| 2007-06-15 10:14:54 | BUILDING PLAN REVIEW |
| | PERMIT: 06070445 |
| | ADD: 2029 OKEECHOBEE BLVD |
| | CONT: BOCA DEVEL & CONST |
| | TEL: (954) 5886695 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 3RDREVIEW |
| | ACTION: DENIED |
| | |
| | 1)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 2)) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE |
| | FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF |
| | THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| | NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| | RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| | 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| | THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) NEW COMMENT: SINCE THE LAST COMMENT THE SCOPE OF |
| | WORK HAS CHANGED, THAT THE EXISTING ROOF WAS REMOVED |
| | AND THAT THE WALLS,COLUMNS, FLOOR AND FOOTING/ |
| | FOUNDATIONS HAVE ALL BEEN REMOVED |
| | FOR THIS PORTION OF THE BUILDING BAY 1,2& 3. SHEET A1.2 |
| | STE DATAUNDER TYPE OF CONSTRUCTION : LIST TO MATCH |
| | EXISTING CONSTRUCTION? THE FOLLOWING ARE ITEMS REQUIRED |
| | TO BE ON THE PLAN BEFORE ISSUANCE: |
| | 3A) (1)110.2* W. P. B. ADMINISTRATIVE CODE, |
| | INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR |
| | CERTIFICATE OF OCCUPANCY: |
| | (2) THE EDITION OF THE CODE UNDER WHICH THE |
| | PROJECT WAS DESIGNED. |
| | 2004/2005 FBC- BUILDING AND THE 2004/2005 |
| | FBC EXISTING BUILDING CODE, WHAT LEVEL OF ALTERATION: |
| | LEVEL 3, THIS IS NOW AN ADDITION TO THE BASE BUILDING. |
| | B) THE USE AND OCCUPANCY, IN |
| | ACCORDANCE WITH THE PROVISIONS OF CHAPTER |
| | 3. |
| | (3)THE TYPE OF CONSTRUCTION AS DEFINED IN |
| | CHAPTER 6, TABLE 601. |
| | (4)THE OCCUPANT LOAD, SEE 1004. |
| | (5)IF AN AUTOMATIC SPRINKLER SYSTEM IS |
| | PROVIDED, WHETHER THE SPRINKLER SYSTEM IS REQUIRED. (6) |
| | ANY SPECIAL STIPULATIONS & CONDITIONS OF THE BUILDING |
| | PERMIT. |
| | (7) SQ. FT. FOOTPRINT |
| | |
| | 3B) FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR |
| | RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA, |
| | DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT |
| | INSPECTOR PROGRAM IS REQUIRED, |
| | ON THIS PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: X |
| | - BUILDINGS/ADDITIONS OF TYPE I OR II |
| | CONSTRUCTION |
| | - ANY MAJOR STRUCTURAL ALTERATIONS |
| | - STRUCTURES IN WHICH THE CONCRETE |
| | DESIGN IS BASED ON COMPRESSIVE |
| | STRENGTH (F'C) IN EXCESS OF 3000 PSI |
| | - PILE DRIVING |
| | - BUILDINGS OVER 20,000 SQFT IN AREA |
| | - BUILDINGS OVER 2 STORIES IN HEIGHT |
| | - BUILDING/STRUCTURES OF UNUSUAL DESIGN |
| | OR METHODS OF CONSTRUCTION |
| | |
| | 3C)SINCE THIS BUILDING WILL REQUIRE A RESIDENT |
| | INSPECTOR ,(3) OF ALL DOCUMEENTS WILL BE REQUIRED TO |
| | BE SUBMITTED TO THE CITY. |
| | |
| | 4)SUBMITTED ARE 2 ORIGINAL SIGNED AND SEALED SOILS |
| | REPORTS, NOW (3) WILL BE REQUIRED. |
| | |
| | 5) NOT REQUIRED, AS THE ROOF DECK AND BAR JOIST HAVE |
| | BEEN REMOVED. |
| | |
| | 6) COMPLIED. SURVEYS SHOW A NEW UTILITY EASEMENT. |
| | |
| | 7)3RD REQUEST, TABLE 602, DEALS WITH THE BUILDING NOT |
| | TO TRANSGRESS ACROSS PROPERTY LINES. COMMENTS |
| | FROM THE LAST REVIEW INDICATE THE OWNERS ARE PROCEEDING |
| | TOWARDS SECURING A UNITY OF TITLE. PLEASE PROVIDE A |
| | COPY OF THE RECORDEDNOTICE |
| | OF COMMENCEMENT WITH THE CLERK OF THE COURT. |
| | |
| | 8) COMMENT#(10) FROM THE PREVIOUS REVIEW, DEALS WITH |
| | CHARTER 13 ENERGY, ONE BIG CHANGE IN THE CODE DEALS |
| | WITH ELECTRICAL |
| | COMMENT# 3, AUTOMATIC LIGHTING CONTROLS, FBC |
| | 12-415.1.ABC 1.1, 1.2. |
| | |
| | 9)3RDREQUEST COMMENT# 11 FROM THE PREVIOUS REVIEW, |
| | DEALS WITH THE STRUCTURAL CALCULATIONSDESIGNED TO ASCE |
| | 7-98 VS. THE STRUCTURAL PLANS DESIGNED TO ASCE 7-02. |
| | RESPONCE COMMENTS REFER TO STRUCTURAL ANALYSIS? PLEASE |
| | ELABORATE WHERE THIS DOCUMENT COULD BE FOUND? |
| | |
| | 10-12) COMPLIED. |
| | |
| | 13) COMMENT# 16 FROM THE 1ST REVIEW, |
| | FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) STOREFRONT SYSTEMS/ MULLIONS |
| | B) GLAZED SWING DOORS |
| | C) ROOF ASSEMBLIES- HIGHLIGHT WHICH SUB-SYSTEM TO BE |
| | INSTALLED SEE IF LIMITATION 7 OR 9 IS INVOLED! |
| | D) PREMANUFACTURED METAL A/C STANDS |
| | E) METAL BAHAMA SHUTTERS SEE NOTE!16 |
| | |
| | 14) COMMENT# 17FROM THE PREVIOUS REVIEW, |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 15) COMMENT# 18FROM THE PREVIOUS REVIEW, |
| | W P B ADMINISTRTIVE CODE 106.3.3* |
| | PRODUCT APPROVALS. THOSE PRODUCTS WHICH |
| | ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 16) 2ND REQUEST, COMMENT# 19 FROM THE PREVIOUS REVIEW, |
| | METAL BAHAMA SHUTTERS- TO BE INSTALLED IN THE FIXED |
| | OPEN POSITION, SHUTTERS WILL REQUIRE ENGINEERING IN THE |
| | OPEN POSITION. THIS SYSTEM WILL NOT |
| | REQUIRE FL COVERSHEET. PLEASE PROVIDE ADDITIONAL |
| | DOCUMENTATION FROM AN ENGINEER SHOWING THAT THEY WILL |
| | WITHSTAND 140 MPH WIND IN THE OPEN POSITION. THEY ARE |
| | DESIGNED TAND TESTED IN THE CLOSED POSITION. |
| | |
| | BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |
| | E-MAIL: [email protected] |
| | |