| 2006-08-08 00:00:00 | REVIEW IN PROGRESS |
| | *** UNSAT *** |
| | |
| | 1) NOTE: PLEASE SEE VALUE FOR PROPOSED |
| | SCOPE OF WORK IS WAY LOW. PLEASE KNOW |
| | VALUE FOR COMPLETE SCOPE OF WORK ON |
| | PLANS NEEDS TO BE ADJUSTED. PLEASE SEE |
| | VALUE BE BASED ON ALL LABOUR AND |
| | MATERIALS WHETHER OR NOT ANY EQUIPMENT, |
| | LIGHTING ETC IS OWNER SUPPLIED. |
| | FBC 108.3 ADMINISTRATIVE SECTION AS |
| | ADOPTED BY THE CITY OF WEST PALM BEACH. |
| | ** PLEASE ALSO PROVIDE THE DESCRIPTION |
| | ON APPLICATION FOR ACTUAL SCOPE OF WORK |
| | BEING PERFORMED AS THE DETAIL GIVEN |
| | SEEMS TO BE ABOUT THE SAME AS THE SHELL |
| | BLDG APPLICATION. |
| | ** NOTE FOR CONTRACTOR AND DOES NOT |
| | APPLY TO PLANS. |
| | |
| | 2) NOTE: PLEASE SEE PLANS SUBMITTED ARE |
| | NOT SIGNED, DATED OR SEALED BY ANY OF |
| | THE DESIGN PROFESSIONAL RESPONSEIBLE FOR |
| | DESIGNS ETC. THIS COMMENT IS FOR ALL |
| | TRADES AND ALL REVIEWS WHETHER OR NOT |
| | COMMENT IS MADE BY OTHER TRADES. |
| | FS 471.025, 481.221, FAC 61G15-23.002, |
| | 61G1-16 |
| | |
| | 3) NOTE: PLEASE BE SURE THE PLANS |
| | REFLECT THE FOLLOWING CODES AT A MINIMUM |
| | FOR ELECTRICAL REVIEW. |
| | 2002 NFPA-70(NEC), 2002 NFPA-72, 2003 |
| | NFPA-101 AND THE 2004 FBC. |
| | PLEASE SEE THERE ARE CODE ARTICLES |
| | REFERENCED ON PLANS WHICH ARE FROM THE |
| | 1996 NEC> |
| | PLEASE SEE REDLINED SET. |
| | |
| | 4) NOTE: PLEASE SEE THIS PLAN AND RISER |
| | IS SHOWING A NEW AND SEPARATE ELECTRICAL |
| | SERVICE WHICH DOES NOT CORRELATE WITH |
| | THE SHELL BUILDING PLANS. PLEASE REVISE |
| | RISER TOINCLUDE THE MAIN FEED FROM THE |
| | MAIN ELECTRICAL ROOM. |
| | PLEASE ALSO SEE ELECTRICAL PLANS SHOW |
| | 400A MAIN AND RISER SHOWS 600A. |
| | THIS IS ONE BUILDING AND THE SEPARATION |
| | PROVIDED IN THE ARCHITECTURAL AND |
| | STRUCTURAL PLANS DO NOT SEEM TO LEND TO |
| | THE DEFINITION OF A "BUILDING" WHICH |
| | WOULD CONTAIN A "FIRE WALL". PLEASE SEE DEFINITIONS OF |
| | "FIRE WALL". (4HR RATED |
| | AND ABLE TO COLLAPSE ON BOTHS SIDES |
| | WITHOUT AFFECT THE STRUCTURAL INTEGRITY |
| | OF THE OTHER STRUCTURE. |
| | PLEASE SEE 230.2, AND GRANTING OF AN |
| | ADDITIONAL SERVICE AT THIS TIME IS NOT |
| | GRANTED. |
| | |
| | 5) NOTE: PLEASE PLACE NOTE ON PLANS WITH |
| | NOTE #1 AS NOTED FOR PANEL SCHEDULES AND |
| | PROPOSED LOCK OFF DEVICES ON BRKRS. |
| | PLEASE KNOW ALL "LOCK-OFF/ON" DEVICES |
| | MUST BE AN INTEGRAL PART OF THE BREAKER |
| | AND NOT CAPABLE OF BEING REMOVED WITHOUT |
| | THE BREAKER BEING REMOVED. |
| | ** MANY OF THE PROPOSED DEVICES EASLIY |
| | FALL OFF WHEN REMOVING PANEL COVERS OR |
| | CAN BE READILY REMOVED. |
| | |
| | 6) NOTE: PLEASE SEE AND CLARIFY THE |
| | NUMBER OF CONDUCTORS ON THE LINE SIDE OF |
| | THE TRANSFORMER AS THE TRANSFORMER IS |
| | INDEED A SDS, AND A NEUTRAL CONDUCTOR |
| | WOULD NOT BE BROUGHT TO THIS EQUIPMENT. |
| | 250.6, 250.24B 230.50,250.20 ETC |
| | |
| | 7) NOTE: PLEASE SEE NOTE WHICH IS ADDED |
| | TO THE BOTTOM OF FIXTURE SCHEDULE |
| | MENTIONS "EM" STANDS FOR EMERGENCY |
| | FIXTURE, HOWEVER PLEASE INDICATE THE |
| | BATTERY BACK UP AND THE TIME. |
| | LS101 7.8, 7.9 |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE FBC CHAPTER 13. 13-413.1.ABC.1, |
| | PROVIDE A WORST CASE |
| | SCENERIO. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2, AND |
| | .1.3. |
| | PLEASE SEE 13-415.1.AB.1, |
| | 13-415.2.ABC.1, TABLES 415.2.C.1, AND |
| | 415.2.B.1 |
| | PLEASE ALSO SEE NO ENERGY CALCULATIONS |
| | WERE SUBMITTED FOR REVIEW. |
| | PLEASE SEE ALL OF CHAPTER 13 IN THE 2004 |
| | FBC. |
| | |
| | ** PLEASE SEE ANY OTHER COMMENTS FROM |
| | OTHER TRADES WHICH MAY AFFECT THE |
| | ELECTRICAL PLANS. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CONSTUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2006-08-07 00:00:00 | IN ELEC FOR REVIEW |