Plan Review Notes
Plan Review Notes For Permit 06070451
Permit Number 06070451
Review Stop B
Sequence Number 2
Notes
Date Text
2007-01-05 14:52:54BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) COMMENT #5 FROM THE FIRST REVIEW DEALS
 WITH THE MINIMUM REQUIREMENTS OF CHAPTER
 13 ENERGY CODE REQUIREMENTS
 PLEASE SEE ELECTRICAL STATEMENTS.
  
 4 COMMEENT# 7 FROM THE PREVIOUS EVIEW DEALS
 WITH THE AUTOMATIC SLIDING DOORS,ADDITIONAL
 INFORMATION
 AS TOO HOW ONE WILL GAIN EGRESS FROM THE STORE IN THE
 EVENT OF LOSS OF POWER.
 PLEASE PROVIDE PROUCT APPROVAL FOR OTHER DOCUMENTATION
 PROVIDING
 COMPLIANCE WITH:
  
 1008.1.3.3 HORIZONTAL SLIDING DOORS.
  
 IN OTHER THAN GROUP H OCCUPANCIES, HORIZONTAL SLIDING
 DOORS PERMITTED TO BE A COMPONENT OF A MEANS OF EGRESS
 IN ACCORDANCE WITH EXCEPTION 5 TO SECTION 1008.1.2
 SHALL COMPLY WITH ALL OF THE FOLLOWING CRITERIA: 1.
 THE DOORS SHALL BE POWER OPERATED AND SHALL BE CAPABLE
 OF BEING OPERATED MANUALLY IN THE EVENT OF POWER
 FAILURE.
 2.THE DOORS SHALL BE OPENABLE BY A SIMPLE METHOD
 FROM BOTH SIDES WITHOUT SPECIAL KNOWLEDGE OR EFFORT. 3.
 THE FORCE REQUIRED TO OPERA TE THE DOOR SHALL NOT
 EXCEED 30 POUNDS (133 N) TO SET THE DOOR IN MOTION AND
 15 POUNDS (67 N) TO CLOSE THE DOOR OR OPEN IT TO THE
 MINIMUM REQUIRED WIDTH.
 4.THE DOOR SHALL BE OPENABLE WITH A FORCE NOT TO
 EXCEED 15 POUNDS (67 N) WHEN A FORCE OF 250 POUNDS
 (1100 N) IS APPLIED PERPENDICULAR TO THE DOOR ADJACENT
 TO THE OPERATING DEVICE.
 5.THE DOOR ASSEMBLY SHALL COMPLY WITH THE
 APPLICABLE FIRE PROTECTION RATING AND, WHERE RATED,
 SHALL BE SELF-CLOSING OR AUTOMATIC-CLOSING BY SMOKE
 DETECTION, SHALL BE INSTALLED IN ACCORDANCE WITH NFPA
 80 AND SHALL COMPLY WITH SECTION 715 .
 6.THE DOOR ASSEMBLY SHALL HAVE AN INTEGRATED
 STANDBY POWER SUPPLY.
 7.THE DOOR ASSEMBLY POWER SUPPLY SHALL BE
 ELECTRICALLY SUPERVISED.
 8.THE DOOR SHALL OPEN TO THE MINIMUM REQUIRED
 WIDTH WITHIN 10 SECONDS AFTER ACTIVATION OF THE
 OPERATING DEVICE.
 9.IN APARTMENT BUILDINGS, HOTELS AND DORMITORIES,
 HORIZONTAL SLIDING DOORS SHALL NOT BE USED ACROSS
 CORRIDORS.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]