Plan Review Notes
Plan Review Notes For Permit 06070445
Permit Number 06070445
Review Stop P
Sequence Number 1
Notes
Date Text
2006-10-13 07:50:45DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL ARCHITECTURAL SHEETS. THE CERTIFICATE OF
 AUTHORIZATION NUMBER, (BUSINESS NUMBER), IS SHOWN AS
 DELINQUENT STATUS FOR THE ARCHITECTURAL BUSINESS. SEE
 ATTACHED SHEET. FAC 61G1-16.004(1) & FS 481.219.
  
 2. SHT A1.1.4 IN THE REMOVAL OF ANY PART OF A SANITARY
 SYSTEM, DEAD ENDS ARE PROHIBITED. SECTION 704.5. ALL
 CAPPED PIPES SHALL NOT BE COVERED PRIOR TO INSPECTION.
  
 3. SHT A2.2 SUBMIT CALCULATIONS FOR PRIMARY AND
 SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL
 SUBSECTIONS. THIS IS FOR THE NEW ROOFS AND THE EXISTING
 ROOFS THAT HAVE ADDITIONAL ROOF AREA OR VERTICAL
 CONTRIBUTION ADDED TO TOTAL AREA TO BE DRAINED.
 CALCULATIONS SHALL SHOW THE ROOF AREA TO BE DRAINED TO
 EACH PRIMARY DRAIN, ALONG WITH 1/2 AREA OF ALL VERTICAL
 WALLS, INCLUDING PARAPETS, AS WELL AS ANY AREA OF A
 ROOF THAT DRAINS ONTO THE ROOF FROM ABOVE. INDICATE NEW
 ROOF AREA ADDED, AS THE "NEW ROOF" MAY JUST BE A NEW
 ROOF FOR EXISTING AREA AND SOME AREAS OF THE "NEW ROOF
 AREA" ARE NOT CLEAR. SECTION 106.1.1.
  
 4. SHT A2.2 EXISTING SCUPPER LOCATED AT THE S.E. CORNER
 OF THE EXISTING BAY 2 ROOF IS NOT APPROVED FOR
 EMERGENCY OVERFLOW FOR THAT ROOF DRAIN, NOR FOR THE NEW
 ROOF DRAIN COVERING THE WALKWAY EAST OF EXISTING BAY 2.
 THE DISCHARGE SHALL BE IN A LOCATION WHICH WOULD
 NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR
 MAINTENANCE PERSONEL. SECTION 1107.2.
  
 5. SHT 5.2 INDICATE THE ELEVATION OF THE ROOF LEVEL
 ALONG WITH THE ELEVATION OF THE PARAPET WALLS TO VERIFY
 VERTICAL CONTRIBUTION ADDED TO THE ROOF AREAS IN THE
 CALCULATIONS. SECTION 106.1.1.
  
 6. SHT A8.3 DETAIL #10 "TYPICAL OVERFLOW SCUPPER
 DETAIL". INDICATE MEASUREMENT FROM THE ROOF TO THE FLOW
 LINE OF THE OVERFLOW SCUPPER PER SECTION 1503.4.3.
 INDICATE THE HEIGHT & WIDTH OF THE SCUPPERS TO BE SIZED
 PER SECTIONS 1101.7, 1107.3 AND TABLE 1106.7.
  
 7. IRRIGATION PLANS AND PERMIT REQUIRED. SECTION
 106.3.5.1.3(9).
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]