL PART OF THE BREAKER AND NOT CAPABLE OF BEING
 REMOVED WITHOUT THE BREAKER BEING REMOVED.
 ** MANY OF THE PROPOSED DEVICES EASILY FALL OFF WHEN
 REMOVING PANEL COVERS OR CAN BE READILY REMOVED.
  
 6) NOTE:OK, HOWEVER SEE NEW NOTES.
  
 7) NOTE: OK.
  
 8) NOTE:NO, PLEASE SEE PLANS STILL NEED SOME ITEMS
 FOR CHAPTER 13 COMPLIANCE.
 PLEASE SEE MISSING TIMES ON OVER RIDE DEVICES. PLEASE
 SEE MISSING SCHEDULING OF SYSTEM.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR THE
 NEW LIGHTING CONTROL PANEL.
 110.3/90.7 277/120V IN THE SAME ENCLOSURE NEEDS TO BE
 VERIFIED AS SHOWN.
 SPECS/CUT SHEETS FROM THE MANUFACTURE MUST CONTAIN THE
 LISTING FROM A NRTL(NATION RECOGNIZED TESTING
 LABORATORY).
 PLEASE SUBMIT A DETAIL FOR THIS PANEL AND HOW ALL
 EMERGENCY AND EXIT LIGHTING WILL BE WIRED AHEAD OF ALL
 LIGHTING CONTROLS AND OCCUPANCY DEVICES.
 PLEASE SEE 13-415.1.ABC.3 FOR NOTES AND INDICATION OF
 TANDEM WIRING.
 PLEASE STATE ALL MAXIMUM TIMES ON OVER RIDE AND
 OCCUPANCY DEVICES. (SOME SHOWN AND NOTED AT 10MINS
 WHICH ARE OK).
 PLEASE SEE METHOD A IS NOW BEING SUBMITTED FOR THIS
 BEING A BUILD OUT OF WHAT WILL BE AN EXISTING SHELL
 BUILDING WHICH IS NOT YET ISSUED FOR PERMIT OR
 SUBMITTED BACK FOR REVIEW.
 PLEASE SEE SAME METHOD A WHICH INDICATES ALL LIGHTING
 WITH MANUAL CONTROL. THIS IS NOT POSSIBLE AS AUTOMATED
 SYSTEMS ARE BEING INSTALLED AND REQUIRED.
 PLEASE KNOW AS SOME ITEMS ARE NOT AVAILABLE FOR REVIEW,
 THERE MAY BE SOME FUTURE COMMENTS.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, PROVIDE A
 WORST CASE SCENARIO.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND .1.3. PLEASE SEE
 13-415.1.AB.1,
 13-415.2.ABC.1, TABLES 415.2.C.1, AND 415.2. B.1 PLEASE
 ALSO SEE NO ENERGY CALCULATIONS WERE SUBMITTED FOR
 REVIEW.
 PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 FBC.
  
 *** NEW NOTES**
  
 1) NOTE: PLEASE SEE THAT THE BASE BUILDING PLANS IF
 CONTAINING A FIRE ALARM SYSTEM AS REQUIRED SHALL
 INDICATE ALL LOCATIONS OF THE FA SYSTEM INCLUDING ALL
 DEVICES.
 PLEASE KNOW ALL DEVICES AS HORNS AND STROBE DEVICES
 SHALL NOT ONLY MEET NFPA-72 THEY MUST ALSO INDICATE THE
 MINIMUM LEVELS AS REQUIRED PER 2004 FBC 11-4.28.1, .2,
 .3(4).
 PLEASE KNOW THIS COMMENT WAS NOT PART OF PREVIOUS
 REVIEW AS THIS HAS NOW BECOME PART OF THE ELECTRICAL
 REVIEW TO REVIEW DEVICES FOR CHAPTER 11 REQUIREMENTS.
 THE BASE BUILDING SHALL INDICATE ALL FIRE ALARM SYSTEMS
 EVEN THOUGH THEY WILL BE UNDER SEPARATE PERMITS AND
 PLANS AT A LATER DATE AFTER ISSUANCE OF THE BASE
 BUILDING.
 FBC ADMIN SECTION 106.3.5.1.1, FS 553.79(2)
  
 2) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO DESIGN PROFESSIONALS ANDREPEAT COMMENTS
 FOR CODE COMPLIANCE.
  
 3) NOTE: PLEASE CORRELATE RISER AND PANELS. PLEASE SEE
 BASED ON THE PANELS, LARGER CONDUCTORS FOR PANEL P2
 WILL BE REQUIRED. PLEASE SEE BOTH 250A MCB AND 300A MCB
 ARE BEING SHOWN ON PLANS.
 PLEASE SEE PANEL P1 WHICH ALSO INDICATES TWO DIFFERENT
 SIZES MCB'S PLEASE CORRELATE AND ADJUST.
  
 4) NOTE: PLEASE CORRELATE LOAD ON MDP WITH LOADS ON
 EACH OF THE TWO PANELS TO THE TRANSFORMER. PLEASE SEE
 THAT THE LOAD ON THE TRANSFORMER AS SHOWN ON MDP
 EXCEEDS THE RATING OF THE 112KVA RATING.
 PLEASE CLARIFY THIS AND ADJUST WHERE NEEDED.
 FBC 106.1.2 ADMIN SECTION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]