| Date |
Text |
| 2006-10-13 07:50:45 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL ARCHITECTURAL SHEETS. THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER, (BUSINESS NUMBER), IS SHOWN AS |
| | DELINQUENT STATUS FOR THE ARCHITECTURAL BUSINESS. SEE |
| | ATTACHED SHEET. FAC 61G1-16.004(1) & FS 481.219. |
| | |
| | 2. SHT A1.1.4 IN THE REMOVAL OF ANY PART OF A SANITARY |
| | SYSTEM, DEAD ENDS ARE PROHIBITED. SECTION 704.5. ALL |
| | CAPPED PIPES SHALL NOT BE COVERED PRIOR TO INSPECTION. |
| | |
| | 3. SHT A2.2 SUBMIT CALCULATIONS FOR PRIMARY AND |
| | SECONDARY ROOF DRAINS PER SECTIONS 1106 & 1107 WITH ALL |
| | SUBSECTIONS. THIS IS FOR THE NEW ROOFS AND THE EXISTING |
| | ROOFS THAT HAVE ADDITIONAL ROOF AREA OR VERTICAL |
| | CONTRIBUTION ADDED TO TOTAL AREA TO BE DRAINED. |
| | CALCULATIONS SHALL SHOW THE ROOF AREA TO BE DRAINED TO |
| | EACH PRIMARY DRAIN, ALONG WITH 1/2 AREA OF ALL VERTICAL |
| | WALLS, INCLUDING PARAPETS, AS WELL AS ANY AREA OF A |
| | ROOF THAT DRAINS ONTO THE ROOF FROM ABOVE. INDICATE NEW |
| | ROOF AREA ADDED, AS THE "NEW ROOF" MAY JUST BE A NEW |
| | ROOF FOR EXISTING AREA AND SOME AREAS OF THE "NEW ROOF |
| | AREA" ARE NOT CLEAR. SECTION 106.1.1. |
| | |
| | 4. SHT A2.2 EXISTING SCUPPER LOCATED AT THE S.E. CORNER |
| | OF THE EXISTING BAY 2 ROOF IS NOT APPROVED FOR |
| | EMERGENCY OVERFLOW FOR THAT ROOF DRAIN, NOR FOR THE NEW |
| | ROOF DRAIN COVERING THE WALKWAY EAST OF EXISTING BAY 2. |
| | THE DISCHARGE SHALL BE IN A LOCATION WHICH WOULD |
| | NORMALLY BE OBSERVED BY THE BUILDING OCCUPANTS OR |
| | MAINTENANCE PERSONEL. SECTION 1107.2. |
| | |
| | 5. SHT 5.2 INDICATE THE ELEVATION OF THE ROOF LEVEL |
| | ALONG WITH THE ELEVATION OF THE PARAPET WALLS TO VERIFY |
| | VERTICAL CONTRIBUTION ADDED TO THE ROOF AREAS IN THE |
| | CALCULATIONS. SECTION 106.1.1. |
| | |
| | 6. SHT A8.3 DETAIL #10 "TYPICAL OVERFLOW SCUPPER |
| | DETAIL". INDICATE MEASUREMENT FROM THE ROOF TO THE FLOW |
| | LINE OF THE OVERFLOW SCUPPER PER SECTION 1503.4.3. |
| | INDICATE THE HEIGHT & WIDTH OF THE SCUPPERS TO BE SIZED |
| | PER SECTIONS 1101.7, 1107.3 AND TABLE 1106.7. |
| | |
| | 7. IRRIGATION PLANS AND PERMIT REQUIRED. SECTION |
| | 106.3.5.1.3(9). |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |