Plan Review Notes
Plan Review Notes For Permit 06070445
Permit Number 06070445
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2006-10-10 13:34:24***DENIED***
  
 1) LIFE SAFETY SHALL COMPLY WITH NFPA 101, 2003
 EDITION.
  
 2) CONSTRUCTION, ALTERATION AND DEMOLITION TO COMPLY
 WITH NFPA 241.
  
 3) HANDRAILS ARE REQUIRED ON BOTH SIDES OF STAIRS AND
 RAMPS.
  
 4) ADDRESSES ARE REQUIRED ON BUILDINGS AND SHALL BE A
 MINIMUM OF 6" IN HEIGHT, 1" WIDE AND CONTRASTING TO THE
 BACKGROUND.
  
 5) SEPARATE SHOP DRAWINGS AND PERMITS ARE REQUIRED FOR
 FIRE SPRINKLER AND FIRE ALARM REMODEL.
  
 6) FIRE ALARM TO BE UL CERTIFIED FOR CENTRAL STATION
 SERVICE.
  
 7) EXIT DOORS SHALL SWING IN THE DIRECTION OF TRAVEL
 WHEN SERVINGS AREAS OF OCCUPANT LOAD GREATER THAN 50.
  
 8) EMERGENCY ACCESS TO BUILDINGS SHALL BE MAINTAINED
 PRIOR TO, DURING AND AFTER CONSTRUCTION.
  
 9) 2A-10B,C RATED FIRE EXTINGUISHERS ARE REQUIRED AND
 SHALL BE MOUNTED AT DISTANCES NOT TO EXCEED 75'.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW (561) 805-6722