Plan Review Notes
Plan Review Notes For Permit 06070445
Permit Number 06070445
Review Stop B
Sequence Number 3
Notes
Date Text
2007-06-15 10:14:54BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2029 OKEECHOBEE BLVD
 CONT: BOCA DEVEL & CONST
 TEL: (954) 5886695
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 3RDREVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 2)) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE
 FILED WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF
 THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) NEW COMMENT: SINCE THE LAST COMMENT THE SCOPE OF
 WORK HAS CHANGED, THAT THE EXISTING ROOF WAS REMOVED
 AND THAT THE WALLS,COLUMNS, FLOOR AND FOOTING/
 FOUNDATIONS HAVE ALL BEEN REMOVED
 FOR THIS PORTION OF THE BUILDING BAY 1,2& 3. SHEET A1.2
 STE DATAUNDER TYPE OF CONSTRUCTION : LIST TO MATCH
 EXISTING CONSTRUCTION? THE FOLLOWING ARE ITEMS REQUIRED
 TO BE ON THE PLAN BEFORE ISSUANCE:
 3A) (1)110.2* W. P. B. ADMINISTRATIVE CODE,
 INFORMATION THAT IS REQUIRED FOR RECORD KEEPING & FOR
 CERTIFICATE OF OCCUPANCY:
 (2) THE EDITION OF THE CODE UNDER WHICH THE
 PROJECT WAS DESIGNED.
 2004/2005 FBC- BUILDING AND THE 2004/2005
 FBC EXISTING BUILDING CODE, WHAT LEVEL OF ALTERATION:
 LEVEL 3, THIS IS NOW AN ADDITION TO THE BASE BUILDING.
 B) THE USE AND OCCUPANCY, IN
 ACCORDANCE WITH THE PROVISIONS OF CHAPTER
 3.
 (3)THE TYPE OF CONSTRUCTION AS DEFINED IN
 CHAPTER 6, TABLE 601.
 (4)THE OCCUPANT LOAD, SEE 1004.
 (5)IF AN AUTOMATIC SPRINKLER SYSTEM IS
 PROVIDED, WHETHER THE SPRINKLER SYSTEM IS REQUIRED. (6)
 ANY SPECIAL STIPULATIONS & CONDITIONS OF THE BUILDING
 PERMIT.
 (7) SQ. FT. FOOTPRINT
  
 3B) FBC* 105.3RESIDENT INSPECTOR. SUBMIT INSPECTOR
 RESUME' AND LICENSE DOCUMENTS TO HAROLD PISKURA,
 DIRECTOR OF THE RESIDENT INSPECTOR PROGRAM.A RESIDENT
 INSPECTOR PROGRAM IS REQUIRED,
 ON THIS PROJECT, DUE TO ONE OR MORE OF THE FOLLOWING: X
 - BUILDINGS/ADDITIONS OF TYPE I OR II
 CONSTRUCTION
 - ANY MAJOR STRUCTURAL ALTERATIONS
 - STRUCTURES IN WHICH THE CONCRETE
 DESIGN IS BASED ON COMPRESSIVE
 STRENGTH (F'C) IN EXCESS OF 3000 PSI
 - PILE DRIVING
 - BUILDINGS OVER 20,000 SQFT IN AREA
 - BUILDINGS OVER 2 STORIES IN HEIGHT
 - BUILDING/STRUCTURES OF UNUSUAL DESIGN
 OR METHODS OF CONSTRUCTION
  
 3C)SINCE THIS BUILDING WILL REQUIRE A RESIDENT
 INSPECTOR ,(3) OF ALL DOCUMEENTS WILL BE REQUIRED TO
 BE SUBMITTED TO THE CITY.
  
 4)SUBMITTED ARE 2 ORIGINAL SIGNED AND SEALED SOILS
 REPORTS, NOW (3) WILL BE REQUIRED.
  
 5) NOT REQUIRED, AS THE ROOF DECK AND BAR JOIST HAVE
 BEEN REMOVED.
  
 6) COMPLIED. SURVEYS SHOW A NEW UTILITY EASEMENT.
  
 7)3RD REQUEST, TABLE 602, DEALS WITH THE BUILDING NOT
 TO TRANSGRESS ACROSS PROPERTY LINES. COMMENTS
 FROM THE LAST REVIEW INDICATE THE OWNERS ARE PROCEEDING
 TOWARDS SECURING A UNITY OF TITLE. PLEASE PROVIDE A
 COPY OF THE RECORDEDNOTICE
 OF COMMENCEMENT WITH THE CLERK OF THE COURT.
  
 8) COMMENT#(10) FROM THE PREVIOUS REVIEW, DEALS WITH
 CHARTER 13 ENERGY, ONE BIG CHANGE IN THE CODE DEALS
 WITH ELECTRICAL
 COMMENT# 3, AUTOMATIC LIGHTING CONTROLS, FBC
 12-415.1.ABC 1.1, 1.2.
  
 9)3RDREQUEST COMMENT# 11 FROM THE PREVIOUS REVIEW,
 DEALS WITH THE STRUCTURAL CALCULATIONSDESIGNED TO ASCE
 7-98 VS. THE STRUCTURAL PLANS DESIGNED TO ASCE 7-02.
 RESPONCE COMMENTS REFER TO STRUCTURAL ANALYSIS? PLEASE
 ELABORATE WHERE THIS DOCUMENT COULD BE FOUND?
  
 10-12) COMPLIED.
  
 13) COMMENT# 16 FROM THE 1ST REVIEW,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT SYSTEMS/ MULLIONS
 B) GLAZED SWING DOORS
 C) ROOF ASSEMBLIES- HIGHLIGHT WHICH SUB-SYSTEM TO BE
 INSTALLED SEE IF LIMITATION 7 OR 9 IS INVOLED!
 D) PREMANUFACTURED METAL A/C STANDS
 E) METAL BAHAMA SHUTTERS SEE NOTE!16
  
 14) COMMENT# 17FROM THE PREVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 15) COMMENT# 18FROM THE PREVIOUS REVIEW,
 W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 16) 2ND REQUEST, COMMENT# 19 FROM THE PREVIOUS REVIEW,
 METAL BAHAMA SHUTTERS- TO BE INSTALLED IN THE FIXED
 OPEN POSITION, SHUTTERS WILL REQUIRE ENGINEERING IN THE
 OPEN POSITION. THIS SYSTEM WILL NOT
 REQUIRE FL COVERSHEET. PLEASE PROVIDE ADDITIONAL
 DOCUMENTATION FROM AN ENGINEER SHOWING THAT THEY WILL
 WITHSTAND 140 MPH WIND IN THE OPEN POSITION. THEY ARE
 DESIGNED TAND TESTED IN THE CLOSED POSITION.
  
 BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026