2006-10-10 10:50:54***DENIED***
  
 1) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE AT
 LEAST 6" IN HEIGHT AND CONTRASTING TO THE BACKGROUND.
 NUMBER TO BE AT LEAST 1" IN WIDTH.
  
 2) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL.
  
 3) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 4) NFPA 13 AND NFPA 72 2003 EDITIONS.
  
 5) PLANS SHOW THE FDC BEING RELOCATED. THE CONNECTION
 SHALL BE LOCATED NOT FURTHER THAN 150' FROM A FIRE
 HYDRANT.
  
 6) DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A
 GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL
 REQUIREMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722