2007-01-12 14:12:16BUILDING PLAN REVIEW
 PERMIT: 06070445
 ADD: 2029 OKEECHOBEE BLVD. (SHELL PERMIT)
 CONT: BOCA DEVEL. & CONST.
 TEL: (561)391-6227
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 EX FBC CODE= 2004 EXISTING FLORIDA
 BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 2ND REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT BEFORE A
 PERMIT WILL BE ISSUED. NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLY COMMENCED
 WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID.
  
 3) SEE ADDRESSING COMMENT FROM THE FIRST REVIEW, THE
 ADDRESS TO BE USED FOR THIS SHELL PERMIT IS 2029
 OKEECHOBEE BLVD.2029 SHOULD BE USED
 ON ALL PLANS, PERMIT APPLICATION & ANY SUBMITTALS.
  
 4) COMPLIED.
  
 5) WILL BE A BUILDING PROVISO:
 ENGINEER OF RECORD IRVING ABCUGTO SHALL
 SUBMIT A SHORING PLAN PRIOR TO THE REMOVAL OF ANY
 BEARING COMPONENTS.
  
 6) COMPLIED. SURVEYS SHOW A NEW UTILITY EASEMENT.
  
 7)TABLE 602, DEALS WITH THE BUILDING NOT TO
 TRANSGRESS ACROSS PROPERTY LINES. COMMENTS
 FROM THE LAST REVIEW INDICATE THE OWNERS ARE PROCEEDING
 TOWARDS SECURING A UNITY OF TITLE. PLEASE PROVIDE A
 COPY OF THE RECORDEDNOTICE
 OF COMMENCEMENT WITH THE CLERK OF THE COURT.
  
 8) COMMENT#(10) FROM THE PREVIOUS REVIEW, DEALS WITH
 CHARTER 13 ENERGY, ONE BIG CHANGE IN THE CODE DEALS
 WITH ELECTRICAL
 COMMENT# 3, AUTOMATIC LIGHTING CONTROLS, FBC
 12-415.1.ABC 1.1, 1.2.
  
 9)2ND REQUEST COMMENT# 11 FROM THE PREVIOUS REVIEW,
 DEALS WITH THE STRUCTURAL CALCULATIONSDESIGNED TO ASCE
 7-98 VS. THE STRUCTURAL PLANS DESIGNED TO ASCE 7-02.
 RESPONCE COMMENTS REFER TO STRUCTURAL ANALYSIS? PLEASE
 ELABORATE WHERE THIS DOCUMENT COULD BE FOUND?
  
 10) 2ND REQUEST, COMMENT 13A & 13B:
 10A) (13A) A1.3 SITE PLAN DETAIL A8.1.1DETAIL NUMBER 3,
 PLANS DO NOT PROVIDE THE WIDTH
 OF THE CURB CUT. PLEASE PROVIDE DETAILS INDICATING
 COMPLIANCE WITH
 CURB CUTS AS USED WITH THIS PLAN.
  
 10B)2ND REQUEST(13C) THE CROSS WALKS THAT LEAD FROM
 THE
 DEISABLED PARKING SPACE TO THE STORES
 DOES NOT LEAD TO THE STORE FRONTS WHERE
 THE COVERED ENTRY IS LOCATED BUT TO A
 SIDEWALK WITH A MUCH SMALLER CANOPY AND
 A FURTHER DISTANCE TO THE STORE FRONT.
 11-2.2 EQUIVALENT FACILITATION.
 RESPONCE INDICATES A NEW SECTION
 BUT THE SECTION DOESN,T SHOW ANY CURB CUTS?
  
 11) 2ND REQUEST, PLANS COMMENT NUMBER (14A) FROM THE
 PREVIOUS REVIEW:
 I SPOKE WITH THE ARCHITECT ABOUT THIS SITUATION, A
 NARRATIVE MAY BE HELPFUL IN INDICATING COMPLIANCE, A1.2
 SITE PLAN INDICATES THE NEW
 CURB CUTS ACCESS AISLES, NEW LANDSCAPE
 AND NEW LANDSCAPED ISLAND. EX FBC 706
 A BUILDING, FACILITY OR ELEMENT THAT IS
 ALTERED SHALL COMPLY WITH CHAPTER 11 OF
 THE FBC, BUILDING.
 11-4.6.2(1) ALL PARKING SPACES MUST
 BE LOCATED ON AN ACCESSIBLE ROUTE NO
 LESS THAN 44 INCHES (1118 MM)WIDE SO
 THAT USERS WILL NOT BE COMPELLED TO WALK
 OR WHEEL BEHIND PARKED VEHICLES
 THIS PLAN DOES NOT PROVIDE THE
 DISABLED ACCESS TO THE SSTORES WITHOUT
 TRAVELING BEHIND SOMEONE ELSES PARKED
 VEHICLE.
 NOTE, 11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
 PLEASE PROVIDE AN ALYSIS OF MONIES
 SPENT TO MEET THE 20% OF CONTRACT VALUE.
  
 12) 2ND REQUEST COMMENT# (14B) FROM THE PREVIOUS
 REVIEW,
 14B) THE SECOND ISSUE IS THE CROSS WALKS
 AND HANDICAPPED ACCESS
 AISLES,11-4.6.2(1) SO THAT NO USER WILL
 NOT BE COMPELLED TO WALK OR WHEEL BEHIND
 PARKED VEHICLES.
 A1.1.3 THE DEMO PLAN DOESN'T
 INDICATE THE SITE AS IS NOW.
 11-4.1.6(1)
 GENERAL. ALTERATIONS TO EXISTING
 BUILDINGS AND FACILITIES SHALL COMPLY
 WITH THE FOLLOWING:
 (A)NO ALTERATION SHALL BE
 UNDERTAKEN WHICH DECREASES OR HAS THE
 EFFECT OF DECREASING ACCESSIBILITY OR
 USABILITY OF A BUILDING OR FACILITY
 BELOW THE REQUIREMENTS FOR NEW
 CONSTRUCTION AT THE TIME OF ALTERATION.
 (B)IF EXISTING ELEMENTS, SPACES, OR
 COMMON AREAS ARE ALTERED, THEN EACH SUCH
 ALTERED ELEMENT, SPACE, FEATURE, OR AREA
 SHALL COMPLY WITH THE APPLICABLE
 PROVISIONS OF SECTION 11-4.1.1 TO
 SECTION 11-4.1.3 , MINIMUM REQUIREMENTS
 FOR NEW CONSTRUCTION. IF THE APPLICABLE
 PROVISION FOR NEW CONSTRUCTION REQUIRES
 THAT AN ELEMENT, SPACE, OR COMMON AREA
 BE ON AN ACCESSIBLE ROUTE, THE ALTERED
 ELEMENT, SPACE, OR COMMON AREA IS NOT
 REQUIRED TO BE ON AN ACCESSIBLE ROUTE
 EXCEPT AS PROVIDED IN SECTION 11-4.1.6
 (2), ALTERATIONS TO AN AREA CONTAINING A
 PRIMARY FUNCTION.
  
 13) COMMENT# 16 FROM THE 1ST REVIEW,
 FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) STOREFRONT SYSTEMS/ MULLIONS
 B) GLAZED SWING DOORS
 C) EXTERIOR METAL SWING DOORS
 D)ROLL UP DOORS
 E)LOUVERS
 F) ROOF ASSEMBLIES
 G) PREMANUFACTURED METAL A/C STANDS
 H) METAL BAHAMA SHUTTERS SEE NOTE!
  
 14) COMMENT# 17FROM THE PREVIOUS REVIEW,
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 15) COMMENT# 18FROM THE PREVIOUS REVIEW,
 W P B ADMINISTRTIVE CODE 106.3.3*
 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 16) 2ND REQUEST, COMMENT# 19 FROM THE PREVIOUS REVIEW,
 METAL BAHAMA SHUTTERS- TO BE
 INSTALLED IN THE FIXED OPEN POSITION,
 SHUTTERS WILL REQUIRE ENGINEERING IN THE
 OPEN POSITION. THIS SYSTEM WILL NOT
 REQUIRE FL COVERSHEET.
  
 17)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  