| Date |
Text |
| 2007-01-05 14:52:54 | BUILDING PLAN REVIEW |
| | PERMIT: 06070445 |
| | ADD: 2015 OKEECHOBEE BLVD. |
| | CONT: BOCA DEVEL. & CONST. |
| | TEL: (561)391-6227 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | EX FBC CODE= 2004 EXISTING FLORIDA |
| | BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2NDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) COMMENT #5 FROM THE FIRST REVIEW DEALS |
| | WITH THE MINIMUM REQUIREMENTS OF CHAPTER |
| | 13 ENERGY CODE REQUIREMENTS |
| | PLEASE SEE ELECTRICAL STATEMENTS. |
| | |
| | 4 COMMEENT# 7 FROM THE PREVIOUS EVIEW DEALS |
| | WITH THE AUTOMATIC SLIDING DOORS,ADDITIONAL |
| | INFORMATION |
| | AS TOO HOW ONE WILL GAIN EGRESS FROM THE STORE IN THE |
| | EVENT OF LOSS OF POWER. |
| | PLEASE PROVIDE PROUCT APPROVAL FOR OTHER DOCUMENTATION |
| | PROVIDING |
| | COMPLIANCE WITH: |
| | |
| | 1008.1.3.3 HORIZONTAL SLIDING DOORS. |
| | |
| | IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING |
| | DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS |
| | IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2 |
| | SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1. |
| | THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE |
| | OF BEING OPERATED MANUALLY IN THE EVENT OF POWER |
| | FAILURE. |
| | 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD |
| | FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3. |
| | THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT |
| | EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND |
| | 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE |
| | MINIMUM REQUIRED WIDTH. |
| | 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO |
| | EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS |
| | (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT |
| | TO THE OPERATING DEVICE. |
| | 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE |
| | APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED, |
| | SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE |
| | DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA |
| | 80 AND SHALL COMPLY WITH SECTION 715 . |
| | 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED |
| | STANDBY POWER SUPPLY. |
| | 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE |
| | ELECTRICALLY SUPERVISED. |
| | 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED |
| | WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE |
| | OPERATING DEVICE. |
| | 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES, |
| | HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS |
| | CORRIDORS. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |