Plan Review Notes
Plan Review Notes For Permit 06070451
Permit Number 06070451
Review Stop AD
Sequence Number 1
Notes
Date Text
2006-08-21 00:00:00ADDRESS ON THE APPLICATION 2035
 OKEECHOBEE BLVD BELONGS TO ROOMS RO GO
 KIDS , PLS CORRECT ADDR
2006-08-15 00:00:00BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2015 OKEECHOBEE BLVD.
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) ARCHITECT STEVEN L. COHEN AR0006819
 IS WORKING WITH A DELINGUENT LICENSE,
 EXPIRED 02/28/05.
 WWW.MYFLORIDA.COM/LICENSING
  
 4) PLANS ARE NOT SIGNED NOR SEALED
 ARCHITECTURALS OR MEP PLANS.
 PLANS, SPECIFICATIONS, REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 5) NOTE: A-1 PLANS INDICATE EXISTING
 PASSAGEWAY, TO BE COMPLETED UNDER THE
 SHELL PERMIT.
  
 6) EX FBC 708.1 ALTERATIONS SUBJECT TO
 THIS CHAPTER SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 13 OF THE FBC
 BUILDING.
  
 7) EX FBC 706.1 A BUILDING FACILITY, OR
 ELEMENT THAT IS ALTERED SHALL COMPLY
 WITH CHAPTER 11 OF THE FBC, BUILDING.
 SHEET A-2 DOORS 5/106 & 6/107 TO COMPLY
 WITH: 11-4.13.6 MANEUVERING CLEARENCES
 AT DOORS. MINIMUM MANEUVERING CLEARANCES
 AT DOORS THAT ARE NOT AUTOMATIC OR
 POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITH
 IN THE REQUIRED CLEARANCES SHALL BE
 CLEAR & LEVEL.
  
 8) A-2 AND A-5 BOTH INDICATE SOME TYPE
 OF SECURITY GRILL, PROVIDE ADDITIONAL
 INFORMATION, 106.1.2.
  
 9) A-2 AND A-5 BOTH INTERIOR AUTO DOORS
 PROVIDE NOTICE OF ACCEPTANCE.
  
 10) A7 DETAIL 16 DOESN'T INDICATE
 TERMITE TREATMENT:
 1816.1 TERMITE PROTECTION.
 TERMITE PROTECTION SHALL BE PROVIDED BY
 REGISTERED TERMITICIDES, INCLUDING SOIL
 APPLIED PESTICIDES, BAITING SYSTEMS, AND
 PESTICIDES APPLIED TO WOOD, OR OTHER
 APPROVED METHODS OF TERMITE PROTECTION
 LABELED FOR USE AS A PREVENTATIVE
 TREATMENT TO NEW CONSTRUCTION. SEE
 SECTION 202 , REGISTERED TERMITICIDE.
 UPON COMPLETION OF THE APPLICATION OF
 THE TERMITE PROTECTIVE TREATMENT, A
 CERTIFICATE OF COMPLIANCE SHALL BE
 ISSUED TO THE BUILDING DEPARTMENT BY THE
 LICENSED PEST CONTROL COMPANY THAT
 CONTAINS THE FOLLOWING STATEMENT: ?THE
 BUILDING HAS RECEIVED A COMPLETE
 TREATMENT FOR THE PREVENTION OF
 SUBTERRANEAN TERMITES. TREATMENT IS IN
 ACCORDANCE WITH RULES AND LAWS
 ESTABLISHED BY THE FLORIDA DEPARTMENT OF
 AGRICULTURE AND CONSUMER SERVICES.?
  
 11) A-3 NOTES 3,4 & 5 ALL INDICATE
 UNPAINTED PLYWOOD TO VARIOUS HEIGHTS.
 603.1 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED
 IN BUILDINGS OF TYPE I OR II
 CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH
 SECTIONS 603.1.1 THROUGH 603.1.3 :
 1.FIRE-RETARDANT-TREATED WOOD SHALL
 BE PERMITTED IN:
 1.1.NONBEARING PARTITIONS WHERE THE
 REQUIRED FIRE-RESISTANCE RATING IS 2
 HOURS OR LESS.
  
 12) PROVIDE ADDITIONAL INFORMATION HOW
 TO COMPLY WITH:1210.2 WALLS.
 WALLS WITHIN 2 FEET (610 MM) OF URINALS
 AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT
 OF 4 FEET (1219 MM) ABOVE THE FLOOR, AND
 EXCEPT FOR STRUCTURAL ELEMENTS, THE
 MATERIALS USED IN SUCH WALLS SHALL BE OF
 A TYPE THAT IS NOT ADVERSELY AFFECTED BY
 MOISTURE.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
2006-08-10 00:00:00PROJECT UNDER REVIEW.FIELD VERIFICATION
 IS NEEDED,