| 2006-08-15 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 06070445 |
| | ADD: 2015 OKEECHOBEE BLVD. |
| | CONT: BOCA DEVEL. & CONST. |
| | TEL: (561)391-6227 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | EX FBC CODE= 2004 EXISTING FLORIDA |
| | BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| | BER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| | TION PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| | YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | 2) FL S S 713.13 |
| | NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT BEFORE A |
| | PERMIT WILL BE ISSUED. NOTE: 713.13(2) |
| | IF THE WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS |
| | NOT ACTUALLY COMMENCED |
| | WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. |
| | |
| | 3) ARCHITECT STEVEN L. COHEN AR0006819 |
| | IS WORKING WITH A DELINGUENT LICENSE, |
| | EXPIRED 02/28/05. |
| | WWW.MYFLORIDA.COM/LICENSING |
| | |
| | 4) THE ARCHITECTURAL AS WELL AS THE MEP |
| | PLANS ARE NOT SIGNED NOR SEALED. |
| | PLANS, SPECIFICATIONS, REPORTS OR |
| | OTHER DOCUMENTS PREPARED BY THE DESIGN PROFESSIONAL AND |
| | BEING FILED FOR PUBLIC |
| | RECORD SHALL HAVE THE SIGNATURE AND |
| | SEAL OF THE DESIGN PROFESSIONAL AFFIXED |
| | TO THE DOCUMENT. |
| | FL STATE STAT: 61G15-23.002 ENGINEERS |
| | FL ATATE STAT: 61G16.003 ARCHITECTS |
| | |
| | 5) EX FBC 708.1 MINIMUM REQUIREMENTS. |
| | ALTERATIONS SUBJECT TOTHIS CHAPTER SHALL |
| | COMPLY WITH THE REQUIREMENTS OF CHAPTER |
| | 13 OF THE FBC, BUILDING. |
| | |
| | 6) EX FBC 706.1 A BUILDING, FACILITY OR |
| | ELEMENT THAT IS ALTERED SHALL COMPLY |
| | WITH CHAPTER 11 OF THE FBC BUILDING. |
| | SHEET A2 DOOR5/106 & 6/107 DO NOT MEET |
| | THE REQUIREMENTS OF 11-4.13.6 |
| | MANEUVERING CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| | CLEARANCES AT DOORS THAT ARE |
| | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE |
| | AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITH |
| | IN THE REQUIRED CLEARANCES SHALL BE |
| | CLEAR & LEVEL. |
| | |
| | 7) PROVIDE ADDITIONAL INFORMATION FOR |
| | A) SECURITY GRILLE LOCATED AT VESTIBULE |
| | B) VESTIBULE AUTO SLIDING DOORS |
| | LOCATED ON SHEET A2 & A5 |
| | 106.1.2* ADDITIONAL INFO. |
| | |
| | 8) SHEET A7 DETAIL# 16 FLOOR SLAB, |
| | PROIDE INFORMATION ON TERMITE TRATMENT. |
| | 1816.1 TERMITE PROTECTION. |
| | TERMITE PROTECTION SHALL BE PROVIDED BY |
| | REGISTERED TERMITICIDES, INCLUDING SOIL |
| | APPLIED PESTICIDES, BAITING SYSTEMS, AND PESTICIDES |
| | APPLIED TO WOOD, OR OTHER |
| | APPROVED METHODS OF TERMITE PROTECTION |
| | LABELED FOR USE AS A PREVENTATIVE |
| | TREATMENT TO NEW CONSTRUCTION. SEE |
| | SECTION 202 , REGISTERED TERMITICIDE. |
| | UPON COMPLETION OF THE APPLICATION OF |
| | THE TERMITE PROTECTIVE TREATMENT, A |
| | CERTIFICATE OF COMPLIANCE SHALL BE |
| | ISSUED TO THE BUILDING DEPARTMENT BY THE |
| | LICENSED PEST CONTROL COMPANY THAT |
| | CONTAINS THE FOLLOWING STATEMENT: ?THE |
| | BUILDING HAS RECEIVED A COMPLETE |
| | TREATMENT FOR THE PREVENTION OF |
| | SUBTERRANEAN TERMITES. TREATMENT IS IN |
| | ACCORDANCE WITH RULES AND LAWS |
| | ESTABLISHED BY THE FLORIDA DEPARTMENT OF AGRICULTURE |
| | AND CONSUMER SERVICES.? |
| | |
| | 9) SHEET A-3 NOTES 3-5 INDICATE THAT |
| | PLYWOOD TO BE APPLIED TO WALL ROOM |
| | FINISH NOTES. IS THIS A WALL FINISH OR |
| | INCASED IN THE WALL? |
| | 603.1 ALLOWABLE MATERIALS. |
| | COMBUSTIBLE MATERIALS SHALL BE PERMITTED |
| | IN BUILDINGS OF TYPE I OR II |
| | CONSTRUCTION IN THE FOLLOWING |
| | APPLICATIONS AND IN ACCORDANCE WITH |
| | SECTIONS 603.1.1 THROUGH 603.1.3 : |
| | 1.FIRE-RETARDANT-TREATED WOOD SHALL |
| | BE PERMITTED IN: |
| | 1.1.NONBEARING PARTITIONS WHERE THE |
| | REQUIRED FIRE-RESISTANCE RATING IS 2 |
| | HOURS OR LESS. |
| | 1.2.NONBEARING EXTERIOR WALLS WHERE |
| | NO FIRE RATING IS REQUIRED. |
| | TABLE 803.5 MERCANTILE OCCUPANCY |
| | SPRINKLERED FLAME SPREAD INDEX 76-200 |
| | SMOKE DEVELOPMENT 0-450. IF THE PLYWOOD |
| | IS TO BE A FINISHED WALL THEN PROVIDE |
| | THE FLAME SPREAD AND SMOKE DEVELOPMEENT. |
| | |
| | 10) A7 RESTROOMS SHOW COMPLIANCE WITH |
| | RESTROOM NONABSORBENT WALLS.PROVIDE |
| | MANUFACTURER INFORMATION.1210.2 WALLS. |
| | WALLS WITHIN 2 FEET (610 MM) OF URINALS |
| | AND WATER CLOSETS SHALL HAVE A SMOOTH, |
| | HARD, NONABSORBENT SURFACE, TO A HEIGHT |
| | OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND |
| | EXCEPT FOR STRUCTURAL ELEMENTS, THE |
| | MATERIALS USED IN SUCH WALLS SHALL BE OF |
| | A TYPE THAT IS NOT ADVERSELY AFFECTED BY MOISTURE. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |