Plan Review Notes
Plan Review Notes For Permit 06070445
Permit Number 06070445
Review Stop E
Sequence Number 2
Notes
Date Text
2007-01-14 15:19:39 
  
 **** UNSAT2ND REVIEW****
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN QUESTION. PLEASE SEE SOME ARE NEW BASED ON THE
 REVISED PLANS SUBMITTED.
  
 PLEASE SEE THE COMMENTS BELOW ARE TAKEN DIRECTLY FROM
 THE PREVIOUS REVIEW WITH AN ANSWERS OF OK, NO OR
 OK/NO.
  
 OK, WILL SHOW THE PREVIOUS NOTE REMOVED.
 NO, WILL CONTAIN FURTHER EXPLANATION OF THE PREVIOUS
 NOTE.
 NO/OK, IS THAT PART OF THE COMMENT MAY NOT HAVE BEEN
 ADDRESSED FULLY AND WILL BE FOLLOWED BY FURTHER
 EXPLANATION.
  
 ** PLEASE SEE THAT ANY NEW NOTES WILL BE ADDED TO THE
 END OF THESE REVIEW NOTES AND WILL BE SEPARATED WITH
 *** NEW NOTES 2ND REVIEW ***
  
 1) NOTE:NO, PLEASE SEE THE RESPONSE MENTIONS THIS IS
 SUBMITTED AND IS LOCATE DON E00. PLEASE SEE ONLY A
 LIGHT POLE DETAIL WAS SUBMITTED. NO REFERENCE TO WIND
 LOADS, RATINGS, EPA OF FIXTURES ETC.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SUBMIT WIND LOADING CALCULATIONS FOR NEW LT
 POLES. IF THESE ARE NOT GOING TO BE UNDER THIS PERMIT,
 THEN THE CALCULATIONS MAY BE SUBMITTED WITH A SEPARATE
 PERMIT APPLICATION FEES AND PLANS AT A LATER DATE. FBC
 106.1.2
  
 2) NOTE:NO/OK. PLEASE SEE SOME OF THESE WERE ADDED
 HOWEVER PLEASE SEE PLANS ON E-2 WHICH INDICATES THE
 2003-2004 FBC. PLEASE SEE THIS IS NOT POSSIBLE. IT
 SEEMS TO HAVE BEEN A MISPRINT AS NO REFERENCE TO THE
 2003 NFPA-101 WAS MADE.
 PLEASE COMPLETE AND CORRELATE AS NOTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE BE SURE THE PLANS REFLECT THE FOLLOWING CODES AT
 A MINIMUM.
 2002 NFPA-70, 2002 NFPA-72, 2003 NFPA-101.
 2004 FBC.
  
 3) NOTE:NO, PLEASE SEE NO TIMES OR DETAILS FOR THESE
 DEVICES WAS NOTED OR SHOWN. PLEASE SEE MAXIMUMS TIMES
 PERMITTED SHALL BE STATED. (30 MINS FOR OC TYPE DEVICE
 AND 4HRS ON ANY TIMER TYPE DEVICES).PLEASE ALSO SEE
 TIME DEVICE SHOWN ON PLANS, BUT NOT IN SYMBOL LEGEND
 ETC. PLEASE SEE NEW NOTES PERTAINING TO THE ENERGY
 CALCULATIONS SUBMITTED.
  
 ** PREVIOUS REVIEW NOTE **
 PLEASE SEE AUTOMATIC LIGHTING CONTROLS FOR SHUTTING OFF
 OF LIGHTING IS REQUIRED PER FBC CHAPTER 13
 13-415.1.ABC.1.1, .1.2
  
 4) NOTE: OK. ? THIS WAS A COMMENT FOR BUILDING/FIRE
 REVIEW WHICH WAS ONLY NOTED.
  
 5) NOTE: OK.
  
 6) NOTE: OK, HOWEVER SEE NEW NOTES.
  
 7) NOTE: OK.
  
 8) NOTE: OK.
  
 9) NOTE:NO, PLEASE SEE THE RISER HAS REMOVED THIS
 HOWEVER PLEASE SEE THE MSB BOARD WHICH STILL INDICATES
 AND EQUIPMENT GROUNDING IN THE FEEDERS WHICH IS NOT
 PERMITTED 250.6, 250.24B. PLEASE KNOW THAT THESE ARE
 ACTUALLY SERVICE ENTRANCE CONDUCTORS. PLEASE SEE NEC
 ART 100 DEFINITIONS AS THESE ARE NOT FEEDERS.
  
 ** PREVIOUS REVIEW NOTE** PLEASE SEE RISER SHOWS AN
 EQUIPMENT GROUNDING CONDUCTOR BEFORE THE FIRST MEANS OF
 DISCONNECT FROM FPL.
 PLEASE SEE 250.6, 250.24B AS "EQUIPMENT GROUNDING
 CONDUCTORS" ARE ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
  
 *** NEW NOTES ****
  
 10) NOTE: PLEASE SEE FBC CHAPTER 13. PLEASE SEE
 13-415.1.AB.1, AND 13-415.2 AS A METHOD C ENERGY
 CALCULATION WAS SUBMITTED WHICH COULD NOT BE USED BASED
 ON THE SCOPE OF WORK BEING DONE.
 PLEASE ALSO SEE THE ENERGY CALCULATIONS NEED TO
 CORRELATE WITH THE ELECTRICAL PLANS FOR THE AMOUNT OF
 FIXTURES AND TYPES OF CONTROLS. PLEASE SEE THESE
 INDICATE 400 FIXTURES AND MANUAL ON/OFF CONTROLS.
 PLEASE SEE 13-415.2.ABC.1.3, 13-415.1.ABC.1.4.
  
 11) NOTE: PLEASE SEE MAIN ELECTRICAL ROOM WHICH
 INDICATES A METER BELOW A DISCONNECT WHICH WILL MOST
 LIKELY NOT MEET 110.26 FOR CLEAR SPACE AND EQUIPMENT
 BEING ABLE TO BE LOCATED 6INCHES OUT.
  
 12) NOTE: PLEASE SEE ADDRESS ON PLANS IS NOT CORRECT
 BASED ON THE LOCATION AND SCOPE OF WORK FOR SHELL AS
 SHOWN. PLEASE SEE BUILDING REVIEW COMMENTS AS WELL AS
 THE COMMENTS FROM THE ADDRESSING REVIEWER.
  
 13) NOTE: PLEASE PROVIDE WORST CASE VOLTAGE DROP
 SCENARIOS FOR BRANCH CIRCUITS AND FEEDERS PER
 13-413.1ABC.1/13-413.1.ABC.1.1, .1.2.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717