| 2007-04-22 14:22:03 | |
| | **** UNSAT3RD REVIEW**** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN QUESTION. |
| | |
| | ** PLEASE SEE NOTES FOR TENANT BUILD OUT AS |
| | COORDINATION FROM BUILD PLANS AND SHELL PLANS NEED TO |
| | BE ADDRESSED. |
| | |
| | ** PLEASE SEE THE RESPONSE LETTER IN PACKAGE ALTHOUGH |
| | NOT REQUIRED IS THAT OF THE SAME RESPONSE LETTER WHICH |
| | WAS IN THE BUILD OUT PLANS FOR TENANT. NO RESPONSE |
| | LETTER COULD BE FOUND FOR THIS REVIEW FOR ELECTRICAL. |
| | |
| | |
| | 1) NOTE:PLEASE SEE PLANS STILL MENTION A 2003-2004 |
| | FBC. THIS IS NOT POSSIBLE AS PREVIOUSLY NOTED. THERE IS |
| | NOT 2003 FBC AND THIS PROJECT IS PERMITTED UNDER THE |
| | 2004 FBC W/ 2005 REVISIONS. |
| | |
| | 2) NOTE: PLEASE EXPLAIN HOW LIGHTING ETC IS BEING SHOWN |
| | FOR SPACE/BAY #2 YET THE TENANT BUILD OUT IS |
| | SUBMITTED? |
| | PLEASE SEE THAT BAY #2 IS MISSING CIRCUITING FOR |
| | LIGHTING. |
| | PLEASE SEE THE LIGHTING IN ENERGY CALCULATIONS DO NOT |
| | CORRELATE WITH THE PLANS OR THE BUILD OUT PLANS. |
| | PLEASE SEE FBC CHAPTER 13. PLEASE SEE 13-415.1.AB.1, |
| | AND 13-415.2 AS A METHOD C ENERGY CALCULATION THAT WAS |
| | SUBMITTED IS THE SAME OF THAT SUBMITTED ON PREVIOUS |
| | REVIEW AND NOT CHANGES WERE MADE. |
| | PLEASE ALSO SEE THE ENERGY CALCULATIONS NEED TO |
| | CORRELATE WITH THE ELECTRICAL PLANS FOR THE AMOUNT OF |
| | FIXTURES AND TYPES OF CONTROLS. PLEASE SEE THESE |
| | INDICATE 400 AND 270 FIXTURES AND MANUAL ON/OFF |
| | CONTROLS. PLEASE SEE 13-415.2.ABC.1.3, |
| | 13-415.1.ABC.1.4. |
| | PLEASE SEE FBC CHAPTER 13. PLANS DENOTE THESE AS |
| | *RENOVATED SPACES*. HOW IS THIS POSSIBLE AS IS DOES NOT |
| | FALL UNDER THE DEFINITION OF RENOVATED AND ALSO THE |
| | CHANGE IN OCCUPANCY. |
| | |
| | 3) NOTE: PLEASE SEE THE VOLTAGE DROP CALCULATIONS WERE |
| | NOT SUBMITTED AND DO NOT CORRELATE WITH THE BUILD OUT |
| | PLANS. PLEASE SEE THE DISTANCE OF FEEDERS FROM BAY 2 |
| | AND BAY 3 DO NOT SEEM TO COMPLY WITH PLANS PROVIDE |
| | WORST CASE VOLTAGE DROP SCENARIOS FOR BRANCH CIRCUITS |
| | AND FEEDERS PER 13-413.1ABC.1/13-413.1.ABC.1.1, .1.2. |
| | PLEASE SEE PLANS AS BASED ON THE SCALE PROVIDED ON |
| | PLANS AND SITE VISIT, THE DISTANCE IS 300FT +/- TO BAY |
| | #3 ALONE. |
| | |
| | 4) NOTE: PLEASE SEE WHAT APPEARS TO BE A MISPRINT FOR |
| | THE DESIGNATION OF THE MAIN SWITCH BOARD. RISER SHOWS |
| | MSB AND PLANS SHOWS MSD. |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SEE NO DETAIL SUBMITTED FOR CONNECTION |
| | OR HOW OC DEVICES WILL BE WIRED WITH LIGHTING. POWER |
| | PACKS, LOW VOLTAGE ETC? |
| | 13-415.1.ABC.1.1, .1.2. |
| | NEC 110.3 |
| | FBC 106.1.2 |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |