| Plan Review Notes For Permit 06070451 |
| Permit Number |
06070451 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2006-10-10 10:50:54 | ***DENIED*** | | | | | | 1) ADDRESS IS REQUIRED ON BUILDING THAT SHALL BE AT | | | LEAST 6" IN HEIGHT AND CONTRASTING TO THE BACKGROUND. | | | NUMBER TO BE AT LEAST 1" IN WIDTH. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM REMODEL. | | | | | | 3) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003 | | | EDITION. | | | | | | 4) NFPA 13 AND NFPA 72 2003 EDITIONS. | | | | | | 5) PLANS SHOW THE FDC BEING RELOCATED. THE CONNECTION | | | SHALL BE LOCATED NOT FURTHER THAN 150' FROM A FIRE | | | HYDRANT. | | | | | | 6) DUCT SMOKE DETECTOR INSTALLATIONS SHALL INITIATE A | | | GENERAL FIRE ALARM IN ACCORDANCE WITH LOCAL | | | REQUIREMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW (561) 805-6722 |
|